Plan Review Notes For Permit 15090394 |
Permit Number |
15090394 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2016-03-30 11:34:33 | APPROVED WITH PROVISOS AS MENTIONED BELOW: | | I REVIEWED THE NEWLY SUBMITTED SHEETS YESTERDAY AND | | FOUND A FEW MINOR ISSUES THAT I BELIEVE CAN BE | | ADDRESSED WITH A PROVISO AS LONG AS THE DESIGN | | PROFESSIONAL AGREES WITH THESE ITEMS. THEY ARE AS | | MENTIONED BELOW: | | | | 1. SHEET E101: FIRE ALARM NOTES 2 QUOTES THE 2008 | | EDITION OF THE NEC WHEN IN FACT THE APPLICABLE CODE | | WOULD BE THE 2011 EDITION. CORRECT ACCORDINGLY. | | 2. INITIALLY WE HAD DISCUSSED THAT THE HOUSE METER AND | | PANEL WOULD BE ON THE BLDG. A WALL, THE PLAN CALL FOR A | | UNI-STRUT STRUCTURE TO SUPPORT THESE ITEMS. IF THIS IS | | FACT WHAT IS PLANNED, PLEASE MAKE CERTAIN THAT ALL | | SHARP EDGES OF THE UNI-STRUT BE PROTECTED WITH END CAPS | | AND THAT THERE BE PROTECTION FROM PHYSICAL DAMAGE IF | | REQUIRED. | | 3. SHEET E102: THOUGH THE END RESULT WILL NOT VARY, THE | | ELECTRICAL LOAD CALCS DO NOT APPEAR TO BE CORRECT. | | 4. SHEET E201: REMINDER THAT THE REQUIRED UTILITY | | EASEMENTS SHALL BE FILES BEFORE ANY FINALS CAN BE | | SECURED. | | 5. NEC 300.5(D)(3) REQUIRES THAT THERE BE A CAUTION | | RIBBON PLACED IN THE SERVICE TRENCH 12"ABOVE THE | | RACEWAYS. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] |
|