2015-09-23 12:15:481ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090563
 09/23/15
  
 1) THE NEW DRYER AND DRYER VENTING SHALL BE IN
 COMPLIANCE WITH SECTION 504 FBC-14 MECHANICAL. PLEASE
 REVISE THE DRAWINGS IN ACCORDANCE WITH THE FOLOWING
 CODE COMPLIANCES.
 504.1 INSTALLATION.
 CLOTHES DRYERS SHALL BE EXHAUSTED IN ACCORDANCE WITH
 THE MANUFACTURER'S INSTRUCTIONS. DRYER EXHAUST SYSTEMS
 SHALL BE INDEPENDENT OF ALL OTHER SYSTEMS AND SHALL
 CONVEY THE MOISTURE AND ANY PRODUCTS OF COMBUSTION TO
 THE OUTSIDE OF THE BUILDING.
 EXCEPTION: THIS SECTION SHALL NOT APPLY TO LISTED AND
 LABELED CONDENSING (DUCTLESS) CLOTHES DRYERS.
 504.2 EXHAUST PENETRATIONS.
 WHERE A CLOTHES DRYER EXHAUST DUCT PENETRATES A WALL OR
 CEILING MEMBRANE, THE ANNULAR SPACE SHALL BE SEALED
 WITH NONCOMBUSTIBLE MATERIAL, APPROVED FIRE CAULKING OR
 A NONCOMBUSTIBLE DRYER EXHAUST DUCT WALL RECEPTACLE.
 DUCTS THAT EXHAUST CLOTHES DRYERS SHALL NOT PENETRATE
 OR BE LOCATED WITHIN ANY FIREBLOCKING, DRAFTSTOPPING OR
 ANY WALL, FLOOR/CEILING OR OTHER ASSEMBLY REQUIRED BY
 THE FLORIDA BUILDING CODE, BUILDING TO BE
 FIRE-RESISTANCE RATED, UNLESS SUCH DUCT IS CONSTRUCTED
 OF GALVANIZED STEEL OR ALUMINUM OF THE THICKNESS
 SPECIFIED IN SECTION 603.4 AND THE FIRE-RESISTANCE
 RATING IS MAINTAINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. FIRE DAMPERS, COMBINATION
 FIRE/SMOKE DAMPERS AND ANY SIMILAR DEVICES THAT WILL
 OBSTRUCT THE EXHAUST FLOW SHALL BE PROHIBITED IN
 CLOTHES DRYER EXHAUST DUCTS.
 504.3 CLEANOUT.
 EACH VERTICAL RISER SHALL BE PROVIDED WITH A MEANS FOR
 CLEANOUT.
 504.4 EXHAUST INSTALLATION.
 DRYER EXHAUST DUCTS FOR CLOTHES DRYERS SHALL TERMINATE
 ON THE OUTSIDE OF THE BUILDING AND SHALL BE EQUIPPED
 WITH A BACKDRAFT DAMPER. SCREENS SHALL NOT BE INSTALLED
 AT THE DUCT TERMINATION. DUCTS SHALL NOT BE CONNECTED
 OR INSTALLED WITH SHEET METAL SCREWS OR OTHER FASTENERS
 THAT WILL OBSTRUCT THE EXHAUST FLOW. CLOTHES DRYER
 EXHAUST DUCTS SHALL NOT BE CONNECTED TO A VENT
 CONNECTOR, VENT OR CHIMNEY. CLOTHES DRYER EXHAUST DUCTS
 SHALL NOT EXTEND INTO OR THROUGH DUCTS OR PLENUMS.
 504.5 MAKEUP AIR.
 INSTALLATIONS EXHAUSTING MORE THAN 200 CFM (0.09M3/S)
 SHALL BE PROVIDED WITH MAKEUP AIR. WHERE A CLOSET IS
 DESIGNED FOR THE INSTALLATION OF A CLOTHES DRYER, AN
 OPENING HAVING AN AREA OF NOT LESS THAN 100 SQUARE
 INCHES (0.0645 M2) SHALL BE PROVIDED IN THE CLOSET
 ENCLOSURE OR MAKEUP AIR SHALL BE PROVIDED BY OTHER
 APPROVED MEANS.
 504.6 DOMESTIC CLOTHES DRYER DUCTS.
 EXHAUST DUCTS FOR DOMESTIC CLOTHES DRYERS SHALL CONFORM
 TO THE REQUIREMENTS OF SECTIONS 504.6.1 THROUGH
 504.6.7.
 504.6.1 MATERIAL AND SIZE.
 EXHAUST DUCTS SHALL HAVE A SMOOTH INTERIOR FINISH AND
 SHALL BE CONSTRUCTED OF METAL A MINIMUM 0.016 INCH (0.4
 MM) THICK. THE EXHAUST DUCT SIZE SHALL BE 4 INCHES (102
 MM) NOMINAL IN DIAMETER.
 504.6.2 DUCT INSTALLATION.
 EXHAUST DUCTS SHALL BE SUPPORTED AT 4-FOOT (1219 MM)
 INTERVALS AND SECURED IN PLACE. THE INSERT END OF THE
 DUCT SHALL EXTEND INTO THE ADJOINING DUCT OR FITTING IN
 THE DIRECTION OF AIRFLOW. DUCTS SHALL NOT BE JOINED
 WITH SCREWS OR SIMILAR FASTENERS THAT PROTRUDE INTO THE
 INSIDE OF THE DUCT.
 504.6.3 TRANSITION DUCTS.
 TRANSITION DUCTS USED TO CONNECT THE DRYER TO THE
 EXHAUST DUCT SYSTEM SHALL BE A SINGLE LENGTH THAT IS
 LISTED AND LABELED IN ACCORDANCE WITH UL 2158A.
 TRANSITION DUCTS SHALL BE A MAXIMUM OF 8 FEET (2438 MM)
 IN LENGTH AND SHALL NOT BE CONCEALED WITHIN
 CONSTRUCTION.
 504.6.4 DUCT LENGTH.THE MAXIMUM ALLOWABLE EXHAUST DUCT
 LENGTH SHALL BE DETERMINED BY ONE OF THE METHODS
 SPECIFIED IN SECTION 504.6.4.1 OR 504.6.4.2.
 504.6.4.1 SPECIFIED LENGTH.
 THE MAXIMUM LENGTH OF THE EXHAUST DUCT SHALL BE 35 FEET
 (10 668 MM) FROM THE CONNECTION TO THE TRANSITION DUCT
 FROM THE DRYER TO THE OUTLET TERMINAL. WHERE FITTINGS
 ARE USED, THE MAXIMUM LENGTH OF THE EXHAUST DUCT SHALL
 BE REDUCED IN ACCORDANCE WITH TABLE 504.6.4.1.
 504.6.4.2 MANUFACTURER'S INSTRUCTIONS.
 THE MAXIMUM LENGTH OF THE EXHAUST DUCT SHALL BE
 DETERMINED BY THE DRYER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE CODE OFFICIAL SHALL BE PROVIDED WITH
 A COPY OF THE INSTALLATION INSTRUCTIONS FOR THE MAKE
 AND MODEL OF THE DRYER. WHERE THE EXHAUST DUCT IS TO BE
 CONCEALED, THE INSTALLATION INSTRUCTIONS SHALL BE
 PROVIDED TO THE CODE OFFICIAL PRIOR TO THE CONCEALMENT
 INSPECTION. IN THE ABSENCE OF FITTING EQUIVALENT LENGTH
 CALCULATIONS FROM THE CLOTHES DRYER MANUFACTURER, TABLE
 504.6.4.1 SHALL BE USED.
 504.6.5 LENGTH IDENTIFICATION.
 WHERE THE EXHAUST DUCT IS CONCEALED WITHIN THE BUILDING
 CONSTRUCTION, THE EQUIVALENT LENGTH OF THE EXHAUST DUCT
 SHALL BE IDENTIFIED ON A PERMANENT LABEL OR TAG. THE
 LABEL OR TAG SHALL BE LOCATED WITHIN 6 FEET (1829 MM)
 OF THE EXHAUST DUCT CONNECTION.
 SEE TABLE 504.6.4.1 DRYER EXHAUST DUCT FITTING
 EQUIVALENT LENGTH
 DRYER EXHAUST DUCT FITTING TYPE EQUIVALENT LENGTH
 2) SHEET A002: NO AC RETURN GRILLS ARE SHOWN IN THE
 CEILING OF THE NEW COSTUME SHOP, AND NO SUPPLY
 DIFFUSERS OR RETURNS ARE SHOWN IN THE CEILINGS OF THE
 NEW BREAKROOM AND THE NEW LAUNDRY ROOM- BALANCED AIR IS
 REQUIRED IN ACCORDANCE WITH SECTION 601.5 FBC-14
 MECHANICAL.
 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE VENTILATION CALCULATIONS FOR EACH ROOM AND
 SPACE. TO VERIFY COMPLIANCE WITH THIS SECTION, THE
 CALCULATIONS MUST INDICATE THE REQUIRED AMOUNT OF O/A
 CFM'S AND THE AMOUNT BEING PROVIDED, AND THE PLAN MUST
 SHOW THE AIRFLOW CFM'S AT EACH DIFFUSER AND RETURN
 GRILL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  