2015-11-24 11:22:41THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. THE LOAD INDICATED FOR PANEL "A" INCLUDES A 20 AMP
 SINGLE POLE CIRCUIT FOR A 1.8 KVA CLOTHES DRYER. IF
 THIS DRYER IS GAS INDICATE THIS ON THE DRAWINGS
 OTHERWISE PROVIDE MANUFACTURER SPEC SHEET FOR THIS
 APPLIANCE OR REVISE THE LOAD CALCS ACCORDINGLY.
 2. NEC 300.9, YOUR WIRING SCHEDULE REFLECTS THHN
 INSULATION FOR THE FEEDERS. THIS INSULATION IS NOT
 LISTED FOR WET LOCATIONS. REVISE THE SCHEDULE
 ACCORDINGLY.
 3. FBC-E C405 HAS MANDATORY SWITCHING REQUIREMENTS.
 REVISE YOUR DRAWINGS TO COMPLY.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  