2015-10-22 10:12:50 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE PLANS WILL NEED TO BE DIVIDED INTO TWO SEPARATE |
| SUBMITTAL PACKAGES SUCH THAT ALL OF THE DRAWINGS AND |
| CONSTRUCTION DOCUMENTS FOR THE 6 TOWNHOUSE UNIT A |
| BUILDING ARE IN ONE AND THE DRAWINGS AND CONSTRUCTION |
| DOCUMENTS FOR THE 8 TOWNHOUSE UNIT B BUILDING ARE IN |
| THE OTHER. THIS WILL PROVIDE CLARIFICATION FOR RECORD |
| MANAGEMENT AND HELP TO AVOID CONFUSION AND DELAYS IN |
| THE FIELD DUE TO FAILED INSPECTIONS. FBC 107.2.1.4 |
| |
| 2) THE SURVEY SPECIFIES THE PROPERTY AS BEING IN FLOOD |
| ZONE B WHEN IT IS ACTUALLY IN FLOOD ZONE C. IF NOT |
| CORRECTED, THIS MAY RESULT IN THE HOMEOWNERS PAYING |
| MORE FOR FLOOD INSURANCE. |
| |
| 3) THE FLOOR PLANS AND ELEVATIONS SHOW THE ADJACENT |
| INTERIOR UNITS WITH WINDOWS ON THE ZERO LOT LINE, WHICH |
| IS NOT ALLOWED. FBC-R302.1 |
| |
| 4) THE NOTE STATING THAT THE WINDOWS IN THE SIDE WALL |
| ARE ONLY ON THE END UNITS IS MISSING FROM SHEET A-1.7 |
| |
| 5) PROVIDE A DETAIL FOR THE 2 HOUR FIRE RATED COMMON |
| WALL BETWEEN DWELLING UNITS AND DETACHED GARAGES THAT |
| SHOWS COMPLIANCE WITH FBC-R302.2 TOWNHOUSES. |
| EACH TOWNHOUSE SHALL BE CONSIDERED A SEPARATE BUILDING |
| AND SHALL BE SEPARATED BY FIRE-RESISTANCE-RATED WALL |
| ASSEMBLIES MEETING THE REQUIREMENTS OF SECTION R302.1 |
| FOR EXTERIOR WALLS. EXCEPTION: A COMMON 2-HOUR |
| FIRE-RESISTANCE-RATED WALL ASSEMBLY TESTED IN |
| ACCORDANCE WITH ASTM E 119 OR UL 263 IS PERMITTED FOR |
| TOWNHOUSES IF SUCH WALLS DO NOT CONTAIN PLUMBING OR |
| MECHANICAL EQUIPMENT, DUCTS OR VENTS IN THE CAVITY OF |
| THE COMMON WALL, UNLESS SUCH MATERIALS AND METHODS OF |
| PENETRATION COMPLY WITH SECTION R302.4. THE WALL SHALL |
| BE RATED FOR FIRE EXPOSURE FROM BOTH SIDES AND SHALL |
| EXTEND TO AND BE TIGHT AGAINST EXTERIOR WALLS AND THE |
| UNDERSIDE OF THE ROOF SHEATHING. ELECTRICAL |
| INSTALLATIONS SHALL BE INSTALLED IN ACCORDANCE WITH |
| CHAPTER 34. PENETRATIONS OF ELECTRICAL OUTLET BOXES |
| SHALL BE IN ACCORDANCE WITH SECTION R302.4. |
| |
| 6) SHOW COMPLIANCE WITH R302.2.4 STRUCTURAL |
| INDEPENDENCE. EACH INDIVIDUAL TOWNHOUSE SHALL BE |
| STRUCTURALLY INDEPENDENT. |
| |
| 7) SHOW COMPLIANCE WITH FBC-R302.2.2 PARAPETS. |
| PARAPETS CONSTRUCTED IN ACCORDANCE WITH SECTION |
| R302.2.3 SHALL BE CONSTRUCTED FOR TOWNHOUSES AS AN |
| EXTENSION OF EXTERIOR WALLS OR COMMON WALLS IN |
| ACCORDANCE WITH THE FOLLOWING: |
| 1. WHERE ROOF SURFACES ADJACENT TO THE WALL OR WALLS |
| ARE AT THE SAME ELEVATION, THE PARAPET SHALL EXTEND NOT |
| LESS THAN 30 INCHES ABOVE THE ROOF SURFACES. |
| 2. WHERE ROOF SURFACES ADJACENT TO THE WALL OR WALLS |
| ARE AT DIFFERENT ELEVATIONS AND THE HIGHER ROOF IS NOT |
| MORE THAN 30 INCHES ABOVE THE LOWER ROOF, THE PARAPET |
| SHALL EXTEND NOT LESS THAN 30 INCHES ABOVE THE LOWER |
| ROOF SURFACE. |
| EXCEPTION: A PARAPET IS NOT REQUIRED IN THE TWO CASES |
| ABOVE WHEN THE ROOF IS COVERED WITH A MINIMUM CLASS C |
| ROOF COVERING, AND THE ROOF DECKING OR SHEATHING IS OF |
| NONCOMBUSTIBLE MATERIALS OR APPROVED |
| FIRE-RETARDANT-TREATED WOOD FOR A DISTANCE OF 4 FEET ON |
| EACH SIDE OF THE WALL OR WALLS, OR ONE LAYER OF |
| 5/8-INCH TYPE X GYPSUM BOARD IS INSTALLED DIRECTLY |
| BENEATH THE ROOF DECKING OR SHEATHING, SUPPORTED BY A |
| MINIMUM OF NOMINAL 2-INCH LEDGERS ATTACHED TO THE SIDES |
| OF THE ROOF FRAMING MEMBERS, FOR A MINIMUM DISTANCE OF |
| 4 FEET ON EACH SIDE OF THE WALL OR WALLS AND THERE ARE |
| NO OPENINGS OR PENETRATIONS IN THE ROOF WITHIN 4 FEET |
| OF THE COMMON WALLS. |
| 3. A PARAPET IS NOT REQUIRED WHERE ROOF SURFACES |
| ADJACENT TO THE WALL OR WALLS ARE AT DIFFERENT |
| ELEVATIONS AND THE HIGHER ROOF IS MORE THAN 30 INCHES |
| ABOVE THE LOWER ROOF. THE COMMON WALL CONSTRUCTION FROM |
| THE LOWER ROOF TO THE UNDERSIDE OF THE HIGHER ROOF DECK |
| SHALL HAVE NOT LESS THAN A 1-HOUR FIRE-RESISTANCE |
| RATING. THE WALL SHALL BE RATED FOR EXPOSURE FROM BOTH |
| SIDES. |
| |
| 8) SHOW COMPLIANCE WITH FBC-R302.2.3 PARAPET |
| CONSTRUCTION. |
| PARAPETS SHALL HAVE THE SAME FIRE-RESISTANCE RATING AS |
| THAT REQUIRED FOR THE SUPPORTING WALL OR WALLS. ON ANY |
| SIDE ADJACENT TO A ROOF SURFACE, THE PARAPET SHALL HAVE |
| NONCOMBUSTIBLE FACES FOR THE UPPERMOST 18 INCHES, TO |
| INCLUDE COUNTERFLASHING AND COPING MATERIALS. WHERE THE |
| ROOF SLOPES TOWARD A PARAPET AT SLOPES GREATER THAN 2 |
| UNITS VERTICAL IN 12 UNITS HORIZONTAL, THE PARAPET |
| SHALL EXTEND TO THE SAME HEIGHT AS ANY PORTION OF THE |
| ROOF WITHIN A DISTANCE OF 3 FEET, BUT IN NO CASE SHALL |
| THE HEIGHT BE LESS THAN 30 INCHES. |
| |
| 9) THERE IS A NOTE ON THE ROOF FRAMING PLANS FOR |
| BUILDING A THAT STATES SEE DETAIL 10/S5 FOR PLYWOOD |
| NAILING PATTERN. THERE IS NO DETAIL 10 ON SHEET S5. FBC |
| 107.2.1 |
| |
| 10) THERE IS A NOTE ON THE ROOF FRAMING PLANS FOR |
| BUILDING B THAT STATES SEE DETAIL 1/S12 FOR PLYWOOD |
| NAILING PATTERN. DETAIL 1 ON SHEET S12 DOES NOT PROVIDE |
| THE PLYWOOD NAILING PATTERN. THE NAILING FOR THE ROOF |
| SHEATHING IS SPECIFIED ON DETAIL 4 ON S15. FBC 107.2.1 |
| |
| 11) SHOW COMPLIANCE WITH FBC-R302.5.1 OPENING |
| PROTECTION. OPENINGS BETWEEN THE GARAGE AND RESIDENCE |
| SHALL BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN |
| 1-3/8 INCHES IN THICKNESS, SOLID OR HONEYCOMB-CORE |
| STEEL DOORS NOT LESS THAN 1-3/8 INCHES THICK, OR |
| 20-MINUTE FIRE-RATED DOORS, EQUIPPED WITH A |
| SELF-CLOSING DEVICE. |
| |
| 12) SHOW COMPLIANCE WITH FBC-R302.6 DWELLING/GARAGE |
| FIRE SEPARATION. THE GARAGE SHALL BE SEPARATED AS |
| REQUIRED BY TABLE R302.6. OPENINGS IN GARAGE WALLS |
| SHALL COMPLY WITH SECTION R302.5. THIS PROVISION DOES |
| NOT APPLY TO GARAGE WALLS THAT ARE PERPENDICULAR TO THE |
| ADJACENT DWELLING UNIT WALL. |
| |
| 13) SHOW COMPLIANCE WITH FBC-R311.7.8.1 HANDRAIL |
| HEIGHT, MEASURED VERTICALLY FROM THE SLOPED PLANE |
| ADJOINING THE TREAD NOSING, OR FINISH SURFACE OF RAMP |
| SLOPE, SHALL BE NOT LESS THAN 34 INCHES (864 MM) AND |
| NOT MORE THAN 38 INCHES (965 MM). |
| |
| 14) SHOW COMPLIANCE WITH FBC-R806.1 VENTILATION |
| REQUIRED. ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES |
| FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE |
| UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION |
| FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS |
| PROTECTED AGAINST THE ENTRANCE OF RAIN OR SNOW. |
| VENTILATION OPENINGS SHALL HAVE A LEAST DIMENSION OF |
| 1/16 INCH MINIMUM AND 1/4 INCH MAXIMUM. VENTILATION |
| OPENINGS HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH |
| SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH |
| SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL WITH |
| OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH MINIMUM |
| AND 1/4 INCH MAXIMUM. OPENINGS IN ROOF FRAMING MEMBERS |
| SHALL CONFORM TO THE REQUIREMENTS OF SECTION R802.1.8. |
| REQUIRED VENTILATION OPENINGS SHALL OPEN DIRECTLY TO |
| THE OUTSIDE AIR. |
| |
| 15) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF |
| THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES, |
| STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES (INCLUDING |
| SECTIONAL GARAGE DOORS). |
| THE FOLLOWING IS A LINK TO THE MIAMI - DADE PRODUCT |
| APPROVAL WEBSITE. |
| HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP |
| THE FOLLOWING IS A LINK TO THE FLORIDA PRODUCT APPROVAL |
| WEBSITE. |
| HTTPS://FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX |
| |
| 16) THE ENERGY PERFORMANCE EVALUATION FORM CONTAINS |
| ERRORS AND IS MISSING INFORMATION. THE FORMS REQUIRE |
| THE SIGNATURE OF THE OWNER/AGENT. THE STREET IS LAKE |
| AVE. AND NOT LAKE WORTH AVE. THE CITY IS WEST PALM |
| BEACH AND NOT LANTANA. THE JURIDICTION NUMBER IS |
| 604700. THE UNITS DO NOT MEET THE CRITERIA IN FBC |
| ENERGY CONSERVATION SECTION R405.7.4 TO USE THE CROSS |
| VENTILATION OPTION CREDIT. |
| |
| 17) THERE IS AN OVER-TYPE ERROR IN THE TITLE BLOCK OF |
| SHEETS S10, S11, S12 AND S13. FBC 107.2.1 |
| |
| 18) SPECIFY THE TYPE OF CONSTRUCTION AND OCCUPANCY ON |
| THE PLANS. THE CONSTRUCTION IS TYPE V-B AND TOWNHOUSES |
| ARE R-3 OCCUPANCIES. FBC 601 AND FBC 302.1 |
| |
| 19) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| RE-SUBMITTAL PROCEDURE |
| YOU ARE REQUIRED TO FILL OUT A RE-SUBMITTAL FORM TO BE |
| SUBMITTED WITH THE CORRECTED PLANS AND/OR OTHER |
| DOCUMENTS. THE PERMIT CLERK WILL RETRIEVE THE DENIED |
| APPLICATION, PLANS AND OTHER DOCUMENTS FOR YOU. YOU ARE |
| REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT HAVE BEEN |
| CORRECTED AND REPLACE THEM WITH THE NEW ONES. THE CLERK |
| WILL PROVIDE YOU WITH A STAPLE REMOVER AND A STAPLER. |
| ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN REMOVED |
| SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG WITH |
| THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED |
| SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED |
| FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS, |
| RESUBMIT THOSE SHEETS. |
| IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO |
| (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS |
| SHALL BE SUBMITTED. |
| |
| |