2015-10-27 17:31:58 | RESIDENTIAL (R3) ALTERATION/CONVERSION BUILDING REVIEW |
| COMMENTS. |
| CODE: 2014 FBC 5TH EDITION (2014). |
| |
| 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) |
| FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| CODE. |
| |
| 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| NOTE: PLANS AND ENERGY CALCULATIONS TO BE COORDINATED |
| TO AVOID CONFLICTS OR DELAYS. |
| |
| 3- SIZES OF WINDOWS SHOWN ON THE FLOOR PLAN ON SHEET |
| A.2 DON'T MATCH SIZES SHOWN ON THE EXTERIOR ELEVATIONS. |
| WINDOWS SHOWN ON THE EXTERIOR ELEVATIONS DON'T COMPLY |
| WITH EGRESS. PROVIDE CLEAR INFORMATION FOR THE EGRESS |
| WINDOW OF THE NEW BEDROOM SHOWING COMPLIANCE WITH ALL |
| THE REQUIREMENTS OF SEC. R310 OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| |
| 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) STORM SHUTTERS. AND, PROVIDE COMPLETE INSTALLATION. |
| SEE CITY SAMPLE FOR SHUTTERS INSTALLATION SCHEDULE. |
| NOTE: SHUTTERS REQUIRED BECAUSE WINDOWS PRODUCT |
| APPROVAL SUBMITTED IS FOR NON-IMPACT WINDOWS. |
| |
| B) WINDOW MULLIONS. AND, CLEARLY MARK SIZE TO BE |
| INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION |
| (2014). |
| NOTE: PROVIDE 2 COPIES. ONLY ONE COPY WAS SUBMITTED |
| THIS TIME. AND PROVIDE COMPLETE DRAWINGS. NOA |
| 11-1213.07 SUBMITTED IS MISSING SHEETS 4 OF 6 TO 6 OF |
| 6. |
| |
| C) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| 5- DESIGNER OF RECORD TO APPROVE IN WRITING (NOT |
| SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE |
| OLD/VOID DRAWINGS TO RESUBMITTED SET OF DRAWINGS. |
| SUBMIT OLD/VOID DRAWINGS FOR REFERENCE. |
| |