2015-09-09 19:04:33 | APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED |
| PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL |
| RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF |
| RE-INSPECTION FEE(S). |
| |
| 1) R703.2 WEATHER-RESISTANT SHEATHING PAPER. |
| ONE LAYER OF NO. 15 ASPHALT FELT, FREE FROM HOLES AND |
| BREAKS, COMPLYING WITH ASTM D 226 FOR TYPE 1 FELT OR |
| OTHER APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED |
| OVER STUDS OR SHEATHING OF ALL EXTERIOR WALLS. SUCH |
| FELT OR MATERIAL SHALL BE APPLIED HORIZONTALLY, WITH |
| THE UPPER LAYER LAPPED OVER THE LOWER LAYER NOT LESS |
| THAN 2 INCHES (51 MM). WHERE JOINTS OCCUR, FELT SHALL |
| BE LAPPED NOT LESS THAN 6 INCHES (152 MM). THE FELT OR |
| OTHER APPROVED MATERIAL SHALL BE CONTINUOUS TO THE TOP |
| OF WALLS AND TERMINATED AT PENETRATIONS AND BUILDING |
| APPENDAGES IN A MANNER TO MEET THE REQUIREMENTS OF THE |
| EXTERIOR WALL ENVELOPE AS DESCRIBED IN SECTION R703.1. |
| |
| |
| 2) SUBMIT TWO SETS OF PRODUCT APPROVALS WITH |
| INSTALLATION INSTRUCTIONS FOR THE EXTERIOR CEMENT PANEL |
| SHEATHING. 703.1.2 WIND RESISTANCE. WALL COVERINGS, |
| BACKING MATERIALS AND THEIR ATTACHMENTS SHALL BE |
| CAPABLE OF RESISTING WIND LOADS IN ACCORDANCE WITH |
| TABLES R301.2(2) AND R301.2(3). WIND-PRESSURE |
| RESISTANCE OF THE SIDING AND BACKING MATERIALS SHALL BE |
| DETERMINED BY ASTM E 330 OR OTHER APPLICABLE STANDARD |
| TEST METHODS. |