Date |
Text |
2016-01-27 09:04:25 | 2ND REVIEW 2014 MECHANICAL |
| PERMIT #15090397 |
| 12/14/15 |
| |
| I HAVE REVIEWED THE REVISED PLANS AND THE RESPONSE |
| NARRATIVE FROM JWL ENGINEERING, HOWEVER INADEQUATE |
| REVISIONS AND RESPONSES HAVE BEEN GIVEN TO SOME OF THE |
| COMMENTS. THE FOLLWOWNG REVIEW WILL REFER BACK TO THOSE |
| 1ST REVIEW COMMENTS. PLEASE NOTE THE RESPONSE NARRATIVE |
| FROM JWL ADDRESSES ONLY THE FIRST FOUR COMMENTS (LISTED |
| AS 6-9 IN THE NARRATIVE), AND THERE WERE NO RESPONSES |
| FROM THE ARCHITECT. |
| 1) COMMENT #1: THE NARRATIVE REPONSE TO THIS COMMENT |
| STATES THAT THE REQUESTED DESIGN CRITERIA FOR THE |
| PROJECT IS NOTED ON SHEET M101, HOWEVER I DID NOT SEE |
| ANY INFORMATION LISTED IN THE MECH SPEC NOTES. |
| 2) COMMENT #3: SECTION 405.4.2 EXCEPTION ALLOWS FOR |
| WORSE CASE SCENARARIOS, HOWEVER AS NOTED IN THE 1ST |
| REVIEW, INDIVIDUAL ENERGY AND AC CALCULATIONS SHALL BE |
| SUBMITTED FOR EACH TOWN HOME UNDER PERMIT PER SECTION |
| R103.1 FBC-14 ENERGY CONSERVATION. PLEASE NOTE THAT THE |
| RE-SUBMITTED ENERGY FORM R405-2014 INDICATES IT IS NOT |
| A WORSE CASE ON PAGE 1. |
| 3) COMMENT #4: RE-SUBMITTED FORM R405-2014 : A) PAGE 1 |
| INDICATES 98.7 KBTU/HR FOR 2263 SQ.FT.- ONE OF THESE |
| VALUES IS INCORRECT. B) PAGE 3- THE COOLING SYSTEM DATA |
| DOES NOT INDICATE A COOLING CAPACITY VALUE, AND THE |
| 2960 AIR FLOW CFM'S DOES NOT MATCH THE CFM'S INDICATED |
| IN THE AC EQUIPMENT SCHEDULE ON M101. |
| 4) COMMENTS #6, 8,9,10,11,12,13,&14- NO RESPONSES OR |
| REVISIONS WERE PROVIDED: REFER TO 1ST REVIEW COMMENTS |
| AND COMPLY. PLEASE NOTE IN REGARD TO COMMENT #9- THE |
| PLUMBING PLANS LIST THE WATER HEATER CAPACTITY AT 199 |
| CFH NOT AT 34 KBTUH, |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |
| [email protected] |
| |
| |