2016-01-27 12:39:05 | 1) SHT. A-1.0 SHOWS A DECK DRAIN BY THE POOL. IS THE |
| DRAIN AND PIPING BEING INSTALLED UNDER THE PLUMBING FOR |
| THE BUILDING? IF SO, SHOW THE PIPING ON THE CIVIL |
| DRAWINGS, THE SIZE AND THE SQUARE FOOTAGE DRAINED BY |
| THE DRAIN. CLARIFY. WPB AMEND. TO FBC SEC. 107.2.1. |
| 2) SUBMIT A SCUPPER DETAIL. THE LOCATION OF THE SCUPPER |
| SHALL COMPLY WITH 2014 FBCR SEC.R903.4.1.SUBMIT |
| CALCULATIONS FOR THE SIZE OF THE OVERFLOW SCUPPER. |
| SCUPPER SHALL BE SIZED IN ACCORDANCE WITH 2014 |
| FBC-PLUMBING. |
| 4) SHT.A-3.1 REFERS TO A-6.0 FOR A SECTION DETAIL. THIS |
| SHEET IS NOT IN THE PLANS. DOES THIS SHEET SHOW THE |
| SCUPPER DETAIL? CLARIFY. |
| 5) SHT. A-5.3-DETAIL #1 CALLS OUT AN ENLARGED KITCHEN |
| PLAN BUT A BATHROOM IS SHOW. PLEASE REVISE. |
| 6) SHT. P-102 SHOWS A MAIN WATER METER. WHAT WILL THIS |
| METER SERVICE? CLARIFY. WPB AMEND. TO FBC SEC. 107.2.1. |
| 7) SHT. P301 - SIZE THE VENTS ON THE SANITARY RISER. IF |
| THE VENTS ARE TYPICAL, SIZE THE VENT AND NOTE THAT THE |
| OTHER VENTS ARE TYPICAL SIZE. THE VENT SYSTEM SHALL BE |
| SIZED IN ACCORDANCE WITH 2014 FBCR- SEC.P3113.1. |
| 8) THE RESPONSE FROM THE ENGINEERING FIRM FOR THE GAS |
| COMMENT REGARDING COMBUSTION AIR REFERS TO SHT. M301. |
| THERE IS NO SUCH DRAWING IN THIS SET OF PLANS. CLARIFY. |
| 9) SHT. M401 - WATER HEATER COMBUSTION AIR CALCULATIONS |
| SHOWS THE TANKLESS WATER HEATER AS 35,000 BTU'S AND THE |
| GAS RISER SHOWS THE BTU LOAD AS 199,000 BTU'S. THIS IS |
| OBVIOUSLY A MISPRINT. REVISE. |
| 10) SHT. P101-WATER HEATER DETAIL REFERS TO A HOT WATER |
| RECIRCULATING LINE (?) BUT THIS IS NOT SHOWN ON THE |
| WATER PIPING PLAN VIEW. CLARIFY. |
| 11) THE PLUMBING PLANS SHALL BEAR THE WET SIGNATURE OF |
| THE ENGINEER OF RECORD PER THE F.A.C. RULE |
| 61G15-23.001, .002, & .003. |
| |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |