2015-09-23 12:15:48 | 1ST REVIEW: FBC 2014 MECHANICAL |
| PERMIT #15090563 |
| 09/23/15 |
| |
| 1) THE NEW DRYER AND DRYER VENTING SHALL BE IN |
| COMPLIANCE WITH SECTION 504 FBC-14 MECHANICAL. PLEASE |
| REVISE THE DRAWINGS IN ACCORDANCE WITH THE FOLOWING |
| CODE COMPLIANCES. |
| 504.1 INSTALLATION. |
| CLOTHES DRYERS SHALL BE EXHAUSTED IN ACCORDANCE WITH |
| THE MANUFACTURER'S INSTRUCTIONS. DRYER EXHAUST SYSTEMS |
| SHALL BE INDEPENDENT OF ALL OTHER SYSTEMS AND SHALL |
| CONVEY THE MOISTURE AND ANY PRODUCTS OF COMBUSTION TO |
| THE OUTSIDE OF THE BUILDING. |
| EXCEPTION: THIS SECTION SHALL NOT APPLY TO LISTED AND |
| LABELED CONDENSING (DUCTLESS) CLOTHES DRYERS. |
| 504.2 EXHAUST PENETRATIONS. |
| WHERE A CLOTHES DRYER EXHAUST DUCT PENETRATES A WALL OR |
| CEILING MEMBRANE, THE ANNULAR SPACE SHALL BE SEALED |
| WITH NONCOMBUSTIBLE MATERIAL, APPROVED FIRE CAULKING OR |
| A NONCOMBUSTIBLE DRYER EXHAUST DUCT WALL RECEPTACLE. |
| DUCTS THAT EXHAUST CLOTHES DRYERS SHALL NOT PENETRATE |
| OR BE LOCATED WITHIN ANY FIREBLOCKING, DRAFTSTOPPING OR |
| ANY WALL, FLOOR/CEILING OR OTHER ASSEMBLY REQUIRED BY |
| THE FLORIDA BUILDING CODE, BUILDING TO BE |
| FIRE-RESISTANCE RATED, UNLESS SUCH DUCT IS CONSTRUCTED |
| OF GALVANIZED STEEL OR ALUMINUM OF THE THICKNESS |
| SPECIFIED IN SECTION 603.4 AND THE FIRE-RESISTANCE |
| RATING IS MAINTAINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. FIRE DAMPERS, COMBINATION |
| FIRE/SMOKE DAMPERS AND ANY SIMILAR DEVICES THAT WILL |
| OBSTRUCT THE EXHAUST FLOW SHALL BE PROHIBITED IN |
| CLOTHES DRYER EXHAUST DUCTS. |
| 504.3 CLEANOUT. |
| EACH VERTICAL RISER SHALL BE PROVIDED WITH A MEANS FOR |
| CLEANOUT. |
| 504.4 EXHAUST INSTALLATION. |
| DRYER EXHAUST DUCTS FOR CLOTHES DRYERS SHALL TERMINATE |
| ON THE OUTSIDE OF THE BUILDING AND SHALL BE EQUIPPED |
| WITH A BACKDRAFT DAMPER. SCREENS SHALL NOT BE INSTALLED |
| AT THE DUCT TERMINATION. DUCTS SHALL NOT BE CONNECTED |
| OR INSTALLED WITH SHEET METAL SCREWS OR OTHER FASTENERS |
| THAT WILL OBSTRUCT THE EXHAUST FLOW. CLOTHES DRYER |
| EXHAUST DUCTS SHALL NOT BE CONNECTED TO A VENT |
| CONNECTOR, VENT OR CHIMNEY. CLOTHES DRYER EXHAUST DUCTS |
| SHALL NOT EXTEND INTO OR THROUGH DUCTS OR PLENUMS. |
| 504.5 MAKEUP AIR. |
| INSTALLATIONS EXHAUSTING MORE THAN 200 CFM (0.09M3/S) |
| SHALL BE PROVIDED WITH MAKEUP AIR. WHERE A CLOSET IS |
| DESIGNED FOR THE INSTALLATION OF A CLOTHES DRYER, AN |
| OPENING HAVING AN AREA OF NOT LESS THAN 100 SQUARE |
| INCHES (0.0645 M2) SHALL BE PROVIDED IN THE CLOSET |
| ENCLOSURE OR MAKEUP AIR SHALL BE PROVIDED BY OTHER |
| APPROVED MEANS. |
| 504.6 DOMESTIC CLOTHES DRYER DUCTS. |
| EXHAUST DUCTS FOR DOMESTIC CLOTHES DRYERS SHALL CONFORM |
| TO THE REQUIREMENTS OF SECTIONS 504.6.1 THROUGH |
| 504.6.7. |
| 504.6.1 MATERIAL AND SIZE. |
| EXHAUST DUCTS SHALL HAVE A SMOOTH INTERIOR FINISH AND |
| SHALL BE CONSTRUCTED OF METAL A MINIMUM 0.016 INCH (0.4 |
| MM) THICK. THE EXHAUST DUCT SIZE SHALL BE 4 INCHES (102 |
| MM) NOMINAL IN DIAMETER. |
| 504.6.2 DUCT INSTALLATION. |
| EXHAUST DUCTS SHALL BE SUPPORTED AT 4-FOOT (1219 MM) |
| INTERVALS AND SECURED IN PLACE. THE INSERT END OF THE |
| DUCT SHALL EXTEND INTO THE ADJOINING DUCT OR FITTING IN |
| THE DIRECTION OF AIRFLOW. DUCTS SHALL NOT BE JOINED |
| WITH SCREWS OR SIMILAR FASTENERS THAT PROTRUDE INTO THE |
| INSIDE OF THE DUCT. |
| 504.6.3 TRANSITION DUCTS. |
| TRANSITION DUCTS USED TO CONNECT THE DRYER TO THE |
| EXHAUST DUCT SYSTEM SHALL BE A SINGLE LENGTH THAT IS |
| LISTED AND LABELED IN ACCORDANCE WITH UL 2158A. |
| TRANSITION DUCTS SHALL BE A MAXIMUM OF 8 FEET (2438 MM) |
| IN LENGTH AND SHALL NOT BE CONCEALED WITHIN |
| CONSTRUCTION. |
| 504.6.4 DUCT LENGTH.THE MAXIMUM ALLOWABLE EXHAUST DUCT |
| LENGTH SHALL BE DETERMINED BY ONE OF THE METHODS |
| SPECIFIED IN SECTION 504.6.4.1 OR 504.6.4.2. |
| 504.6.4.1 SPECIFIED LENGTH. |
| THE MAXIMUM LENGTH OF THE EXHAUST DUCT SHALL BE 35 FEET |
| (10 668 MM) FROM THE CONNECTION TO THE TRANSITION DUCT |
| FROM THE DRYER TO THE OUTLET TERMINAL. WHERE FITTINGS |
| ARE USED, THE MAXIMUM LENGTH OF THE EXHAUST DUCT SHALL |
| BE REDUCED IN ACCORDANCE WITH TABLE 504.6.4.1. |
| 504.6.4.2 MANUFACTURER'S INSTRUCTIONS. |
| THE MAXIMUM LENGTH OF THE EXHAUST DUCT SHALL BE |
| DETERMINED BY THE DRYER MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS. THE CODE OFFICIAL SHALL BE PROVIDED WITH |
| A COPY OF THE INSTALLATION INSTRUCTIONS FOR THE MAKE |
| AND MODEL OF THE DRYER. WHERE THE EXHAUST DUCT IS TO BE |
| CONCEALED, THE INSTALLATION INSTRUCTIONS SHALL BE |
| PROVIDED TO THE CODE OFFICIAL PRIOR TO THE CONCEALMENT |
| INSPECTION. IN THE ABSENCE OF FITTING EQUIVALENT LENGTH |
| CALCULATIONS FROM THE CLOTHES DRYER MANUFACTURER, TABLE |
| 504.6.4.1 SHALL BE USED. |
| 504.6.5 LENGTH IDENTIFICATION. |
| WHERE THE EXHAUST DUCT IS CONCEALED WITHIN THE BUILDING |
| CONSTRUCTION, THE EQUIVALENT LENGTH OF THE EXHAUST DUCT |
| SHALL BE IDENTIFIED ON A PERMANENT LABEL OR TAG. THE |
| LABEL OR TAG SHALL BE LOCATED WITHIN 6 FEET (1829 MM) |
| OF THE EXHAUST DUCT CONNECTION. |
| SEE TABLE 504.6.4.1 DRYER EXHAUST DUCT FITTING |
| EQUIVALENT LENGTH |
| DRYER EXHAUST DUCT FITTING TYPE EQUIVALENT LENGTH |
| 2) SHEET A002: NO AC RETURN GRILLS ARE SHOWN IN THE |
| CEILING OF THE NEW COSTUME SHOP, AND NO SUPPLY |
| DIFFUSERS OR RETURNS ARE SHOWN IN THE CEILINGS OF THE |
| NEW BREAKROOM AND THE NEW LAUNDRY ROOM- BALANCED AIR IS |
| REQUIRED IN ACCORDANCE WITH SECTION 601.5 FBC-14 |
| MECHANICAL. |
| 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE |
| AND PROVIDE VENTILATION CALCULATIONS FOR EACH ROOM AND |
| SPACE. TO VERIFY COMPLIANCE WITH THIS SECTION, THE |
| CALCULATIONS MUST INDICATE THE REQUIRED AMOUNT OF O/A |
| CFM'S AND THE AMOUNT BEING PROVIDED, AND THE PLAN MUST |
| SHOW THE AIRFLOW CFM'S AT EACH DIFFUSER AND RETURN |
| GRILL. |
| |