Plan Review Notes For Permit 15090327 |
Permit Number |
15090327 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-07-11 09:20:09 | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED. | | | | FLORIDA ENERGY CODE FBC 2014 | | | | (1) PROVIDE ENERGY CALCULATIONS FORM R402-2014 OR FORM | | R405-2014. CONFIRM BOTH "PREPARED BY" AND "OWNER/AGENT" | | SIGNATURES ARE PRESENT. | | (2) PROVIDE MANUAL J HEAT LOAD CALCULATIONS. | | | | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | (3) PROVIDE A COMPLETE SET OF PLANS. SHOW ALL DUCTWORK | | IN THE RESIDENCE. DIFFERENTIATE NEW AND EXISTING | | DUCTWORK. SHOW ALL CFM FOR ALL AREAS OF HOME. SHOW ALL | | RETURNS FROM BEDROOMS. | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | | | |
|