Plan Review Notes
Plan Review Notes For Permit 15090654
Permit Number 15090654
Review Stop G
Sequence Number 1
Notes
Date Text
2015-11-07 05:47:341)SUBMIT COMBUSTION AIR CALCULATIONS FOR ALL GAS
 APPLIANCES LOCATED ON THE INTERIOR OF THE STRUCTURE.
 COMPLY W/2010 FBC-RESIDENTIAL SEC.G2407.1 & G2407.5
 THROUGH G2407.11.
 2) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS. IT
 APPEARS ONLY ONE COPY HAS BEEN SUBMITTED. WPB AMEND. TO
 FBC SEC. 107.1.
 3) THE SUBMITTED DOCUMENT FOR GAS COOKTOP DOES NOT SHOW
 THAT THE RANGE IS LISTED OR LABELED PER 2010 FBC-RES.
 SEC. G2404.3. THE SUBMITTED DOCUMENT IS NOTHING MORE
 THAN AN INTERNET SALES SHEET.
 4) SUBMIT MANUF. SPECIFICATIONS FOR THE OPTIONAL GRILL.
 WPB AMEND. TO FBC SEC. 107.1.
 5) THE INSTALLATION MANUALS FOR ALL GAS EQUIPMENT SHALL
 BE ONSITE FOR THE INSPECTOR PER THE 2010 FBC-RES. SEC.
 G 2408.1.
 6) SUBMIT DETAILS FOR THE VENT FOR THE WATER HEATER IN
 THE GARAGE. INDICATE VENT TYPE, DIAMETER, ROOF
 PENETRATION AND HOW IT IS TO BE SEALED AT THE ROOF
 PENETRATION, ETC. COMPLY WITH 2010 FBC-RES.SECS.G2426 &
 G2427.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  