2016-03-29 10:17:45 | 4TH ELECTRICAL REVIEW NOTES FOR PERMIT 15090399. PLANS |
| FILED UNDER PERMIT #:15090395 |
| REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014, |
| NFPA 70 2011 (NEC) |
| |
| CORRECTIONS REQUIRED: |
| |
| 1. PER A TELEPHONE CONVERSATION WITH ANDREW OF |
| SILBERSTEIN ARCHITECTURE THE SOUTH ELEVATION OF UNIT |
| ?B? WILL BE REVISED TO SHOW THE SLIDING DOOR ENTRY FROM |
| THE COURTYARD. IN DOING SO, THE RECEPTACLES NOW |
| INDICATED ON THE PLANS SHALL BE RELOCATED TO MEET NEC |
| 210.52 REQUIREMENTS. |
| 2. THE ADDITION OF THE DOOR/ENTRY WILL GENERATE THE |
| NEED TO LIGHT CONTROL AS PER NEC 210.70 FOR THE |
| REQUIRED LIGHT OUTSIDE THE DOOR. |
| 3. NEC 210.52 (E)(3) REQUIRES THAT YOU PROVIDE A GFI |
| OUTLET IN EVERY BALCONY GREATER THAN 20 SQ. FT. (B202, |
| B302 & B306) |
| 4. IN THE INTEREST OF LIFE SAFETY, USER CONVENIENCE AND |
| ENERGY CONSERVATION, 3 WAY SWITCHING IS RECOMMENDED AT |
| A MINIMUM FOR THE TRAVERSE LIGHTING. |
| 5. FBC-R MECHANICAL VENTILATION IS REQUIRED FOR ROOMS |
| B102, B303 & B304. THE EXHAUST FAN SHALL COME ON WITH |
| THE LIGHT. |
| 6. NEC 314.27 A LISTED FAN BOX IS REQUIRED FOR ROOM |
| B101. |
| 7. NEC 210.70 REQUIRES THAT ROOM LIGHTS BE SWITCH UPON |
| ENTRY, THEREFORE IF WALL CONTROL IS DESIRED FOR THE |
| PADDLE FAN, AN ADDITIONAL SWITCH WILL BE REQUIRED. |
| 8. NEC 404.2(C) REQUIRES THAT A GROUNDED CONDUCTOR BE |
| PROVIDED AT EVERY LIGHT SWITCH. |
| 9. FBC-ER404.1 REQUIRES THAT A MINIMUM OF 75% OF THE |
| LAMPS IN PERMANENTLY INSTALLED FIXTURES BE HIGH |
| EFFICIENCY. |
| 10. THESE COMMENTS ARE IN ADDITION TO ANY OF THE |
| PREVIOUSLY MENTIONED WHICH HAVE NOT YET BEEN SATISFIED. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |