Plan Review Notes For Permit 15090611 |
Permit Number |
15090611 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-12-02 10:43:07 | PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED. | | IN ADDITON INCLUDE EXHAUST FAN DRAWINGS ON MASTER | | BUILDING SET OF PLANS. | | PLANS SHOW NO WORK IN RESIDENTIAL SPACE ON FLOOR 2, | | THIS IS CONTRADICTED BY DEMO PLANS. | | WINDOWS BY NEW STAIR LOCATION WILL REQUIRE FIRE RATING. | | 12/2/2015, LINDOW | | | | PREVIOUS COMMENTS FOR REFERENCE. | | DEFINE INTENDED USE OFCSTUDIO 102 | | PROVIDE FIRE RATING DETAIL FOR SECOND FLOOR | | RESIDENTIAL. | | PROVIDE DEMOLITION PLANS. | | SEPARATE DRAWINGS AND PERMIT REQUIRED FOR EXHAUST HOOD | | AND FIRE SUPPRESSION SYSTEM. | | 9/17/15 LINDOW |
|