Plan Review Notes
Plan Review Notes For Permit 15090611
Permit Number 15090611
Review Stop E
Sequence Number 3
Notes
Date Text
2016-01-26 19:02:54YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS. THESE PLANS HAVE BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE) AND THE FBC, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS IN EFFECT AT THE TIME OF SUBMITTAL.
  
 THE ELECTRICAL SHEET INDEX ON PAGE E0.1 INDICATES THAT
 CHANGES WERE ONLY MADE TO SHEETS E2.2 & E3.2. THE
 UNMENTIONED REVISION OF SHEET E2.1 PROMPTED ME TO
 CONDUCT A COMPLETE REVIEW OF THE PLANS TO CHECK FOR
 ADDITIONAL UNANNOUNCED CHANGES TO THE PLANS. BELOW ARE
 MY REMARKS TO YOUR RESPONSES ALONG WITH THE COMMENTS OF
 THIS REVIEW.
  
 1. CORRECT ELECTRICAL SPECIFICATIONS P & Q TO READ
 FBC-EC405.7.3.2 AND FBC-EC405.7.3.1 RESPECTIVELY.
 2. CORRECT GENERAL NOTES COMMERCIAL LIGHTING REFERENCE
 TO READ FBC-EC405.
 3. SEE THE REMARKS TO YOUR RESPONSES:
  
 COMMENT 1: FIXTURE SCHEDULE OR LEGEND SHALL BE REVISED
 TO MATCH THE FLOOR PLANS MARKINGS. IT SHALL CLEARLY
 INDICATE THE EMERGENCY LIGHTING AS REQUIRED.
  
 THE LACK OF LUMINAIRE DATA MAKES IDENTIFICATION
 DIFFICULT, SO AS A NOTE ADHERE TO THE FBC-E C402.4.8
 RECESSED LIGHTING. RECESSED LIGHTING INSTALLED IN THE
 BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND BE
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED &
 UNCONDITIONED SPACES.
  
 COMMENT 2: ALL LIGHTING SHALL COMPLY WITH THE ENERGY
 CONSERVATION REQUIREMENTS FOR THE FBC.
  
 TO COMPLY WITH THE ENERGY CODE YOU SHALL SUBMIT A LIGHT
 DENSITY ALLOWANCE CHART SHOWING COMPLIANCE WITHIN THE
 ALLOWABLE LIGHTING ENERGY.
  
 COMMENT 3: PROVIDE A LIGHTING PLAN FOR THE 2ND FLOOR
 AREA. INCLUDE THE STAIRWAY ILLUMINATION AND SWITCHING
 REQUIREMENTS.
  
 THE SECOND FLOOR IS MISSING THE REQUIRED EXIT LIGHTS TO
 INDICATE THE PATH OF EGRESS. THE SECOND FLOOR IS
 MISSING THE REQUIRED EMERGENCY LIGHTING. THE STAIRWAY
 HAS NO ILLUMINATION AS REQUIRED BY BOTH FBC & NEC.
  
 COMMENT 4: NEC 210.62 HAS SPECIFIC SHOW WINDOW LIGHTING
 REQUIREMENTS NOT ALL OF WHICH HAVE BEEN COMPLIED WITH.
 YOU SHALL PROVIDE A SHOW WINDOW OUTLET FOR EVERY 12
 LINEAR FOOT OR PORTION THEREFOF. NOT JUST A SELECTED
 SET OF WINDOWS.
  
 COMPLIED
  
 COMMENT 5: NEC 600.5 HAS SPECIFIC REQUIREMENTS FOR SIGN
 OUTLETS. IT CALLS FOR A DEDICATED SIGN OUTLET AT EVERY
 PEDESTRIAN ENTRY TO EVERY COMMERCIAL ESTABLISHMENT.
 THAT DOES NOT MEAN JUST THE FRONT/MAIN DOOR.
  
 YOU ARE TO PROVIDE THE REQUIRED SIGN OUTLETS, BUT FLOOR
 OUTLETS WERE NEVER MENTIONED FOR SIGNAGE.
  
 COMMENT 6: PROVIDE A POWER PLAN FOR THE 2ND FLOOR AREA.
  
 NEC 210.52 HAS SPECIFIC REQUIREMENTS FOR OUTLET
 PLACEMENTS. CHECK THE OUTLETS IN THE KITCHEN COUNTER
 AND BEDROOM 204. YOU INDICATE THE UPSTAIRS AHU AS BEING
 INSIDE THE ATTIC NEC 110.33(B) REQUIRES THAT THERE BE A
 PERMANENT LADDER TO ACCESS THE UNIT. FURTHERMORE, YOU
 ARE REQUIRED TO HAVE A SERVICE OUTLET AND PROPER
 LIGHTING. ALL RECEPTACLES IN THE SECOND FLOOR DWELLING
 SHALL BE TAMPER-RESISTANT AND BE AFCI PROTECTED AS
 INDICATED BY NEC 210.12
  
 COMMENT 7: SHOW ON THE FLOOR PLAN THE ELECTRICAL
 OUTLETS OR POWER SOURCE FOR ALL THE WORK TABLES OR
 STATIONS.
  
 COMPLIED
  
 COMMENT 8: THE ADDITIONAL OUTLET WILL AFFECT THE
 ELECTRICAL LOAD CALCS AND MAYBE THE RISER DIAGRAM.
 CORRECT THOSE ACCORDINGLY.
  
 COMPLIED
  
 4. IN ADDITION TO THE ABOVE, THERE DOES NOT APPEAR TO
 BE AMPLE LIGHTING ABOUT THE ELECTRICAL PANELS. NEC
 110.26(D) REQUIRES THAT THERE BE AMPLE LIGHTING.
 5. THERE ARE STILL MISSING EXIT SIGNS TO INDICATE THE
 PATHS OF EGRESS.
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  