2016-03-30 11:34:33APPROVED WITH PROVISOS AS MENTIONED BELOW:
 I REVIEWED THE NEWLY SUBMITTED SHEETS YESTERDAY AND
 FOUND A FEW MINOR ISSUES THAT I BELIEVE CAN BE
 ADDRESSED WITH A PROVISO AS LONG AS THE DESIGN
 PROFESSIONAL AGREES WITH THESE ITEMS. THEY ARE AS
 MENTIONED BELOW:
  
 1. SHEET E101: FIRE ALARM NOTES 2 QUOTES THE 2008
 EDITION OF THE NEC WHEN IN FACT THE APPLICABLE CODE
 WOULD BE THE 2011 EDITION. CORRECT ACCORDINGLY.
 2. INITIALLY WE HAD DISCUSSED THAT THE HOUSE METER AND
 PANEL WOULD BE ON THE BLDG. A WALL, THE PLAN CALL FOR A
 UNI-STRUT STRUCTURE TO SUPPORT THESE ITEMS. IF THIS IS
 FACT WHAT IS PLANNED, PLEASE MAKE CERTAIN THAT ALL
 SHARP EDGES OF THE UNI-STRUT BE PROTECTED WITH END CAPS
 AND THAT THERE BE PROTECTION FROM PHYSICAL DAMAGE IF
 REQUIRED.
 3. SHEET E102: THOUGH THE END RESULT WILL NOT VARY, THE
 ELECTRICAL LOAD CALCS DO NOT APPEAR TO BE CORRECT.
 4. SHEET E201: REMINDER THAT THE REQUIRED UTILITY
 EASEMENTS SHALL BE FILES BEFORE ANY FINALS CAN BE
 SECURED.
 5. NEC 300.5(D)(3) REQUIRES THAT THERE BE A CAUTION
 RIBBON PLACED IN THE SERVICE TRENCH 12"ABOVE THE
 RACEWAYS.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER