Plan Review Notes
Plan Review Notes For Permit 15090611
Permit Number 15090611
Review Stop B
Sequence Number 1
Notes
Date Text
2015-09-24 14:07:59BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090611
 ADD: 4912 S DIXIE
 CONT: LEIGHTON MCGINN
 TEL: (561)863-4455
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. SEPT. 24/ 2015
 ACTION: DENIED
  
 1) THE SHEET LS.1 LIST THE BUILDING TYPE AS A VB-
 UNSPRINKLERED. THE OCCUPANCY TYPES LISTED ARE ASSEMBLY,
 BUSINESS & RESIDENTIAL BUT THE PLANS DO NOT INDICATE
 THE SQUARE FOOTAGE OF EACH OF THE OCCUPANCIES AND
 COMPLIANCE WITH 2014 FBC-B 508.2.1 AREA LIMITATIONS /
 MIXED OCCUPANCIES.
  
 2)SHEET LS1 DOES NOT LIST IF THE BUILDING WAS DESIGNED
 AS SEPERATED OR NON-SEPARATED OCCUPANCIES BETWEEN THE
 ASSEMBLY AND BUSINESS OCCUPANCIES. 508.4.4 SEPARATE
 OCCUPANCIES OR 508.3.3 NON-SEPARATED.
  
 3) SHEET LS1 ALSO LIST A RESIDENTIAL R2 OCCUPANCY BUT
 APPEARS TO BE A SINGLE DWELLING UNIT WITH 2 BEDROOMS.
 NOTE WHEN YOU LOOK AT SECTION 310.4 R2 IT IS FOR MORE
 THAN EITHER 2 SLEEPING UNITS OR 2 DWELLING UNITS. THE
 RESIDENTIAL UNIT ON THE 2ND FLOOR IS ACTUALLY A R3,
 PRIMARILY PERMANENT IN NATURE AND NOT CLASSIFIED AS
 GROUP R-1, R-2, R-4 OR I. NOTE THIS IS A MIXED USE
 OCCUPANCY, THE RESIDENTIAL UNIT IS CONSIDERED A R3.
  
 4) SHEET LS1 LIST TABLE 601 FIRE RESISTANCE RATINGS FOR
 BUILDING ELEMENTS, TYPE 5B UNDER THE FLOOR ELEMENT
 THERE IS NO REQUIREMENT FOR FIRE RATING BUT THERE IS NO
 MENTION IN THE CODE DATE REQUIREMENTS FOR HORIZONTAL
 ASSEMBLIES BETWEEN FIRE AREAS ( OCCUPANCIES) SEE TABLE
 707.3.10 (2 HR.) BETWEEN BUSINESS AND RESIDENTIAL.
  
 5) DISCREPANCY IN PLANS, UNDER PERMIT 15070711/
 REVISION 15080905 SHEET D1.1 NOTE # 23 INDICATED A
 SECTION OF ROOFINGAND ROOF STRUCTUREALONG WITH WOOD
 FRAMING STRUCTURE, INCLUDES PLASTER AND FRAMING. SHEET
 A1.2 THE SECOND FLOOR PLAN & ROOF PLAN NOTE # 4 ROOF TO
 REMAIN. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
 SHEET A6.0 DETAIL # 2 DOES NOT INDICATE WHAT TYPE OF
 ROOF FRAMING IS LOCATED IN THE SOUTH PORTION OF THE ONE
 STORY BUILDING.
  
 6) SHEET LS1 THE CODE ANALYSIS DOES NOT PROVIDE ANY
 INFORMATION FOR THE NORTH WALL OF THE BUILDING OR THE
 REQUIRED FIRE RATING SEE 2014 FBC-B TABLE 602 FOR 10
 FEET OR LESS REQUIRES A 1 HOUR FIRE RATED WALL AND
 PLEASE REVIEW ALLOWABLE OPENINGS IN TABLE 705.8 PROVIDE
 THE PER CENTAGE OF OPENINGS INDICATED IN THE NORTH
 WALL.
  
 7) SHEET LS1 THE NORTH & WEST WALLS INDICATES NEW
 WINDOW OPENINGS (NOTE # 3) WITHIN THE BLOCK WALL BUT
 THERE ARE NO DETAILS AS TOHOW THE BLOCK ABOVE THE NEW
 OPENING WILL BE HELD IN PLACE. NO LINTELS OR BEAMS AND
 COLUMNS FOUND ON SHEET A11.0. PART OF THE MAIN WIND
 FORCE RESISTING SYSTEM.
  
 8) SHEET A11.0 THE ROOF AND WALL PRESSURES ARE TAKEN AT
 20 FEET PLEASE REVIEW SHEETS A5.0 AND A5.1 INDICATE THE
 ROOF HEIGHT AT 22FEET. THE OTHER ISSUE WITH THE
 PRESSURES ARE IN ZONE 3 THE PRESSURES ARE TAKEN AS IF
 THERE IS A 3'-0" PARAPET AROUND THE BUILDING, WHICH
 THERE IS NOT. PBC PICTOMETY DOES NOT SHOW 3'-0"
 PARAPETS. FBC-B 1609. 6.2 .
  
 9) SHEET A1.1 SHOWS A DETAIL FOR NEW EXTERIOR METAL
 STAIRS. IN BOTH SHEETS A1.1, AND A5.1 THE PLANS SHOW
 WINDOWS AND DOORS DIRECTLY IN FRONT OF THE EXTERIOR
 STAIRCASE, THIS IS THE ONLY MEANS OF EGRESS FROM THE
 2ND FLOOR R-3 OCCUPANCY. PLEASE REVIEW 2014 FBC-B
 1026.6 ALSO REVIEW THE 2012 IBC BASE CODE FIGURE
 1026.6(1) NOTE OPENINGS SHALL BE LIMITED TO THOSE
 NECESSARY FOR EGRESS FROM NORMALLY OCCUPIED SPACES, NO
 WINDOWS ALLOWED 1ST FLOOR OR 2ND FLOOR.
  
 10) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS. OVERHEAD DOORS, STOREFRONT
 DOORS, METAL CLAD OR SOLID EXTERIOR WOOD DOORS.
 (B) WINDOWS 2ND FLOOR EGRESS WINDOWS SHEET A5.0 & A5.1
 NOTE 2 INDICATES NEW STOREFRONT
 (C) STOREFRONTS, CURTAIN WALLS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES REPAIRS FOR AROUND
 SKYLIGHTS AND NEW INTAKE & EXHAUST FAN CURBS
  
 11) THE PLANS SHEETS A5.0 & A5.1 BOTH INDICATE WITH
 NOTE # 2 NEW STOREFRONT WINDOWS IN THE R3 RESIDENCE.
 PLEASE REVIEW 2014 FBC-B 1029 THE REQUIREMENT FOR AT
 LEAST ONE WINDOW IN EACH SLEEPING ROOM COMPLY WITH
 1029.1 & 1029.2.
  
 12) SHEET A6.1 INDICATES NEW EXTERIOR STAIRS BUT THERE
 IS NO DESIGN CRITERIA FOR THE FABRICATOR. 2014 FBC-B
 TABLE 1607.1.
  
 14) ENERGY COMPLIANCE FORM:
 14A) THE ENERGY DATA REPORT HAS NOT BEEN FILED IN, CAN
 NOT VERIFY COMPLIANCE WITH THE PERSCRIPTIVE METHOD.
  
 14B) SHEETS 7-12 THE MANDATORY REQUIREMENTS HAVE NOT
 BEEN FILED IN YES, N/A OR EX.
  
 14C) 2014 FBC-ENERGY C101.4.6 WHERE A BUILDING INCLUDES
 BOTH RESIDENTIAL AND COMMERCIAL OCCUPANCIES, EACH
 OCCUPANCY SHALL BE SEPARATELY CONSIDERD AND MEET THE
 APPLICABLE PROVISIONS OF THE COMMERCIAL PROVISONS OR
 RESIDENTIAL PROVISIONS OF THIS CODE.
  
 15) SITE PLAN:
 15A) THE SITE PLAN INDICATES THE ACCESSIBLE PARKING
 SPACE ON THE SOUTH SIDE OF THE BUILDING AND BOTH THE
 ACCESSIBLE PARKING SPACE AND ACCESS AISLE CONTINUE PAST
 THE PROPERTY LINE INTO THE RIGHT OF WAY.
 2014 FBC-ACCESSIBLITY CODE 502.3.2 LENGTH
  
 15B) THE SECOND ISSUE IS FROM THE ACCESSIBLE PARKING
 SPACE AND ADJACENT ACCESS AISLE THERE IS 4'-0" FROM THE
 CAR STOP TO THE BUILDING. WITH A 2'-0" OVERHANG OF THE
 CAR THERE IS ONLY 2'-0" FRONT OF THE CAR TO THE WALL
 LINE OF THE STRUCTURE. NOT ENOUGH CLEARANCE FOR AN
 ACCESSIBLE PATH TO THE ACCESSIBLE ENTRANCE. 2014
 FBC-ACC. CODE 206.2.2 WITHIN THE SITE.
  
 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  