2016-01-26 19:02:54 | YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED |
| DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL |
| REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED |
| BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO |
| SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE |
| REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION |
| OF ANY PREVIOUS COMMENTS. THESE PLANS HAVE BEEN |
| REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| (NATIONAL ELECTRICAL CODE) AND THE FBC, (FLORIDA |
| BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| AMENDMENTS IN EFFECT AT THE TIME OF SUBMITTAL. |
| |
| THE ELECTRICAL SHEET INDEX ON PAGE E0.1 INDICATES THAT |
| CHANGES WERE ONLY MADE TO SHEETS E2.2 & E3.2. THE |
| UNMENTIONED REVISION OF SHEET E2.1 PROMPTED ME TO |
| CONDUCT A COMPLETE REVIEW OF THE PLANS TO CHECK FOR |
| ADDITIONAL UNANNOUNCED CHANGES TO THE PLANS. BELOW ARE |
| MY REMARKS TO YOUR RESPONSES ALONG WITH THE COMMENTS OF |
| THIS REVIEW. |
| |
| 1. CORRECT ELECTRICAL SPECIFICATIONS P & Q TO READ |
| FBC-EC405.7.3.2 AND FBC-EC405.7.3.1 RESPECTIVELY. |
| 2. CORRECT GENERAL NOTES COMMERCIAL LIGHTING REFERENCE |
| TO READ FBC-EC405. |
| 3. SEE THE REMARKS TO YOUR RESPONSES: |
| |
| COMMENT 1: FIXTURE SCHEDULE OR LEGEND SHALL BE REVISED |
| TO MATCH THE FLOOR PLANS MARKINGS. IT SHALL CLEARLY |
| INDICATE THE EMERGENCY LIGHTING AS REQUIRED. |
| |
| THE LACK OF LUMINAIRE DATA MAKES IDENTIFICATION |
| DIFFICULT, SO AS A NOTE ADHERE TO THE FBC-E C402.4.8 |
| RECESSED LIGHTING. RECESSED LIGHTING INSTALLED IN THE |
| BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND BE |
| SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED & |
| UNCONDITIONED SPACES. |
| |
| COMMENT 2: ALL LIGHTING SHALL COMPLY WITH THE ENERGY |
| CONSERVATION REQUIREMENTS FOR THE FBC. |
| |
| TO COMPLY WITH THE ENERGY CODE YOU SHALL SUBMIT A LIGHT |
| DENSITY ALLOWANCE CHART SHOWING COMPLIANCE WITHIN THE |
| ALLOWABLE LIGHTING ENERGY. |
| |
| COMMENT 3: PROVIDE A LIGHTING PLAN FOR THE 2ND FLOOR |
| AREA. INCLUDE THE STAIRWAY ILLUMINATION AND SWITCHING |
| REQUIREMENTS. |
| |
| THE SECOND FLOOR IS MISSING THE REQUIRED EXIT LIGHTS TO |
| INDICATE THE PATH OF EGRESS. THE SECOND FLOOR IS |
| MISSING THE REQUIRED EMERGENCY LIGHTING. THE STAIRWAY |
| HAS NO ILLUMINATION AS REQUIRED BY BOTH FBC & NEC. |
| |
| COMMENT 4: NEC 210.62 HAS SPECIFIC SHOW WINDOW LIGHTING |
| REQUIREMENTS NOT ALL OF WHICH HAVE BEEN COMPLIED WITH. |
| YOU SHALL PROVIDE A SHOW WINDOW OUTLET FOR EVERY 12 |
| LINEAR FOOT OR PORTION THEREFOF. NOT JUST A SELECTED |
| SET OF WINDOWS. |
| |
| COMPLIED |
| |
| COMMENT 5: NEC 600.5 HAS SPECIFIC REQUIREMENTS FOR SIGN |
| OUTLETS. IT CALLS FOR A DEDICATED SIGN OUTLET AT EVERY |
| PEDESTRIAN ENTRY TO EVERY COMMERCIAL ESTABLISHMENT. |
| THAT DOES NOT MEAN JUST THE FRONT/MAIN DOOR. |
| |
| YOU ARE TO PROVIDE THE REQUIRED SIGN OUTLETS, BUT FLOOR |
| OUTLETS WERE NEVER MENTIONED FOR SIGNAGE. |
| |
| COMMENT 6: PROVIDE A POWER PLAN FOR THE 2ND FLOOR AREA. |
| |
| NEC 210.52 HAS SPECIFIC REQUIREMENTS FOR OUTLET |
| PLACEMENTS. CHECK THE OUTLETS IN THE KITCHEN COUNTER |
| AND BEDROOM 204. YOU INDICATE THE UPSTAIRS AHU AS BEING |
| INSIDE THE ATTIC NEC 110.33(B) REQUIRES THAT THERE BE A |
| PERMANENT LADDER TO ACCESS THE UNIT. FURTHERMORE, YOU |
| ARE REQUIRED TO HAVE A SERVICE OUTLET AND PROPER |
| LIGHTING. ALL RECEPTACLES IN THE SECOND FLOOR DWELLING |
| SHALL BE TAMPER-RESISTANT AND BE AFCI PROTECTED AS |
| INDICATED BY NEC 210.12 |
| |
| COMMENT 7: SHOW ON THE FLOOR PLAN THE ELECTRICAL |
| OUTLETS OR POWER SOURCE FOR ALL THE WORK TABLES OR |
| STATIONS. |
| |
| COMPLIED |
| |
| COMMENT 8: THE ADDITIONAL OUTLET WILL AFFECT THE |
| ELECTRICAL LOAD CALCS AND MAYBE THE RISER DIAGRAM. |
| CORRECT THOSE ACCORDINGLY. |
| |
| COMPLIED |
| |
| 4. IN ADDITION TO THE ABOVE, THERE DOES NOT APPEAR TO |
| BE AMPLE LIGHTING ABOUT THE ELECTRICAL PANELS. NEC |
| 110.26(D) REQUIRES THAT THERE BE AMPLE LIGHTING. |
| 5. THERE ARE STILL MISSING EXIT SIGNS TO INDICATE THE |
| PATHS OF EGRESS. |
| |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE |
| NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |