Date Text
2015-11-21 06:20:051) SHT. A6.0 - DETAIL #4 REFERS TO OUTDOOR SEATING.THE
 OCCUPANT LOAD SHALL BE INCLUDED IN THE TOTAL OCCUPANT
 LOAD.SHOW THE MAXIMUM HEIGHT OF THE COUNTER.
 2) THE WASHING MACHINE SHALL BE INSTALLED ON A MINIMUM
 3 INCH WASTE STACK PER 2014 FBC-PLUMBING SEC.406.
 3) AS DRAWN, A DRINKING FOUNTAIN IS INSTALLED ON A
 HORIZONTAL WET VENT WHICH IS PROHIBITED PER SEC.912.1
 OF FBCP. THE DRINKING FOUNTAIN MUST CCONNECT TO THE
 BUILDING DRAIN DOWNSTREAM OF THE WATER CLOSET IN
 T.R.#105.
 4) THE BRANCH DRAIN FOR THE SINKS, FLOOR DRAINS AND
 WASHING MACHINE CANNOT BE ON A WET VENT PER FBCP SEC.
 912.1.THE BRANCH DRAIN SHALL CONNECT TO THE BUILDING
 DRAIN DOWNSTREAM OF THE WATER CLOSET IN T.R.#105.
 5) A SERVICE SINK IS REQUIRED PER 2014 FBCP TABLE
 403.1.
 6) A GREASE TRAP IS REQUIRED PER 2014 FBCP SEC.
 1003.3.1.
 7) SUBMIT A DETAIL OF THE CONDENSATE DRYWELL AND
 PIPING. WPB AMEND. TO FBC SEC. 107.2.1.
 8) HOT WATER SHALL BE SUPPLIED TO ALL FIXTURES USED FOR
 CULINARY,CLEANINSING, LAUNDRY, OR BUILDING MAINTENANCE
 PURPOSES PER FBCP SEC.607.1. SEE SK-2 AND IT SHALL BE
 SUPPLIED TO THE SERVICE SINK.
 9) SIZE THE WATER SUPPLY LINES TO ALL FIXTURES ON THE
 WATER RISER. ( WASHER, SK-3, EWH, TOILRT ROOMS, SK-2)
  