2016-01-11 08:14:183RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090611
 01/11/16
  
 1) SHEET M6.1: THE AIR BALANCE SCHEDULE DOES NOT
 INCLUDE THE MAKE-UP AIR AND EXHAUST CFM'S FOR THE
 KITCHEN HOOD.
 2) M6.1: AN ENERGY RECOVERY VENTILATION SYSTEM IS
 REQUIRED FOR THE OARTU-1 SERVING THE STUDIO/KITCHEN
 AREA- SEE TABLE C403.2.6 FBC-14 ENERGY CONSERVATION AND
 REVISE THE PLANS TO SHOW COMPLIANCE.
 3) M2.1: PLACE A DUCT SMOKE DETECTOR SYMBOL IN THE
 RETURN AIR SYSTEM OF RTU-1 IN ACCORDANCE WITH SECTION
 606.2.1 FBC-14 MECHANICAL.
 4) THE REVISED ENERGY CALCULATION FORM 506-2014 DOES
 NOT INCLUDE COMPLIANCE DATA FOR THE RTU'S OR AHU-1.
 5) CLARIFY IF EXHAUST SYSTEMS WILL BE PROVIDED FOR ANY
 OF THE PAPER MAKING EQUIPMENT AND PROVIDE DETAILS ON
 THE PLAN.
 6) M2.1 & M2.2: SHOW ACCESS PANEL LOCATIONS AND
 DIMENSIONS FOR AHU'S- 1 & 2: SEE SECTION 306.1.
 7) M2.3: PLEASE LABEL ON ROOF TOP EQUIPMENT SHOWN ON
 THE PLAN.
 8) PROVIDE A SUBMITTAL FOR THE RTU AND OARTU CURBS
 REVIEWED AND APPROVED BY THE ENGINEER OF RECORD, AND
 REVISE SHEET S7.0 TO SHOW DETAILS FOR ATTACHING THE
 UNITS TO THE CURBS.
  