2015-12-22 17:33:49DECEMBER 22ND, 2015 2ND. ELECTRICAL REVIEW
  
 RE: RESPONSE TO FIRST REVIEW COMMENTS FOR THE PARK
 SLOPE TOWNHOUSES.
  
 BELOW IS MY RESPONSE TO YOUR COMMENTS. PLEASE NOTE THAT
 THEY APPEAR IN THE SAME ORDER IN WHICH YOU SUBMITTED
 THEM TO ME.
  
 10) I INFORMED YOU THAT WE WILL NEED A COPY OF THE
 RECORDED EASEMENTS BEFORE WE CAN APPROVE THE ELECTRICAL
 REVIEW. YOU DELEGATED TO SOMEONE ELSE, BUT REGARDLESS
 OF WHO SECURES THE EASEMENTS. A COPY OF THE RECORDED
 DOCUMENTS SHALL ACCOMPANY YOUR SUBMITTAL PRIOR TO
 APPROVAL.
  
 11) WE ALREADY ESTABLISHED A SEPARATE PERMIT FOR THE
 HOUSE METER AND OTHER ITEMS RELATED THERETO.
  
 12) WE CONCUR ON THE POOL PERMIT ISSUE.
  
 13) YOU CORRECTED THE NOTE BUT INCORRECT CODE
 REFERENCES REMAIN. THE PROPER CODES TO FOLLOW ARE: THE
 FLORIDA FIRE PREVENTION CODE (FFPC) 2012, NFPA 70
 (NATIONAL ELECTRICAL CODE) 2011, NFPA 72 2010 EDITION,
 AND THE 5TH EDITION OF THE 2014 FLORIDA BUILDING CODE
 (FBC). CORRECT YOUR NOTE ACCORDINGLY.
  
 17) YOU CONTINUE TO REFER TO A NONEXISTENT CABLE. BX
 CABLE IS NOT RECOGNIZED IN THE CODE BOOK.
  
 30 - 35) REFER TO SHEET E401 & E402 WHICH WAS NOT
 PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME. HAVE A VERY MERRY CHRISTMAS AND A
 PROSPEROUS 2016.
  
 MIKE ALBARRAN,
 ELECTRICAL PLANS EXAMINER
 (561) 805-6746