Plan Review Notes
Plan Review Notes For Permit 15090393
Permit Number 15090393
Review Stop M
Sequence Number 1
Notes
Date Text
2015-09-28 17:13:321ST REVIEW: FBC 2014 RESIDENTIAL
 PERMIT #15090393
 9/28/15
  
 1) DESIGN CRITERIA: PLEASE PROVIDE DEFINITIVE DESIGN
 CRITERIA AND CODE DATA ON THE PLANS FOR THE PROPOSED
 PROJECT. AS THE PERMIT APPLICATIONS INDICATE "TOWN
 HOMES" I AM REVIEWING THE PLANS FOR COMPLIANCE WITH THE
 FBC-14 RESIDENTIAL CODE. PLEASE REVIEW AND REVISE WHERE
 REQUIRED.
 2) CORRECT THE SUBMITTED ENERGY AND HVAC CALCULATIONS
 INDICATING "LANTANA, FL." IN THE TITLE ADDRESSES- THE
 PROPOSED PROJECT IS IN THE CITY OF WEST PALM BEACH.
 3) INDIVIDUAL ENERGY CALCULATIONS AND AC COOLING AND
 HEATING CALCULATIONS SHALL BE SUBMITTED SEPARATELY FOR
 EACH TOWN HOME IN ACCORDANCE WITH SECTION R103.1 FBC-14
 ENERGY CONSERVATION- "GENERAL. CONSTRUCTION DOCUMENTS
 AND OTHER SUPPORTING DATA SHALL BE SUBMITTED IN ONE OR
 MORE SETS WITH EACH APPLICATION FOR A PERMIT. THE
 CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY THE
 STATUTES OF THE JURISDICTION IN WHICH THE PROJECT IS TO
 BE CONSTRUCTED. WHERE SPECIAL CONDITIONS EXIST, THE
 CODE OFFICIAL IS AUTHORIZED TO REQUIRE NECESSARY
 CONSTRUCTION DOCUMENTS TO BE PREPARED BY A REGISTERED
 DESIGN PROFESSIONAL." EACH SUBMITTAL DOCUMENT SHALL
 BEAR THE SAME ADDRESS AS THE ONE LISTED ON THE
 CORRESPONDING PERMIT APPLICATION, AND MANUAL J AC
 SIZING WORKSHEETS SHALL BE SUBMITTED FOR EACH NEW TOWN
 HOME INDICATING DIRECTIONAL ORIENTATIONS AND CALCULATED
 LOADS FOR EACH INDIVIDUAL TOWN HOME- REFER TO SECTION
 R403.6.1 FBC-14 ENERGY CONSERVATION- "WORST CASE
 SCENARIOS" FOR EACH BUILDING ARE NOT ACCEPTABLE.
 4) REVIEW OF THE SUBMITTED ENERGY EFFICIENCY FORM
 R405-2014 FOR BLDG. A REVEALED THESE DEFICIENCIES: A)
 THE SQUARE FOOTAGE CALCULATION DOESN'T MATCH THE
 FOOTAGE LISTED ON SHEET A-1.0. B) THE WINDOW U-VALUES
 LISTED DON'T MATCH THE U-VALUES LISTED ON THE AC
 CALCULATIONS. C) THE 18.46 SEER LISTED FOR THE AC
 SYSTEM DOESN'T MATCH THE 17.3 SEER SYSTEMS LISTED IN
 THE AC EQUIPMENT SCHEDULE. D) THE AIRFLOW CFM'S AND
 HEATING CAPACITIES LISTED DON'T MATCH THE AC SCHEDULE.
 E) THERE IS NO COMPLIANCE DATA LISTED FOR THE DOORS,
 INCLUDING THE GARAGE DOOR WHICH IS PART OF THE THERMAL
 ENVELOPE.
 5) REVIEW OF THE SUBMITTED HVAC CALCULATIONS REVEALED
 THESE DEFICIENCIES: A) THE COOLING EQUIPMENT SUMMARIES
 WERE NOT COMPLETED FOR EACH SYSTEM. B) REFER TO COMMENT
 #3.
 6) SHEET M101: CORRECT THE REFERENCES TO THE FBCM SHOWN
 ON THE BUILDING AND GARAGE VENTILATION TABLES. PROVIDE
 CALCULATIONS IN COMPLIANCE WITH THE FBC-14 RESIDENTIAL.
 7) M102, DETAIL A7: THE PRINT IN THE DETAIL AND
 STRAPPING TABLE IS TOO FAINT TO READ AND NEEDS TO BE
 EMBOLDENED FOR REVIEW AND COMPUTER SCANNING. PLEASE
 NOTE THAT THE ROOM ID NUMBERS SHOWN ON ALL OF THE
 LAYOUT PLANS ALSO NEED TO BE EMBOLDENED.
 8) M102, DETAIL C7: INDICATE THE TYPE AND SIZE OF
 CONDENSATE PIPING TO BE INSTALLED.
 9) M301: CORRECT THE REFERENCES TO THE FBCFG ON THE
 RANGE AND DRYER COMBUSTION TABLES. PROVIDE CALCULATIONS
 IN COMPLIANCE WITH THE FBC-14 RESIDENTIAL. PLEASE NOTE
 THE DRYER IN THE CLOSET MUST BE PROVIDED COMBUSTION AIR
 THROUGH OPENINGS IN THE DOORS- SEE SECTION G2407.5.3
 FBC-14 RESIDENTIAL AND PROVIDE SIZING CALCULATIONS AND
 OPENING SIZES.
 10) M301: REFER TO SECTION M1305.1.1 AND SHOW
 COMPLIANCE FOR THE AIR HANDLERS IN THE CLOSETS- PROVIDE
 AN ENLARGED DETAIL IF NECESSARY TO SHOW THE REQUIRED
 CLEARANCE DIMENSIONS.
 11) M301: CORRECT THE 820 CFM'S OF RETURN AIR SHOWN ON
 THE 16"X 16" GRILL IN BEDROOM #A307. CLARIFY HOW ALL
 AIR IS BEING RETURNED TO THE AIR HANDLER- THE PLAN
 SHOWS A LOUVERED DOOR, BUT THE DETAIL ON M102 SHOWS A
 DUCTED RETURN IN THE CLOSET.
 12) M301: THE AIR HANDLER IN THE GARAGE MUST BE
 PROTECTED FROM VEHICLE IMPACT- SEE SECTION M1307.3.1
 AND PROVIDE A BOLLARD OR OTHER APPROVED MEANS OF
 PROTECTION.
 13) SHOW THE CONDENSATE DISPOSAL PIPING RUNS AND
 DISCHARGE LOCATIONS.
 14) SHOW THE REFRIGERANT PIPING RUNS.
 15) PROVIDE A SUBMITTAL PACKAGE CONSISTING OF THE
 RANGE, RANGE HOOD AND EXHAUST DUCT, WATER HEATER AND
 VENT PIPING, DRYER AND VENT PIPING, AC SYSTEMS, AND THE
 VAV BOXES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]