Plan Review Notes
Plan Review Notes For Permit 15090236
Permit Number 15090236
Review Stop P
Sequence Number 1
Notes
Date Text
2015-09-29 11:33:271) SHT. C-7 - INDICATE ON THE PLAN WHICH GREASE TRAP
 SERVES WHICH RESTAURANT. WPB AMENDMENTS TO FBC SEC.
 107.2.1.
 2) SHT. C-7 - HOW WERE THE SIZE OF THE GREASE TRAPS
 DETERMINED? SUBMIT FACTORY SIZING CALCULATIONS DONE BY
 SCHIER IN ACCORDANCE WITH THE 2014 FBC- PLUMBING,
 SEC.1003.2. CONTACT LEE SCHNEEWEISS, SCHIER
 REPRESENTATIVE AT 1-800-538-4792.
 3) SHT. A-5 - THE EMERGENCY SCUPPERS SHALL BE LOCATED
 IN WALLS OR PARAPETS NO LESS THAN 2 INCHES NOR MORE
 THAN 4 INCHES ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE SIZED IN ACCORDANCE WITH THE FBC-PLUMBING
 TABLE 1106.7 PER THE FBC SEC.1503.4.2.1.
 4) SUBMIT SIZING CALCULATIONS FOR THE ROOF DRAINAGE.
 SHOW THE SQUARE FOOT AREA OF THE ROOF THAT IS BEING
 DRAINED BY EACH ROOF DRAIN. THE ROOF DRAINS SHALL BE
 SIZED IN ACCORDANCE WITH THE 2014 FBC-PLUMBING TABLE
 1106.2.1 & 1106.3. ONE-HALF OF THE AREA OF ANY VERTICAL
 WALL DIVERTS RAINWATTER TO THE ROOF SHALL BE ADDED TO
 THE PROJECTED ROOF AREA. FBC-PLUMBING SEC.1106.4.
 5) SUBMIT A RAINWATER RISER DIAGRAM PER THE WPB AMEND.
 TO FBC SEC. 107.3.5.1.3.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  