Plan Review Notes
Plan Review Notes For Permit 15090397
Permit Number 15090397
Review Stop E
Sequence Number 4
Notes
Date Text
2016-03-29 10:19:334TH ELECTRICAL REVIEW NOTES FOR PERMIT 15090397. PLANS
 FILED UNDER PERMIT #:15090395
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014,
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
  
 1. PER A TELEPHONE CONVERSATION WITH ANDREW OF
 SILBERSTEIN ARCHITECTURE THE SOUTH ELEVATION OF UNIT
 ?B? WILL BE REVISED TO SHOW THE SLIDING DOOR ENTRY FROM
 THE COURTYARD. IN DOING SO, THE RECEPTACLES NOW
 INDICATED ON THE PLANS SHALL BE RELOCATED TO MEET NEC
 210.52 REQUIREMENTS.
 2. THE ADDITION OF THE DOOR/ENTRY WILL GENERATE THE
 NEED TO LIGHT CONTROL AS PER NEC 210.70 FOR THE
 REQUIRED LIGHT OUTSIDE THE DOOR.
 3. NEC 210.52 (E)(3) REQUIRES THAT YOU PROVIDE A GFI
 OUTLET IN EVERY BALCONY GREATER THAN 20 SQ. FT. (B202,
 B302 & B306)
 4. IN THE INTEREST OF LIFE SAFETY, USER CONVENIENCE AND
 ENERGY CONSERVATION, 3 WAY SWITCHING IS RECOMMENDED AT
 A MINIMUM FOR THE TRAVERSE LIGHTING.
 5. FBC-R MECHANICAL VENTILATION IS REQUIRED FOR ROOMS
 B102, B303 & B304. THE EXHAUST FAN SHALL COME ON WITH
 THE LIGHT.
 6. NEC 314.27 A LISTED FAN BOX IS REQUIRED FOR ROOM
 B101.
 7. NEC 210.70 REQUIRES THAT ROOM LIGHTS BE SWITCH UPON
 ENTRY, THEREFORE IF WALL CONTROL IS DESIRED FOR THE
 PADDLE FAN, AN ADDITIONAL SWITCH WILL BE REQUIRED.
 8. NEC 404.2(C) REQUIRES THAT A GROUNDED CONDUCTOR BE
 PROVIDED AT EVERY LIGHT SWITCH.
 9. FBC-ER404.1 REQUIRES THAT A MINIMUM OF 75% OF THE
 LAMPS IN PERMANENTLY INSTALLED FIXTURES BE HIGH
 EFFICIENCY.
 10. THESE COMMENTS ARE IN ADDITION TO ANY OF THE
 PREVIOUSLY MENTIONED WHICH HAVE NOT YET BEEN SATISFIED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]