2016-02-12 09:42:183RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090399: MODEL B- #754.
 2/12/16
  
 1) THERE ARE SEVERAL CONFLICTS BETWEEN THE AC COOLING
 LOAD CALCULATIONS, THE ENERGY CALCULATIONS AND THE AC
 PLANS.
 A) THE AC CALCULATIONS INDICATE TWO ZONES WITH
 CALCULATED COOLING LOADS OF 2.0 ON THE 1ST LEVEL, AND
 3.8 TONS ON THE 2ND AND 3RD LEVELS. ON SHEET M201,
 HOWEVER, 3-TON AND 4-TON SYSTEMS ARE SHOWN FOR UNIT
 #754, AND ON M301 TWO 4-TON SYSTEMS ARE SHOWN (NOTE
 THAT A 4-TON SYSTEM IS USED TO SUPPLY THE 1ST AND 2ND
 LEVEL WHICH CONFLICTS WITH THE CALCS). PLEASE CORRECT
 AND ALSO REFER TO SECTION R403.6.1.1 FBC-14 ENERGY
 CONSERVATION WHICH PROHIBITS OVERSIZING OF AC SYSTEMS
 GREATER THAN 1.15 TIMES THE CALCULATED LOAD.
 B) THE SUBMITTED ENERGY CALCULATION FORM R405-2014
 SHOWS COMPLIANCE DATA FOR A SINGLE COOLING SYSTEM WHICH
 APPEARS TO ACTUALLY BE COMPLIANCE DATA FOR BOTH OF THE
 AC SYSTEMS( 3-TON & 4-TON) COMBINED AND AVERAGED.
 PLEASE PROVIDE COMPLIANCE DATA FOR EACH INDIVIDUAL
 SYSTEM AND, AS NOTED ABOVE, COMPARE WITH THE PLANS
 WHICH INDICATES TWO 4-TON SYSTEMS.
 C) THE AC CALCULATIONS FORM IS INDICATING THE FRONT
 DOOR FACES EAST HOWEVER THE FRONT DOOR IS FACING NORTH.
 2) SHEET: M301: THE MAIN RETURN DUCT SIZES FROM THE
 18X18" GRILL AND THE14X14" GRILLS ARE NOT SHOWN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER