Plan Review Notes
Plan Review Notes For Permit 15090611
Permit Number 15090611
Review Stop B
Sequence Number 4
Notes
Date Text
2016-02-27 08:28:45BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090611
 ADD: 4912 S DIXIE
 CONT: LEIGHTON MCGINN
 TEL: (561)863-4455
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: SAT. FEB. 27/ 2016
 ACTION: DENIED
  
 NOTE: NEW DESIGN. THE RESPONSE COMMENTS INDICATE THE
 PLANNED CONCEPT HAS CHANGED, THE ADDITION OF A
 MEZZANINE LEVEL AND WORK WITHIN THE 2ND FLOOR R3
 OCCUPANCY. THE CONTRACTOR HAS NOT SHOWN AN INCREASE IN
 SCOPE ON THE APPLICATION NOR HAS THE DOLLAR AMOUNT
 INCREASE FOR THE ADDITIONAL WORK!!!!!
  
 1-5) COMPLIED
  
 6) 2ND REQUEST. THE SHEET A5.1 THE CLEAR STORY WINDOWS
 HAVE BEEN REMOVED FROM THE PLANS. ON SHEET A1.1 THE
 NORTH CLEAR STORY WINDOWS STILL SHOW ON THE PLANS AS
 WELL DOES A NOTE FOR THESE WINDOWS ON THE WEST AND
 NORTH FACES OF THE BUILDING. THE STRUCTURAL SHEET S-1
 HAS NOT BEEN UPDATED AND THE CLEAR STORY WINDOWS
 REMOVED. 2014 FBC-B TABLE 602 & 705.8.4
 FROM THE PREVIOUS ROUND OF REVIEWS. SHEET LS1 THE CODE
 ANALYSIS WILL NEED TO PROVIDE THE TRIBUTARY AREA OF
 WALL AREA BEING CONSIDERED, FACING THE NORTH ELEVATION.
 IT APPEARS THERE IS APPROXIMATELY 508 SQ. FT. OF WALL
 AREA, (DO NOT INCLUDE PARAPET ABOVE THE ROOF LINE). 10%
 OF THE WALL WOULD ALLOW 50.8 SQ. FT. OF UNPROTECTED
 OPENINGS. FOR ADDITIONAL OPENINGS SEE FBC-B 705.8.4 FOR
 MIXED OPENINGS.
 2014 FBC-B TABLE 602 FOR 10 FEET OR LESS REQUIRES A 1
 HOUR FIRE RATED WALL AND PLEASE REVIEW ALLOWABLE
 OPENINGS IN TABLE 705.8 PROVIDE THE PERCENTAGE OF
 OPENINGS INDICATED IN THE NORTH WALL.
  
 7)COMPLIED. THIS DETAIL MAY ALSO BE USED FOR OTHER THAN
 THE CLEAR STORY WINDOWS UNDER NEW OPENINGS IN EXISTING
 WALLS.
  
 8-9) COMPLIED. SHEET A11.0 THE ROOF AND WALL PRESSURES
 ARE TAKEN AT 20 FEET PLEASE REVIEW SHEETS A5.0 AND A5.1
 INDICATE THE ROOF HEIGHT AT 22FEET.
  
 10) SEMI- COMPLIED. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3.
  
 SUBMITTED PRODUCTS WITH (2) SETS OF PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD:
 TRULITE 3000 REGISTER STOREFRONT L.M.I. NOA 14-0203.01
 NANA WALL SL-73 OUTSWING FOLDING DOORS L.M.I. NOA
 15-0226.05
 SCHAUGE LOCK CO. NOA 13-1217.16
 OVERHEAD DOOR CORP. NOA 13-1121.06
 MAXIM INDUSTRIES DCM CURB MOUNT SKYLIGHT NOA 14-0318.01
 TREMCO MODIFIED BITUMEN NOA 11-0301.02
  
 SUBMITTED PRODUCT WITH (2) SETS OF PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD:
 THYBAR TC-5 STEEL ROOF CURB FOR CARRIER ROOFTOP UNITS
 NOA15-0218.11, PLEASE NOTE TECH PAGE 5 OF 5. RESTRAINT
 BRACKET QUANTITY IS DETERMINED BY PROJECT SPECIFIC
 CALCULATIONS, PERFORMED BY A FLORIDA LICENSED PE OR
 FLORIDA REGISTERED ARCHITECT THAT CONSIDER THE UNIQUE
 COMBINATION OF THE UNIT SIZE AND APPLICABLE LATERAL AND
 UPLIFT PRESSURES FOR EACH JOB. PLEASE PROVIDE
 CALCULATION FOR HOW MANY BRACKETS WILL BE NEEDED FOR
 EACH TYPE OF UNIT.
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 SUBMITTED PRODUCTS WITH (1) SET OF PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD:
 FL16132-R1 TM WINDOWS/ CASEMENT
 FL16921-R2 PRECESION ALUMINUM PRODUCTS -PRE-ENGINEERED
 A/C STANDS
 FL16554-R3 YKK AP AMERICA SWINGING EXTERIOR DOOR
 ASSEMBLIES
  
 11) COMPLIED. REQUIREMENT FOR AT LEAST ONE WINDOW IN
 EACH SLEEPING ROOM COMPLY WITH 1029.1 & 1029.2.
  
 12-16) COMPLIED.
  
 17-18) COMPLIED. 61G15-23.001 / 61G15-23.002(2) FL.
 ADMINISTRATIVE CODE.
  
 19) COMPLIED. IMPACT FEES.
  
 20) NEW COMMENT, THE SHEET S1.0 AND S2.0 DRAWINGS HAVE
 NOT BEEN UPDATED TO THE NEW WINDOW AND DOOR LAYOUT.
 THEY STILL SHOW THE CLEAR STORY OPENINGS, THE OTHER
 ISSUE IS IN THE SOUTHEAST AREA OF THE 2 STORY PORTION
 OF THE BUILDING, THE STRUCTURAL SHEETS HAVE NOT BEEN
 UPDATED TO REFLECT THE NEW WINDOW AND DOOR LAYOUT ON
 THE 1ST AND 2ND FLOOR. DISCREPANCY IN PLANS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 21)NEW COMMENT. SHEET A1.6 ROOF TOP PLAN. ON THE NEW
 MEZZANINE LEVEL THE PLANS SHOW AN EXTERIOR DOOR THAT
 CAN BE USED TO GAIN ACCESS FOR SERVICING AND OR
 REPLACEMENT OF ROOF TOP MECHANICAL EQUIPMENT BUT THE
 PLANS DO NOT SHOW HOW ACCESS TO THE 2ND STORY ROOF FOR
 SERVICING OF THE MECHANICAL ROOF TOP EQUIPMENT.
 2014 FBC-B ? 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN
 6-INCHES (152 MM) DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2).
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610
 MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR
 SERVICE PLATFORMS .
  
 22) NEW COMMENT. SHEET A11.0 SHOWS VARIOUS DETAILS FOR
 ROOF TOP MECHANICAL EQUIPMENT AND SKYLIGHT ATTACHMENTS
 BUT THESE ARE GENERAL DETAILS. THERE ARE NO STRUCTURAL
 DETAILS PROVIDING THE SIZE OF MATERIALS,
 IF CURBS ARE TO BE WELDED TO STRUCTURAL MEMBERS, SCREED
 OR BOLTED. THERE ARE ALSO NO DETAILS OF HOW THE ROOF
 TOP A/C UNITS WILL BE ANCHORED. 2014 FBC-M - 301.15
 WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
  
 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  