Plan Review Notes For Permit 15090399 |
Permit Number |
15090399 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-01-27 13:10:52 | 1) THE RESPONSE FROM THE ENGINEERING FIRM FOR THE GAS | | COMMENT REGARDING COMBUSTION AIR REFERS TO SHT. M301. | | THERE IS NO SUCH DRAWING IN THIS SET OF PLANS. CLARIFY. | | 2) SHT. M401 - WATER HEATER COMBUSTION AIR CALCULATIONS | | SHOWS THE TANKLESS WATER HEATER AS 35,000 BTU'S AND THE | | GAS RISER SHOWS THE BTU LOAD AS 199,000 BTU'S. THIS IS | | OBVIOUSLY A MISPRINT. REVISE. | | 3) THE PLUMBING PLANS SHALL BEAR THE WET SIGNATURE OF | | THE ENGINEER OF RECORD PER THE F.A.C. RULE | | 61G15-23.001, .002, & .003. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|