2015-09-14 14:21:16 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 |
| [email protected] |
| |
| FBC FLORIDA BUILDING CODE 5TH EDITION 2014 |
| |
| TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED |
| |
| PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| |
| DOCUMENTS SUBMITTED - ONE SET OF ASTM E 90 FOR QEP 6 MM |
| CORK, QEP SPEC SHEET, BADGER CORK FLAME SPREAD TEST |
| |
| TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS |
| REQUIRED. |
| |
| |
| 1. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART |
| OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN |
| DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW |
| IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT |
| BELOW WILL NOT BE ALTERED. |
| |
| PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| |
| 2. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| THE TEST REPORT IS FOR BADGER CORK. THE RELATIONSHIP |
| BETWEEN BADGER CORK AND QEP IS NOT CLEAR. PROVIDE A |
| COPY OF ASTM E 84 FOR QEP 6 MM CORK. |
| |