Plan Review Notes For Permit 15090236 |
Permit Number |
15090236 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-09-29 11:33:27 | 1) SHT. C-7 - INDICATE ON THE PLAN WHICH GREASE TRAP | | SERVES WHICH RESTAURANT. WPB AMENDMENTS TO FBC SEC. | | 107.2.1. | | 2) SHT. C-7 - HOW WERE THE SIZE OF THE GREASE TRAPS | | DETERMINED? SUBMIT FACTORY SIZING CALCULATIONS DONE BY | | SCHIER IN ACCORDANCE WITH THE 2014 FBC- PLUMBING, | | SEC.1003.2. CONTACT LEE SCHNEEWEISS, SCHIER | | REPRESENTATIVE AT 1-800-538-4792. | | 3) SHT. A-5 - THE EMERGENCY SCUPPERS SHALL BE LOCATED | | IN WALLS OR PARAPETS NO LESS THAN 2 INCHES NOR MORE | | THAN 4 INCHES ABOVE THE FINISHED ROOF COVERING AND | | SHALL BE SIZED IN ACCORDANCE WITH THE FBC-PLUMBING | | TABLE 1106.7 PER THE FBC SEC.1503.4.2.1. | | 4) SUBMIT SIZING CALCULATIONS FOR THE ROOF DRAINAGE. | | SHOW THE SQUARE FOOT AREA OF THE ROOF THAT IS BEING | | DRAINED BY EACH ROOF DRAIN. THE ROOF DRAINS SHALL BE | | SIZED IN ACCORDANCE WITH THE 2014 FBC-PLUMBING TABLE | | 1106.2.1 & 1106.3. ONE-HALF OF THE AREA OF ANY VERTICAL | | WALL DIVERTS RAINWATTER TO THE ROOF SHALL BE ADDED TO | | THE PROJECTED ROOF AREA. FBC-PLUMBING SEC.1106.4. | | 5) SUBMIT A RAINWATER RISER DIAGRAM PER THE WPB AMEND. | | TO FBC SEC. 107.3.5.1.3. | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|