2015-09-29 07:26:41 | 1ST REVIEW: FBC 2014 RESIDENTIAL |
| PERMIT #15090399 |
| 9/29/15 |
| |
| 1) DESIGN CRITERIA: PLEASE PROVIDE DEFINITIVE DESIGN |
| CRITERIA AND CODE DATA ON THE PLANS FOR THE PROPOSED |
| PROJECT. AS THE PERMIT APPLICATIONS INDICATE "TOWN |
| HOMES" I AM REVIEWING THE PLANS FOR COMPLIANCE WITH THE |
| FBC-14 RESIDENTIAL CODE. PLEASE REVIEW AND REVISE WHERE |
| REQUIRED. |
| 2) CORRECT THE SUBMITTED ENERGY AND HVAC CALCULATIONS |
| INDICATING "LANTANA, FL." IN THE TITLE ADDRESSES- THE |
| PROPOSED PROJECT IS IN THE CITY OF WEST PALM BEACH. |
| 3) INDIVIDUAL ENERGY CALCULATIONS AND AC COOLING AND |
| HEATING CALCULATIONS SHALL BE SUBMITTED SEPARATELY FOR |
| EACH TOWN HOME IN ACCORDANCE WITH SECTION R103.1 FBC-14 |
| ENERGY CONSERVATION- "GENERAL. CONSTRUCTION DOCUMENTS |
| AND OTHER SUPPORTING DATA SHALL BE SUBMITTED IN ONE OR |
| MORE SETS WITH EACH APPLICATION FOR A PERMIT. THE |
| CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A |
| REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY THE |
| STATUTES OF THE JURISDICTION IN WHICH THE PROJECT IS TO |
| BE CONSTRUCTED. WHERE SPECIAL CONDITIONS EXIST, THE |
| CODE OFFICIAL IS AUTHORIZED TO REQUIRE NECESSARY |
| CONSTRUCTION DOCUMENTS TO BE PREPARED BY A REGISTERED |
| DESIGN PROFESSIONAL." EACH SUBMITTAL DOCUMENT SHALL |
| BEAR THE SAME ADDRESS AS THE ONE LISTED ON THE |
| CORRESPONDING PERMIT APPLICATION, AND MANUAL J AC |
| SIZING WORKSHEETS SHALL BE SUBMITTED FOR EACH NEW TOWN |
| HOME INDICATING DIRECTIONAL ORIENTATIONS AND CALCULATED |
| LOADS FOR EACH INDIVIDUAL TOWN HOME- REFER TO SECTION |
| R403.6.1 FBC-14 ENERGY CONSERVATION- "WORST CASE |
| SCENARIOS" FOR EACH BUILDING ARE NOT ACCEPTABLE. |
| 4) REVIEW OF THE SUBMITTED ENERGY EFFICIENCY FORM |
| R405-2014 FOR BLDG. B REVEALED THESE DEFICIENCIES: A) |
| THE SQUARE FOOTAGE CALCULATION DOESN'T MATCH THE |
| FOOTAGE LISTED ON SHEET A-1.0. B) THE WINDOW U-VALUES |
| LISTED DON'T MATCH THE U-VALUES LISTED ON THE AC |
| CALCULATIONS. C) THE AIRFLOW CFM'S AND HEATING |
| CAPACITIES LISTED DON'T MATCH THE AC SCHEDULE. |
| 5) REVIEW OF THE SUBMITTED HVAC CALCULATIONS REVEALED |
| THESE DEFICIENCIES: A) THE COOLING EQUIPMENT SUMMARIES |
| WERE NOT COMPLETED FOR EACH SYSTEM. B) REFER TO COMMENT |
| #3. |
| 6) SHEET M101: CORRECT THE REFERENCES TO THE FBCM SHOWN |
| ON THE BUILDING AND GARAGE VENTILATION TABLES. PROVIDE |
| CALCULATIONS IN COMPLIANCE WITH THE FBC-14 RESIDENTIAL. |
| 7) M102, DETAIL A7: THE PRINT IN THE DETAIL AND |
| STRAPPING TABLE IS TOO FAINT TO READ AND NEEDS TO BE |
| EMBOLDENED FOR REVIEW AND COMPUTER SCANNING. PLEASE |
| NOTE THAT THE ROOM ID NUMBERS SHOWN ON ALL OF THE |
| LAYOUT PLANS ALSO NEED TO BE EMBOLDENED. |
| 8) M102, DETAIL C7: INDICATE THE TYPE AND SIZE OF |
| CONDENSATE PIPING TO BE INSTALLED. |
| 9) M401: CORRECT THE REFERENCES TO THE FBCFG ON THE |
| RANGE AND DRYER COMBUSTION TABLES. PROVIDE CALCULATIONS |
| IN COMPLIANCE WITH THE FBC-14 RESIDENTIAL. PLEASE NOTE |
| THE DRYER IN THE CLOSET MUST BE PROVIDED COMBUSTION AIR |
| THROUGH OPENINGS IN THE DOORS- SEE SECTION G2407.5.3 |
| FBC-14 RESIDENTIAL AND PROVIDE SIZING CALCULATIONS AND |
| OPENING SIZES. |
| 10) M401: REFER TO SECTION M1305.1.1 AND SHOW |
| COMPLIANCE FOR THE AIR HANDLERS IN THE CLOSETS- PROVIDE |
| AN ENLARGED DETAIL IF NECESSARY TO SHOW THE REQUIRED |
| CLEARANCE DIMENSIONS. |
| 11) M401: INDICATE THE SIZE OF THE LOUVER AT THE FIRST |
| FLOOR AIR HANDLER CLOSET. CLARIFY HOW ALL AIR IS BEING |
| RETURNED TO THE AIR HANDLERS- THE PLAN SHOWS A LOUVERED |
| DOOR, BUT THE DETAIL ON M102 SHOWS A DUCTED RETURN IN |
| THE CLOSET. |
| 12) SHOW THE CONDENSATE DISPOSAL PIPING RUNS AND |
| DISCHARGE LOCATIONS. |
| 13) SHOW THE REFRIGERANT PIPING RUNS. |
| 14) PROVIDE A SUBMITTAL PACKAGE CONSISTING OF THE |
| RANGE, RANGE HOOD AND EXHAUST DUCT, WATER HEATER AND |
| VENT PIPING, DRYER AND VENT PIPING, AC SYSTEMS, AND THE |
| VAV BOXES. |
| |