Plan Review Notes For Permit 15090654 |
Permit Number |
15090654 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-11-07 05:47:34 | 1)SUBMIT COMBUSTION AIR CALCULATIONS FOR ALL GAS | | APPLIANCES LOCATED ON THE INTERIOR OF THE STRUCTURE. | | COMPLY W/2010 FBC-RESIDENTIAL SEC.G2407.1 & G2407.5 | | THROUGH G2407.11. | | 2) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS. IT | | APPEARS ONLY ONE COPY HAS BEEN SUBMITTED. WPB AMEND. TO | | FBC SEC. 107.1. | | 3) THE SUBMITTED DOCUMENT FOR GAS COOKTOP DOES NOT SHOW | | THAT THE RANGE IS LISTED OR LABELED PER 2010 FBC-RES. | | SEC. G2404.3. THE SUBMITTED DOCUMENT IS NOTHING MORE | | THAN AN INTERNET SALES SHEET. | | 4) SUBMIT MANUF. SPECIFICATIONS FOR THE OPTIONAL GRILL. | | WPB AMEND. TO FBC SEC. 107.1. | | 5) THE INSTALLATION MANUALS FOR ALL GAS EQUIPMENT SHALL | | BE ONSITE FOR THE INSPECTOR PER THE 2010 FBC-RES. SEC. | | G 2408.1. | | 6) SUBMIT DETAILS FOR THE VENT FOR THE WATER HEATER IN | | THE GARAGE. INDICATE VENT TYPE, DIAMETER, ROOF | | PENETRATION AND HOW IT IS TO BE SEALED AT THE ROOF | | PENETRATION, ETC. COMPLY WITH 2010 FBC-RES.SECS.G2426 & | | G2427. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|