2015-12-22 15:07:10 | DECEMBER 22ND, 2015 2ND ELECTRICAL REVIEW |
| |
| RE: RESPONSE TO FIRST REVIEW COMMENTS FOR THE PARK |
| SLOPE TOWNHOUSES. |
| |
| BELOW IS MY RESPONSE TO YOUR COMMENTS. PLEASE NOTE THAT |
| THEY APPEAR IN THE SAME ORDER IN WHICH YOU SUBMITTED |
| THEM TO ME. |
| |
| 10) I INFORMED YOU THAT WE WILL NEED A COPY OF THE |
| RECORDED EASEMENTS BEFORE WE CAN APPROVE THE ELECTRICAL |
| REVIEW. YOU DELEGATED TO SOMEONE ELSE, BUT REGARDLESS |
| OF WHO SECURES THE EASEMENTS. A COPY OF THE RECORDED |
| DOCUMENTS SHALL ACCOMPANY YOUR SUBMITTAL PRIOR TO |
| APPROVAL. |
| |
| 11) WE ALREADY ESTABLISHED A SEPARATE PERMIT FOR THE |
| HOUSE METER AND OTHER ITEMS RELATED THERETO. |
| |
| 12) WE CONCUR ON THE POOL PERMIT ISSUE. |
| |
| 13) YOU CORRECTED THE NOTE BUT INCORRECT CODE |
| REFERENCES REMAIN. THE PROPER CODES TO FOLLOW ARE: THE |
| FLORIDA FIRE PREVENTION CODE (FFPC) 2012, NFPA 70 |
| (NATIONAL ELECTRICAL CODE) 2011, NFPA 72 2010 EDITION, |
| AND THE 5TH EDITION OF THE 2014 FLORIDA BUILDING CODE |
| (FBC). CORRECT YOUR NOTE ACCORDINGLY. |
| |
| 17) YOU CONTINUE TO REFER TO A NONEXISTENT CABLE. BX |
| CABLE IS NOT RECOGNIZED IN THE CODE BOOK. |
| |
| 22 -28) REFER TO SHEET E301 WHICH WAS NOT PROVIDED. |
| |
| 33 & 34) I ASKED FOR A FLOOR OUTLET SO THAT YOU COULD |
| GET AWAY WITH A SINGLE UNIT BUT YOU HAVE IMPROVED ON |
| THAT BY ADDING TO OUTLETS IN THE CORRIDORS. FYI AND |
| OUTLET IS REQUIRED HERE EVEN THOUGH THIS IS A HALLWAY. |
| SEE NEC 210.52 (H). |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME. HAVE A VERY MERRY CHRISTMAS AND A |
| PROSPEROUS 2016. |
| |