Plan Review Notes
Plan Review Notes For Permit 15090399
Permit Number 15090399
Review Stop M
Sequence Number 2
Notes
Date Text
2016-01-27 09:07:342ND REVIEW 2014 MECHANICAL
 PERMIT #15090399
 12/14/15
  
 I HAVE REVIEWED THE REVISED PLANS AND THE RESPONSE
 NARRATIVE FROM JWL ENGINEERING, HOWEVER INADEQUATE
 REVISIONS AND RESPONSES HAVE BEEN GIVEN TO SOME OF THE
 COMMENTS. THE FOLLWOWNG REVIEW WILL REFER BACK TO THOSE
 1ST REVIEW COMMENTS. PLEASE NOTE THE RESPONSE NARRATIVE
 FROM JWL ADDRESSES ONLY THE FIRST FOUR COMMENTS (LISTED
 AS 6-9 IN THE NARRATIVE), AND THERE WERE NO RESPONSES
 FROM THE ARCHITECT.
 1) COMMENT #1: THE NARRATIVE REPONSE TO THIS COMMENT
 STATES THAT THE REQUESTED DESIGN CRITERIA FOR THE
 PROJECT IS NOTED ON SHEET M101, HOWEVER I DID NOT SEE
 ANY INFORMATION LISTED IN THE MECH SPEC NOTES.
 2) COMMENT #3: SECTION 405.4.2 EXCEPTION ALLOWS FOR
 WORSE CASE SCENARARIOS, HOWEVER AS NOTED IN THE 1ST
 REVIEW, INDIVIDUAL ENERGY AND AC CALCULATIONS SHALL BE
 SUBMITTED FOR EACH TOWN HOME UNDER PERMIT PER SECTION
 R103.1 FBC-14 ENERGY CONSERVATION. PLEASE NOTE THAT THE
 RE-SUBMITTED ENERGY FORM R405-2014 INDICATES IT IS NOT
 A WORSE CASE ON PAGE 1.
 3) COMMENT #4: RE-SUBMITTED FORM R405-2014 : A) PAGE 1
 INDICATES 98.7 KBTU/HR FOR 2263 SQ.FT.- ONE OF THESE
 VALUES IS INCORRECT. B) PAGE 3- THE COOLING SYSTEM DATA
 DOES NOT INDICATE A COOLING CAPACITY VALUE, AND THE
 2960 AIR FLOW CFM'S DOES NOT MATCH THE CFM'S INDICATED
 IN THE AC EQUIPMENT SCHEDULE ON M101.
 4) COMMENTS #6, 8,9,10,11,12,13,&14- NO RESPONSES OR
 REVISIONS WERE PROVIDED: REFER TO 1ST REVIEW COMMENTS
 AND COMPLY. PLEASE NOTE IN REGARD TO COMMENT #9- THE
 PLUMBING PLANS LIST THE WATER HEATER CAPACTITY AT 199
 CFH NOT AT 34 KBTUH,
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  