2015-10-21 18:59:48 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION |
| OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION |
| OF THE 2014 FBC, (FLORIDA BUILDING CODE) AS APPLICABLE |
| AND BELOW ARE THE DEFICIENCIES NOTED. |
| 1. YOU SHALL PROVIDE PROOF OF THE RECORDED EASEMENTS |
| FOR THE FLORIDA POWER & LIGHT (FPL) UNDERGROUND FEEDERS |
| TRAVERSING NEIGHBORING AND NON RELATED PROPERTIES. |
| 2. THE HOUSE METER AND PANEL ?H? ON THE EXTERIOR OF |
| 1200 S. LAKE AVENUE, ALONG WITH THE RESPECTIVE |
| LANDSCAPE LIGHTING AND ANY INCIDENTAL ATTACHED THERETO |
| INDICATED OR NOT ON THE APPROVED PLANS SHALL BE |
| INSTALLED UNDER A SEPARATE PERMIT. |
| 3. ALL POOL ELECTRIC SHALL BE UNDER A SEPARATE PERMIT. |
| 4. SPEC NOTE 3, QUOTES NON-APPLICABLE CODES. CORRECT TO |
| REFLECT THE CODES IN EFFECT AS INDICATED ABOVE. |
| 5. SPEC NOTE 9, REFLECTS INCORRECT ARC-FAULT |
| REQUIREMENTS FOR THE CURRENT CODE. CORRECT ACCORDINGLY. |
| 6. SPEC NOTE 10, CONDUCTOR INSULATION HAS NOTHING TO DO |
| WITH WIRE GAUGE, BUT WITH INSTALLATION CONDITIONS. THWN |
| SHALL BE REQUIRED REGARDLESS OF GAUGE FOR CONDUCTORS IN |
| WET LOCATIONS. |
| 7. GENERAL NOTES 10, REFER TO BX CABLE, CORRECT THAT TO |
| REFLECT NM OR AC AS IN THE CURRENT EDITION OF THE NEC. |
| 8. GENERAL NOTES 11, ALL LUMINARIES SHALL BE GROUNDED |
| AS INDICATED IN PART V OF SECTION 410 OF THE 2011 NEC. |
| 9. ADDITIONAL NOTES REQUIRED: |
| A) ALL RECEPTACLES TO BE LISTED TAMPER-RESISTANT ?TR? |
| AS REQUIRED IN NEC 406.12. |
| B) ALL CEILING LUMINAIRE OUTLETS SHALL BE RATED TO |
| SUPPORT 50# AS INDICATED IN NEC 314.27. |
| C) RECEPTACLES IN WET LOCATIONS SHALL BE LISTED FOR THE |
| PURPOSE ?WR? AS INDICATED IN NEC 406.8 |
| 10. UNIT ?H? FEEDER NOTES, BLDG. GRD. PER NEC 250.66 A |
| 100 AMP SERVICE REQUIRES A #8CU GEC. *THE 5OHM |
| RESISTANCE CALLED FOR ON THE PLANS IS PROBABLY |
| UNOBTAINABLE. CODE CALLS FOR 25 OHMS IN NEC 250.53. |
| 11. ARE YOU SURE YOU WANT THE PANELS SURFACE MOUNTED AS |
| INDICATED ON THE RESPECTIVE PANEL SCHEDULES? |
| 12. PANEL SCHEDULE ?A? CIRCUIT 14 IS LABELED AS |
| DISPOSAL YET INDICATED AS D/W ON FLOOR PLAN. CORRECT |
| ACCORDINGLY. |
| |
| |
| UNIT ?A? |
| 1. INDICATE LOCATION OF ELECTRIC METER & SERVICE |
| DISCONNECT ON FLOOR PLAN. |
| 2. NEC 210.52(E)(3) REQUIRES THAT THERE BE AN OUTLET IN |
| THE PORCH AREA. |
| 3. ROOM A103, OUTLET SPACING SHALL BE AS PER NEC |
| 210.52(A), CHECK THE NORTH WALL. |
| 4. THE AREA BETWEEN THE PANTRY AND THE POWDER ROOM IS |
| MISSING AN OUTLET. NEC 210.52(A). |
| 5. ROOM A300 IS MISSING AN OUTLET ON THE EXTERIOR WALL |
| OF ROOM A303. |
| 6. ROOM A307 IS MISSING AN OUTLET ON THE EXTERIOR WALL |
| OF ROOM A309. |
| 7. ROOM A306 REQUIRES A LIGHT CONTROLLED BY A WALL |
| SWITCH PER NEC 210.70(A)(3) |
| 8. IT APPEARS THAT THERE IS AN HVAC UNIT INSIDE THE |
| ATTIC, IF THIS IS CASE; NEC 110.33(B) REQUIRES THAT |
| THERE BE A PERMANENT LADDER INTO THE ATTIC. OTHER |
| SECTIONS OF THE CODE REQUIRE THAT THERE BE A GFI OUTLET |
| AND A LIGHT CONTROLLED BY A WALL SWITCH AND NOT A PULL |
| CHAIN INSIDE THE ATTIC. THIS LIGHT SWITCH SHOULD HAVE |
| AN INDICATOR SO AS NOT TO LEAVE THE LIGHT ON INSIDE THE |
| ATTIC WHEN NOT NEEDED. |
| |
| UNIT ?B? |
| 1. INDICATE LOCATION OF ELECTRIC METER & SERVICE |
| DISCONNECT ON FLOOR PLAN. |
| 2. NEC 680.10 PROHIBITS ANY UNDERGROUND WIRING FROM |
| RUNNING UNDER THE POOL OF WITHIN 5? HORIZONTALLY OF THE |
| INSIDE WALL OF THE POOL UNLESS THE WIRING IS DIRECTLY |
| RELATED TO THE POOL. |
| 3. THERE IS A MISSING OUTLET FOR THE SPACE OUTSIDE OF |
| THE SOUTH WALL OF ROOM B302. |
| 4. A FLOOR OUTLET SHALL BE INSTALLED ALONG THE FLOOR |
| LINE OF THE STAIR RAILING. |
| 5. ROOM B200 IS MISSING AN OUTLET ON THE WALL OUTSIDE |
| OF THE BATHROOM. |
| 6. ROOM B307 REQUIRES A LIGHT CONTROLLED BY A WALL |
| SWITCH. |
| |
| THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN |
| MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED |
| FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED |
| TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| |