Notes |
Date |
Text |
2015-10-21 10:28:52 | YOU SHALL SUBMIT AT A MINIMUM AN ELECTRICAL FLOOR PLAN | | SHOWING THE LOCATION OF THE PROPOSED WASHER & DRYER. | | HAVING DONE WORK INSIDE THE BATHROOM WILL REQUIRE THAT | | IT BE TO CODE AS WELL, MEANING THAT THERE HAS TO BE A | | GFCI PROTECTED OUTLET WITHIN 3' OF THE SINK AND THERE | | HAS TO BE A LIGHT WITH A WALL SWITCH FOR THE BATHROOM. | | THE CODE REQUIRES THAT WHEN YOU PLACE ADDITIONAL LOADS | | TO AN EXISTING PANEL THAT YOU PROVIDE LOAD CALCS AND A | | PANEL SCHEDULE. IN ADDITION TO THAT, THE HOME WILL HAVE | | TO BE MADE COMPLIANT TO SMOKE DETECTOR REQUIREMENTS IF | | IT ALREADY IS NOT IN COMPLIANCE. |
|