Plan Review Notes
Plan Review Notes For Permit 15090327
Permit Number 15090327
Review Stop B
Sequence Number 3
Notes
Date Text
2016-07-06 08:34:07RESIDENTIAL (R3) ALTERATION THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2014 FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 NOTE: PLANS AND ENERGY CALCULATIONS TO BE COORDINATED
 TO AVOID CONFLICTS OR DELAYS.
 RESPONSE: REPEAT COMMENT. THIRD TIME. NOT ADDRESSED.
 PERMIT CAN NOT BE ISSUED WITHOUT THE ENERGY
 CALCULATIONS. SEE SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
 RESPONSE: NOA 06-0222.01 SUBMITTED EXPIRED FIVE YEARS
 AGO. 05/21/2011. NEED TO PROVIDE CURRENT NOA. AND,
 PROVIDE COMPLETE NOA NOT JUST THE COVER PAGE.
 NOTE: ARCHITECT REVIEWING THE PRODUCT APPROVAL TO
 PLEASE STAMP THE FRONT PAGE OF THE PRODUCT APPROVAL NOT
 THE BACK OF IT.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  