Plan Review Notes For Permit 15090236
Permit Number 15090236
Review Stop E
Sequence Number 1
Notes
Date Text
2015-09-25 10:08:18CODE: 2011 EDITION OF THE NEC, 2014/5TH EDITION OF THE
 FBC
 1ST ELECTRICAL PLAN REVIEW FOUNDATION ONLY
 ACTION: DENIED
  
 THERE ARE INSUFFICIENT ELECTRICAL PLANS OR
 SPECIFICATIONS INCLUDED WITH THIS SUBMITTAL. REVISE
 YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) AS A SHELL ONLY REVIEW THE MINIMUM PLAN REVIEW
 CRITERIA SHALL INCLUDE BUT NOT BE LIMITED TO AN
 ELECTRICAL GOUNDING ELECTRODE SYSTEM DESIGN DETAIL PER
 THE NEC ARTICLE 250. SEE NEC 250.30(7) AND 250.50 AND
 250.52
  
 STEVEN KENNEDY, CBO