Plan Review Notes
Plan Review Notes For Permit 15090376
Permit Number 15090376
Review Stop B
Sequence Number 1
Notes
Date Text
2015-09-11 18:11:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FS 471. POOR QUALITY PHOTOCOPIES WERE
 SUBMITTED.
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE SOLAR VENT. PROVIDE THE COVER SHEET WHICH SHOWS THE
 APPROVAL NUMBER, CODE VERSION, AND STATUS
 (WWW.FLORIDABUILDING.ORG). IT APPEARS THAT THE
 EVALUATION REPORT PROVIDED IS EXPIRED AS IT MAKES
 REFERENCE TO FBC 2010 (GOVERNING CODE IS FBC 5TH
 EDITION, AKA FBC 2014).
  
 3. SEE INSTALLATION NOTES, ITEM 7.3, "PRODUCT SHALL BE
 INSTALLED ON ROOFS UTILIZING ASPHALT SHINGLES ONLY".
  
 4. REVISE ROOF PLAN TO SHOW THE LOCATION OF PROPOSED
 ROOF VENT AND ROOF SHEATHING INFORMATION (TYPE OF ROOF
 SHEATHING, THICKNESS). THIS INFORMATION IS REQUIRED DUE
 TO LIMITATIONS FOR THE ROOF VENT.
  
 5. PURPOSE OF PROPOSED VENT IS NOT CLEAR. FLAT DECK
 ROOFS TYPICALLY DO NOT HAVE AN ATTIC SPACE. WHAT IS
 BEING VENTED?
  
 6. CONTRACTOR TO CONFIRM THAT A FIRE BARRIER IS
 PROPOSED. CONTRACTOR HAS SELECTED THE ASSEMBLY ON PAGE
 12 OF 13, NOA 12-1019.34, SYSTEM TYPE E. NOTE THAT THE
 SYSTEM PROPOSED INCLUDES A FIRE BARRIER. THIS IS NOT
 OPTIONAL. OPTIONAL ITEMS WILL STATE (OPTIONAL); FOR AN
 EXAMPLE OF AN OPTIONAL COMPONENT, SEE PAGE 9, VAPOR
 RETARDER. SINCE THE FIRE BARRIER IS NOT "OPTIONAL" IT
 IS A PART OF THIS ASSEMBLY AND IS REQUIRED.
  
  
  
  
  
  