2015-09-11 18:11:34 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| ORIGINALS, FS 471. POOR QUALITY PHOTOCOPIES WERE |
| SUBMITTED. |
| |
| 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| THE SOLAR VENT. PROVIDE THE COVER SHEET WHICH SHOWS THE |
| APPROVAL NUMBER, CODE VERSION, AND STATUS |
| (WWW.FLORIDABUILDING.ORG). IT APPEARS THAT THE |
| EVALUATION REPORT PROVIDED IS EXPIRED AS IT MAKES |
| REFERENCE TO FBC 2010 (GOVERNING CODE IS FBC 5TH |
| EDITION, AKA FBC 2014). |
| |
| 3. SEE INSTALLATION NOTES, ITEM 7.3, "PRODUCT SHALL BE |
| INSTALLED ON ROOFS UTILIZING ASPHALT SHINGLES ONLY". |
| |
| 4. REVISE ROOF PLAN TO SHOW THE LOCATION OF PROPOSED |
| ROOF VENT AND ROOF SHEATHING INFORMATION (TYPE OF ROOF |
| SHEATHING, THICKNESS). THIS INFORMATION IS REQUIRED DUE |
| TO LIMITATIONS FOR THE ROOF VENT. |
| |
| 5. PURPOSE OF PROPOSED VENT IS NOT CLEAR. FLAT DECK |
| ROOFS TYPICALLY DO NOT HAVE AN ATTIC SPACE. WHAT IS |
| BEING VENTED? |
| |
| 6. CONTRACTOR TO CONFIRM THAT A FIRE BARRIER IS |
| PROPOSED. CONTRACTOR HAS SELECTED THE ASSEMBLY ON PAGE |
| 12 OF 13, NOA 12-1019.34, SYSTEM TYPE E. NOTE THAT THE |
| SYSTEM PROPOSED INCLUDES A FIRE BARRIER. THIS IS NOT |
| OPTIONAL. OPTIONAL ITEMS WILL STATE (OPTIONAL); FOR AN |
| EXAMPLE OF AN OPTIONAL COMPONENT, SEE PAGE 9, VAPOR |
| RETARDER. SINCE THE FIRE BARRIER IS NOT "OPTIONAL" IT |
| IS A PART OF THIS ASSEMBLY AND IS REQUIRED. |
| |
| |
| |
| |
| |
| |