2016-02-17 17:24:00 | PLAN |
| REVIEW COMMENTS |
| |
| 3RD REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE SURVEY SPECIFIES THE PROPERTY AS BEING IN FLOOD |
| ZONE B WHEN IT IS ACTUALLY IN FLOOD ZONE C. IF NOT |
| CORRECTED, THIS MAY RESULT IN THE HOMEOWNERS PAYING |
| MORE FOR FLOOD INSURANCE. |
| I DID NOT FIND THE NEW SURVEY THAT WAS REFERENCED IN |
| YOUR RESPONSE LETTER IN THE RE-SUBMITTAL. TWO COPIES OF |
| THE CORRECTED SURVEY ARE REQUIRED. BECAUSE THESE ARE |
| FEE SIMPLE TOWNHOUSES, TWO SETS OF INDIVIDUAL SURVEYS |
| FOR EACH LOT ARE REQUIRED FOR EACH UNIT. |
| |
| 2) SHOW COMPLIANCE WITH FBC-R806.1 VENTILATION |
| REQUIRED. ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES |
| FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE |
| UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION |
| FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS |
| PROTECTED AGAINST THE ENTRANCE OF RAIN OR SNOW. SUBMIT |
| TWO COPIES OF THE PRODUCT APPROVALS AND MANUFACTURER'S |
| SPECIFICATIONS FOR THE 18" DIAMETER INTAKE AND EXHAUST |
| ATTIC VENTS ON THE ROOF. PROVIDE INFORMATION TO SHOW |
| THAT THEY WILL PROVIDE THE REQUIRED ATTIC VENTILATION. |
| |
| 3) THE PRODUCT APPROVALS WILL BE A PROVISO ITEM TO BE |
| SUBMITTED FOR REVIEW AND APPROVAL AT A LATER DATE PRIOR |
| TO INSTALLATION AS REQUESTED. FBC 107.3.4 - PROVIDE TWO |
| SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| REGULATED BY DCA RULE 9N-3 THAT HAVE BEEN REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE |
| TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS |
| INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN |
| PRESSURES FOR EACH OF THE DIFFERENT ROOFING MATERIALS, |
| WINDOW/GLASS TYPES, STRUCTURAL MULLIONS AND EXTERIOR |
| DOOR TYPES (INCLUDING SECTIONAL GARAGE DOORS). |
| |
| 4) THE ENERGY PERFORMANCE EVALUATION FORM CONTAINS |
| ERRORS AND IS MISSING INFORMATION. THE FORMS REQUIRE |
| THE SIGNATURE OF THE OWNER/AGENT. INDICATE THE CORRECT |
| ADDRESS ON THE ENERGY FORM FOR THAT SPECIFIC UNIT. |
| |
| 5) SHEETS 1, 2 AND 5 FROM FRANCIS ENGINEERING ( FIRE |
| SPRINKLER PLANS? ) ARE MISSING. A SEPARATE PERMIT, |
| APPLICATION AND REVIEW OF FIRE SPRINKLER PLANS ARE |
| REQUIRED TO BE SUBMITTED AT A LATER DATE PER YOUR |
| REQUEST. |
| |
| 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |