2015-10-13 17:55:44 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE |
| ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH |
| REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE |
| REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED |
| SHALL BE RESUBMITTED FOR ANOTHER REVIEW. |
| 1. NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET ADJACENT |
| TO EVERY PEDESTRIAN DOOR IN EVERY COMMERCIAL |
| ESTABLISHMENT. |
| 2. NEC 210.62 REQUIRES THAT THERE BE A SHOW WINDOW |
| OUTLET FOR EVERY 12 LINEAR FEET OF SHOW WINDOW |
| (STOREFRONT) OR PORTION THEREOF. THIS OUTLET SHALL BE |
| NO MORE THAN 18? ABOVE OR AWAY FROM THE TOP OF THE SHOW |
| WINDOW. |
| 3. NEC 422.52 REQUIRES THAT THE ELECTRICAL OUTLET FOR |
| THE DRINKING FOUNTAIN BE PROTECTED WITH GFCI. |
| 4. NEC 215.5 REQUIRES A SITE SPECIFIC RISER DIAGRAM |
| INCLUDING THE TOTAL CALCULATED LOADS BEFORE AND AFTER |
| AND DEMAND FACTORS. CONDUCTOR SIZING SHALL ALSO BE |
| INCLUDED. (THIS SHALL INCLUDE EVERY PANELBOARD WITHIN |
| THE SCOPE OF THIS PERMIT). |
| 5. NEC 408.4(A) REQUIRES THAT YOU SUBMIT A CIRCUIT |
| DIRECTORY FOR EVERY PANELBOARD. |
| 6. NEC 408.4(B) REQUIRES THAT ALL PANELS BE MARKED TO |
| INDICATE THE LOCATION OF THE SOURCE |
| 7. FBC-B SECTION 1006 HAS SPECIFIC EMERGENCY LIGHTING |
| REQUIREMENTS WHICH DO NOT APPEAR TO HAVE BEEN MET. |
| REVISE YOUR EMERGENCY LIGHTING DETAIL/LAYOUT |
| ACCORDINGLY. |
| 8. FBC-E SECTION C405 HAS MANDATORY LIGHTING |
| REQUIREMENTS FOR COMMERCIAL ESTABLISHMENTS WHICH HAVE |
| TO BE COMPLIED WITH. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU |
| |