Date |
Text |
2015-09-29 16:23:26 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15090236 |
| ADD:2101 PALM BEACH LAKES (744343190020900) |
| CONT: LM DEVELOPMENT GROUP |
| TEL: ( 954)476-0800 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: |
| ACTION: DENIED |
| |
| 1) PLEASE NOTE THE ADDRESSES ON THE PERMIT APPLICATION |
| ARE NOT THE CORRECT SITEADDRESS. FOR THE PREOPERTY |
| CONTROL NUMBER (PCN) 74-43-43-19-10-0020090 THE CORRECT |
| SITE ADDRESS IS 2101 PALM BEACH LAKES BLVD. THE PLANS |
| HAVE NO ADDRESS ON THE PLANSAT ALL. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE |
| PROJECT. |
| ADDRESSES ON COMMERCIAL BUILDINGS, ALL CHARACTERS ON |
| BUILDINGS OTHERTHAN SINGLE-FAMILY AND DUPLEXES SHALL BE |
| NO LESS THAN SIX INCHES IN HEIGHT AND ONE INCH IN |
| WIDTH. SEE THE CITY MUNI CODE FOR SECTION 78-6 FOR |
| RANGE OF ADDRESSES FOR A SITE (TENANT ADDRESSING AND |
| MONUMENT SIGNS). |
| |
| 2) PLEASE PROVIDE SIGNED AND SEALED SOILS REPORTS, |
| (ORIGINALS). SUBMITTED IS A COPY. THIS AREA IS KNOWN |
| FOR QUESTIONABLE SOILS. 2014 FBC-B 1803.5.2. |
| |
| 3) THE PROPOSED BUILDING SITE IS ALSO LOCATED IN AN A8 |
| FLOOD ZONE. FLOOD ZONE CERTIFICATES. FBC BUILDING 1612 |
| AND CITY OF WPB CODE OF ORDINANCES SECTION 94-546. |
| STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD |
| ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW |
| CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN |
| ADDITIONAL 6 INCHES OF ELEVATION. THE MINIMUM FLOOR |
| ELEVATION TO BE 16 FT. 6 INCHES NGVD AND ANY ATTENDANT |
| EQUIPMENT PADS (A/C EQUIPMENT PADS). |
| |
| DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| HEIGHT. |
| (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| ELEVATION CERTIFICATE IS REQUIRED |
| (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| ATTENDANTS |
| A/C PADS OR OTHER SLABS FOR GENERATORS |
| FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| JULY 31/2015 |
| FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| |
| 4) THIS BUILDING QUALIFIES FOR A RESIDENT INSPECTOR |
| SINCE THERE IS TO BE ONSITE WELDING. RESIDENT INSPECTOR |
| |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| 2) WELDED OR BOLTED CONNECTIONS |
| |
| 4A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL |
| PARTIES NOTARIZED AND RETURNED TO THE BUILDING |
| DEPARTMENT. |
| FORMS E-MAILED TO: [email protected] 6:07 AM |
| 9/30/2015 WENDY SIMONIN |
| |
| 4B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT: KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 4C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| [email protected] |
| |
| 4D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE |
| PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP |
| INSPECTORS. |
| |
| 4E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 5) SHEET A2 NOTE ON PLANS, THIS BUILDING IS SET BACK |
| FROM ALL OTHER STRUCTURES BY 30 FT.PLEASE NOT ON SHEET |
| C-03 THE NORTHWEST FACE OF THE BUILDING IS LESS THAN 8 |
| FEET FROM THE PROPERTY LINE AND THE SOUTHWEST FACE IS |
| LESS THAN 17 FEET FROM THE PROPERTY LINE. THE |
| COVERSHEET A1 INDICATES THIS BUILDING DESIGN IS A |
| BUILDING TYPE IIIB- UNSPRINKLERED. |
| |
| 5A) THE NORTHWEST FACE OF THE BUILDING WILL NEED TO |
| PROVIDE 1 HOUR FIRE RATED WALLS (TABLE 602) AND AN |
| ALLOWABLE WINDOW UNPROTECTED OF 10%, PLEASE PROVIDE THE |
| AMOUNT OF OPENINGS IN SQUARE FEET ARE IN THIS WALL, |
| NOTE THE SQAURE FOOTAGE OF THE WALL IS ONLY UP TO THE |
| CEILING HEIGHT, NOT THE PARAPET HEIGHT. |
| |
| 5B) THE SOUTHWEST FACE OF THE BUILDING WILL ALSO NEED |
| TO PROVIDE A 1 HOUR FIRE RATED WALL (TABLE 602) AND THE |
| ALLOWABLE AREA OF UNPROTECTED OPENINGS OF 25 % OF THE |
| WALL AREA, PLEASE PROVIDE THE AMOUNT OF OPENINGS IN |
| SQUARE FEET ARE IN THIS WALL, NOTE THE SQAURE FOOTAGE |
| OF THE WALL IS ONLY UP TO THE CEILING HEIGHT, NOT THE |
| PARAPET HEIGHT. |
| |
| 5C) UTILITIES, POTABLE WATER, SEWER, GAS AND ELECTRIAL |
| UTILITIES COME FROM PALM BEACH LAKES WITH THE EXCEPTION |
| OF TELECOMMUNICATIONS, THIS WILL APPEAR TO NEED TO |
| CROSS OVER PARCEL A FOR TIE IN. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 5D) THE SITE DOES HAVE ACCESS TO ROADWAYS BUT THE CIVIL |
| PLANS SHOW ACCESS TO THIS PROPERTY VIA ANOTHER |
| PROPERTY. THE SURVEY DOES HAVE NOTES ON THE DOCUMENT |
| THERE MAYBE COVENENTS AND EASEMENTS NOT SHOWN ON THIS |
| SURVEY. TO GAIN ACCESS FROM ANOTHER PROPERTY PLEASE |
| PROVIDE THE CROSS ACCESS AGREEMENT AND SINCE THE |
| PROPERTY LINE IS SO CLOSE TO THE BUILDING AND ALLOWABLE |
| OPENINGS IS GREATLY REDUCED THERE MAYBE A RESTRIVTIVE |
| COVENENT FOR THE SURROUNDING PARCEL A. IF THERE IS |
| PLEASE PROVIDE DOCUMENTATION THAT WILL CLEAR UP |
| COMMENTS 5A, 5B & 5C. 107.2.1.3 ADDITIONAL INFORMATION |
| IS REQUIRED. |
| |
| 6A) SHEET A3 ROOF PLAN SHOWS THE USE OF ROOF DRAINS AND |
| THROUGH THE WALL OVER FLOW SCUPPERS. PLEASE PROVIDE THE |
| ROOF DRAINAGE CALCULATIONS (INCHES /HR RAINFALL |
| 100-YEAR RAINFALL.) FBC-P FOR THE SIZING OF THE ROOF |
| DRAINS AS WELL AS THE SECONDARY OVERFLOW WALL SCUPPERS. |
| FBC-B 1503.4 |
| |
| 6B) SHEET A5 DETAIL # 8 INDICATES THE USE OF OVERFLOW |
| (EMERGENCY OVERFLOW) DRAINS. THIS DETAIL IS SHOWN TO BE |
| FLUSH WITH THE ROOF, PLEASE SHOW THE OVERFLOW SCUPPERS |
| 2 TO 4 INCHES ABOVE THE FINISH ROOF COVERING. 2014 |
| FBC-B 1504.3.2.1. |
| |
| 6C) THE OVERFLOW SCUPPERS SHEET A5 DETAIL #8 ARE TO BE |
| SIZED SEE FBC-B 1503.4.1. THE INSTALLATION AND SIZING |
| OF SECONDARY EMERGENCY OVERFLOW DRAINS, LEADERS AND |
| CONDUCTORS SHALL COMPLY WITH SECTIONS 1106 & 1107. AS |
| APPLICABLE, OF CHPTER 11 OF THE FLORIDA BUILDING CODE, |
| PLUMBING. |
| |
| 7) NEITHER SHEET S-0 WHICH PROVIDES THE WIND DESIGN |
| CRITERIA OR S2 ROOF FRAMING PLAN PROVIDE THE ACTUAL |
| MEAN ROOF HEIGHT PRESSURES ARE DETERMINED FROM THE MEAN |
| ROOF HEIGHT. 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 8) SHEET S-2 ROOF PRESSURES SHOW THE MINIMUM SQUARE |
| FEET OF 20 SQ.FT. THE MINIMUM SQUARE FEET FOR ROOF |
| ATTACHMENT (FASTENER) IS AT 10 SQUARE FEET NOT 20 |
| SQUARE FEET PLEASE UPDATE PRESSURE CHART OTHERWISE |
| PRESSURES ARE OK. 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 9) SHEET S-5 THE SCALE NOT PROVIDED FOR THIS SHEET |
| ASSUMED 3/16 TH INCH? 107,2,1,3 ADDITIONAL INFORMATION |
| ISREQUIRED. |
| |
| 10) PRESSURES FOR WALL ZONE 4 FOR WINDOWS AND DOORS |
| APPEARS TO BE LOW EVEN FOR A MEAN ROOF HEIGHT OF 15 |
| FEET. FBC-B 1603.1.4. |
| |
| 11) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C): STOREFRONTS,, WALL LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| INSULATION (ROOF CURBS) |
| |
| 12) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 13) THIS PERMIT IS FOR A SHELL BUILDING ONLY, EXEMPT |
| FROM THE ENERGY CODE, NO RTU TO BE INSTALLED UNDER THIS |
| PERMIT, ROOF TOP CURBS TO BE CAPPED. SHEET A5 DETAILS 6 |
| & 7 SHOW ROOF TOP INSULATION OF R-19 VALUE, IS THIS A |
| R-19 VALUE AT THE ROOF DRAINS AS A MINIMUM? NOTE THIS |
| COMMENT WILL BE A PROVISO: AT CONTRACTORS OWN RISK |
| SINCE THERE IS NO ENERGY CALCULATION PROVIDING WHAT |
| VALUE WILL BE PUT ON THE ROOF OP INSULATION USING THE |
| WHOLE BUILDING METHOD 2014 FBC-ENERGY C101.4.8 EXEMPT |
| BUILDINGS & C101.5.2 LOW ENERGY BUILDINGS. |
| |
| 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |