2016-02-27 08:28:45 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15090611 |
| ADD: 4912 S DIXIE |
| CONT: LEIGHTON MCGINN |
| TEL: (561)863-4455 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 4TH REVIEW |
| DATE: SAT. FEB. 27/ 2016 |
| ACTION: DENIED |
| |
| NOTE: NEW DESIGN. THE RESPONSE COMMENTS INDICATE THE |
| PLANNED CONCEPT HAS CHANGED, THE ADDITION OF A |
| MEZZANINE LEVEL AND WORK WITHIN THE 2ND FLOOR R3 |
| OCCUPANCY. THE CONTRACTOR HAS NOT SHOWN AN INCREASE IN |
| SCOPE ON THE APPLICATION NOR HAS THE DOLLAR AMOUNT |
| INCREASE FOR THE ADDITIONAL WORK!!!!! |
| |
| 1-5) COMPLIED |
| |
| 6) 2ND REQUEST. THE SHEET A5.1 THE CLEAR STORY WINDOWS |
| HAVE BEEN REMOVED FROM THE PLANS. ON SHEET A1.1 THE |
| NORTH CLEAR STORY WINDOWS STILL SHOW ON THE PLANS AS |
| WELL DOES A NOTE FOR THESE WINDOWS ON THE WEST AND |
| NORTH FACES OF THE BUILDING. THE STRUCTURAL SHEET S-1 |
| HAS NOT BEEN UPDATED AND THE CLEAR STORY WINDOWS |
| REMOVED. 2014 FBC-B TABLE 602 & 705.8.4 |
| FROM THE PREVIOUS ROUND OF REVIEWS. SHEET LS1 THE CODE |
| ANALYSIS WILL NEED TO PROVIDE THE TRIBUTARY AREA OF |
| WALL AREA BEING CONSIDERED, FACING THE NORTH ELEVATION. |
| IT APPEARS THERE IS APPROXIMATELY 508 SQ. FT. OF WALL |
| AREA, (DO NOT INCLUDE PARAPET ABOVE THE ROOF LINE). 10% |
| OF THE WALL WOULD ALLOW 50.8 SQ. FT. OF UNPROTECTED |
| OPENINGS. FOR ADDITIONAL OPENINGS SEE FBC-B 705.8.4 FOR |
| MIXED OPENINGS. |
| 2014 FBC-B TABLE 602 FOR 10 FEET OR LESS REQUIRES A 1 |
| HOUR FIRE RATED WALL AND PLEASE REVIEW ALLOWABLE |
| OPENINGS IN TABLE 705.8 PROVIDE THE PERCENTAGE OF |
| OPENINGS INDICATED IN THE NORTH WALL. |
| |
| 7)COMPLIED. THIS DETAIL MAY ALSO BE USED FOR OTHER THAN |
| THE CLEAR STORY WINDOWS UNDER NEW OPENINGS IN EXISTING |
| WALLS. |
| |
| 8-9) COMPLIED. SHEET A11.0 THE ROOF AND WALL PRESSURES |
| ARE TAKEN AT 20 FEET PLEASE REVIEW SHEETS A5.0 AND A5.1 |
| INDICATE THE ROOF HEIGHT AT 22FEET. |
| |
| 10) SEMI- COMPLIED. 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3. |
| |
| SUBMITTED PRODUCTS WITH (2) SETS OF PRODUCT APPROVALS |
| REVIEWED BY DESIGNER OF RECORD: |
| TRULITE 3000 REGISTER STOREFRONT L.M.I. NOA 14-0203.01 |
| NANA WALL SL-73 OUTSWING FOLDING DOORS L.M.I. NOA |
| 15-0226.05 |
| SCHAUGE LOCK CO. NOA 13-1217.16 |
| OVERHEAD DOOR CORP. NOA 13-1121.06 |
| MAXIM INDUSTRIES DCM CURB MOUNT SKYLIGHT NOA 14-0318.01 |
| TREMCO MODIFIED BITUMEN NOA 11-0301.02 |
| |
| SUBMITTED PRODUCT WITH (2) SETS OF PRODUCT APPROVALS |
| REVIEWED BY DESIGNER OF RECORD: |
| THYBAR TC-5 STEEL ROOF CURB FOR CARRIER ROOFTOP UNITS |
| NOA15-0218.11, PLEASE NOTE TECH PAGE 5 OF 5. RESTRAINT |
| BRACKET QUANTITY IS DETERMINED BY PROJECT SPECIFIC |
| CALCULATIONS, PERFORMED BY A FLORIDA LICENSED PE OR |
| FLORIDA REGISTERED ARCHITECT THAT CONSIDER THE UNIQUE |
| COMBINATION OF THE UNIT SIZE AND APPLICABLE LATERAL AND |
| UPLIFT PRESSURES FOR EACH JOB. PLEASE PROVIDE |
| CALCULATION FOR HOW MANY BRACKETS WILL BE NEEDED FOR |
| EACH TYPE OF UNIT. |
| 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| SUBMITTED PRODUCTS WITH (1) SET OF PRODUCT APPROVALS |
| REVIEWED BY DESIGNER OF RECORD: |
| FL16132-R1 TM WINDOWS/ CASEMENT |
| FL16921-R2 PRECESION ALUMINUM PRODUCTS -PRE-ENGINEERED |
| A/C STANDS |
| FL16554-R3 YKK AP AMERICA SWINGING EXTERIOR DOOR |
| ASSEMBLIES |
| |
| 11) COMPLIED. REQUIREMENT FOR AT LEAST ONE WINDOW IN |
| EACH SLEEPING ROOM COMPLY WITH 1029.1 & 1029.2. |
| |
| 12-16) COMPLIED. |
| |
| 17-18) COMPLIED. 61G15-23.001 / 61G15-23.002(2) FL. |
| ADMINISTRATIVE CODE. |
| |
| 19) COMPLIED. IMPACT FEES. |
| |
| 20) NEW COMMENT, THE SHEET S1.0 AND S2.0 DRAWINGS HAVE |
| NOT BEEN UPDATED TO THE NEW WINDOW AND DOOR LAYOUT. |
| THEY STILL SHOW THE CLEAR STORY OPENINGS, THE OTHER |
| ISSUE IS IN THE SOUTHEAST AREA OF THE 2 STORY PORTION |
| OF THE BUILDING, THE STRUCTURAL SHEETS HAVE NOT BEEN |
| UPDATED TO REFLECT THE NEW WINDOW AND DOOR LAYOUT ON |
| THE 1ST AND 2ND FLOOR. DISCREPANCY IN PLANS. 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 21)NEW COMMENT. SHEET A1.6 ROOF TOP PLAN. ON THE NEW |
| MEZZANINE LEVEL THE PLANS SHOW AN EXTERIOR DOOR THAT |
| CAN BE USED TO GAIN ACCESS FOR SERVICING AND OR |
| REPLACEMENT OF ROOF TOP MECHANICAL EQUIPMENT BUT THE |
| PLANS DO NOT SHOW HOW ACCESS TO THE 2ND STORY ROOF FOR |
| SERVICING OF THE MECHANICAL ROOF TOP EQUIPMENT. |
| 2014 FBC-B ? 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS |
| OR ELEVATED STRUCTURES. |
| WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON |
| ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN |
| 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED |
| ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN |
| CRITERIA: |
| 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR |
| ROOF EDGE NOT LESS THAN 30 INCHES (762 MM). |
| 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 |
| INCHES (356 MM) ON CENTER. |
| 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN |
| 6-INCHES (152 MM) DEEP. |
| 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM) |
| BETWEEN RAILS. |
| 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM) |
| DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND |
| (136.1 KG) LOAD. |
| 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE |
| PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF |
| WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2). |
| 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY |
| APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE |
| REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610 |
| MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR |
| SERVICE PLATFORMS . |
| |
| 22) NEW COMMENT. SHEET A11.0 SHOWS VARIOUS DETAILS FOR |
| ROOF TOP MECHANICAL EQUIPMENT AND SKYLIGHT ATTACHMENTS |
| BUT THESE ARE GENERAL DETAILS. THERE ARE NO STRUCTURAL |
| DETAILS PROVIDING THE SIZE OF MATERIALS, |
| IF CURBS ARE TO BE WELDED TO STRUCTURAL MEMBERS, SCREED |
| OR BOLTED. THERE ARE ALSO NO DETAILS OF HOW THE ROOF |
| TOP A/C UNITS WILL BE ANCHORED. 2014 FBC-M - 301.15 |
| WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND |
| SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND |
| INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN |
| ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |