Date |
Text |
2015-12-22 17:33:49 | DECEMBER 22ND, 2015 2ND. ELECTRICAL REVIEW |
| |
| RE: RESPONSE TO FIRST REVIEW COMMENTS FOR THE PARK |
| SLOPE TOWNHOUSES. |
| |
| BELOW IS MY RESPONSE TO YOUR COMMENTS. PLEASE NOTE THAT |
| THEY APPEAR IN THE SAME ORDER IN WHICH YOU SUBMITTED |
| THEM TO ME. |
| |
| 10) I INFORMED YOU THAT WE WILL NEED A COPY OF THE |
| RECORDED EASEMENTS BEFORE WE CAN APPROVE THE ELECTRICAL |
| REVIEW. YOU DELEGATED TO SOMEONE ELSE, BUT REGARDLESS |
| OF WHO SECURES THE EASEMENTS. A COPY OF THE RECORDED |
| DOCUMENTS SHALL ACCOMPANY YOUR SUBMITTAL PRIOR TO |
| APPROVAL. |
| |
| 11) WE ALREADY ESTABLISHED A SEPARATE PERMIT FOR THE |
| HOUSE METER AND OTHER ITEMS RELATED THERETO. |
| |
| 12) WE CONCUR ON THE POOL PERMIT ISSUE. |
| |
| 13) YOU CORRECTED THE NOTE BUT INCORRECT CODE |
| REFERENCES REMAIN. THE PROPER CODES TO FOLLOW ARE: THE |
| FLORIDA FIRE PREVENTION CODE (FFPC) 2012, NFPA 70 |
| (NATIONAL ELECTRICAL CODE) 2011, NFPA 72 2010 EDITION, |
| AND THE 5TH EDITION OF THE 2014 FLORIDA BUILDING CODE |
| (FBC). CORRECT YOUR NOTE ACCORDINGLY. |
| |
| 17) YOU CONTINUE TO REFER TO A NONEXISTENT CABLE. BX |
| CABLE IS NOT RECOGNIZED IN THE CODE BOOK. |
| |
| 30 - 35) REFER TO SHEET E401 & E402 WHICH WAS NOT |
| PROVIDED. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME. HAVE A VERY MERRY CHRISTMAS AND A |
| PROSPEROUS 2016. |
| |
| MIKE ALBARRAN, |
| ELECTRICAL PLANS EXAMINER |
| (561) 805-6746 |
| [email protected] |