Plan Review Notes
Plan Review Notes For Permit 15090236
Permit Number 15090236
Review Stop B
Sequence Number 1
Notes
Date Text
2015-09-29 16:23:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090236
 ADD:2101 PALM BEACH LAKES (744343190020900)
 CONT: LM DEVELOPMENT GROUP
 TEL: ( 954)476-0800
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) PLEASE NOTE THE ADDRESSES ON THE PERMIT APPLICATION
 ARE NOT THE CORRECT SITEADDRESS. FOR THE PREOPERTY
 CONTROL NUMBER (PCN) 74-43-43-19-10-0020090 THE CORRECT
 SITE ADDRESS IS 2101 PALM BEACH LAKES BLVD. THE PLANS
 HAVE NO ADDRESS ON THE PLANSAT ALL.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROJECT.
 ADDRESSES ON COMMERCIAL BUILDINGS, ALL CHARACTERS ON
 BUILDINGS OTHERTHAN SINGLE-FAMILY AND DUPLEXES SHALL BE
 NO LESS THAN SIX INCHES IN HEIGHT AND ONE INCH IN
 WIDTH. SEE THE CITY MUNI CODE FOR SECTION 78-6 FOR
 RANGE OF ADDRESSES FOR A SITE (TENANT ADDRESSING AND
 MONUMENT SIGNS).
  
 2) PLEASE PROVIDE SIGNED AND SEALED SOILS REPORTS,
 (ORIGINALS). SUBMITTED IS A COPY. THIS AREA IS KNOWN
 FOR QUESTIONABLE SOILS. 2014 FBC-B 1803.5.2.
  
 3) THE PROPOSED BUILDING SITE IS ALSO LOCATED IN AN A8
 FLOOD ZONE. FLOOD ZONE CERTIFICATES. FBC BUILDING 1612
 AND CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW
 CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN
 ADDITIONAL 6 INCHES OF ELEVATION. THE MINIMUM FLOOR
 ELEVATION TO BE 16 FT. 6 INCHES NGVD AND ANY ATTENDANT
 EQUIPMENT PADS (A/C EQUIPMENT PADS).
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 4) THIS BUILDING QUALIFIES FOR A RESIDENT INSPECTOR
 SINCE THERE IS TO BE ONSITE WELDING. RESIDENT INSPECTOR
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2) WELDED OR BOLTED CONNECTIONS
  
 4A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
 FORMS E-MAILED TO: [email protected] 6:07 AM
 9/30/2015 WENDY SIMONIN
  
 4B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT: KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 4C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 4D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 4E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 5) SHEET A2 NOTE ON PLANS, THIS BUILDING IS SET BACK
 FROM ALL OTHER STRUCTURES BY 30 FT.PLEASE NOT ON SHEET
 C-03 THE NORTHWEST FACE OF THE BUILDING IS LESS THAN 8
 FEET FROM THE PROPERTY LINE AND THE SOUTHWEST FACE IS
 LESS THAN 17 FEET FROM THE PROPERTY LINE. THE
 COVERSHEET A1 INDICATES THIS BUILDING DESIGN IS A
 BUILDING TYPE IIIB- UNSPRINKLERED.
  
 5A) THE NORTHWEST FACE OF THE BUILDING WILL NEED TO
 PROVIDE 1 HOUR FIRE RATED WALLS (TABLE 602) AND AN
 ALLOWABLE WINDOW UNPROTECTED OF 10%, PLEASE PROVIDE THE
 AMOUNT OF OPENINGS IN SQUARE FEET ARE IN THIS WALL,
 NOTE THE SQAURE FOOTAGE OF THE WALL IS ONLY UP TO THE
 CEILING HEIGHT, NOT THE PARAPET HEIGHT.
  
 5B) THE SOUTHWEST FACE OF THE BUILDING WILL ALSO NEED
 TO PROVIDE A 1 HOUR FIRE RATED WALL (TABLE 602) AND THE
 ALLOWABLE AREA OF UNPROTECTED OPENINGS OF 25 % OF THE
 WALL AREA, PLEASE PROVIDE THE AMOUNT OF OPENINGS IN
 SQUARE FEET ARE IN THIS WALL, NOTE THE SQAURE FOOTAGE
 OF THE WALL IS ONLY UP TO THE CEILING HEIGHT, NOT THE
 PARAPET HEIGHT.
  
 5C) UTILITIES, POTABLE WATER, SEWER, GAS AND ELECTRIAL
 UTILITIES COME FROM PALM BEACH LAKES WITH THE EXCEPTION
 OF TELECOMMUNICATIONS, THIS WILL APPEAR TO NEED TO
 CROSS OVER PARCEL A FOR TIE IN. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5D) THE SITE DOES HAVE ACCESS TO ROADWAYS BUT THE CIVIL
 PLANS SHOW ACCESS TO THIS PROPERTY VIA ANOTHER
 PROPERTY. THE SURVEY DOES HAVE NOTES ON THE DOCUMENT
 THERE MAYBE COVENENTS AND EASEMENTS NOT SHOWN ON THIS
 SURVEY. TO GAIN ACCESS FROM ANOTHER PROPERTY PLEASE
 PROVIDE THE CROSS ACCESS AGREEMENT AND SINCE THE
 PROPERTY LINE IS SO CLOSE TO THE BUILDING AND ALLOWABLE
 OPENINGS IS GREATLY REDUCED THERE MAYBE A RESTRIVTIVE
 COVENENT FOR THE SURROUNDING PARCEL A. IF THERE IS
 PLEASE PROVIDE DOCUMENTATION THAT WILL CLEAR UP
 COMMENTS 5A, 5B & 5C. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 6A) SHEET A3 ROOF PLAN SHOWS THE USE OF ROOF DRAINS AND
 THROUGH THE WALL OVER FLOW SCUPPERS. PLEASE PROVIDE THE
 ROOF DRAINAGE CALCULATIONS (INCHES /HR RAINFALL
 100-YEAR RAINFALL.) FBC-P FOR THE SIZING OF THE ROOF
 DRAINS AS WELL AS THE SECONDARY OVERFLOW WALL SCUPPERS.
 FBC-B 1503.4
  
 6B) SHEET A5 DETAIL # 8 INDICATES THE USE OF OVERFLOW
 (EMERGENCY OVERFLOW) DRAINS. THIS DETAIL IS SHOWN TO BE
 FLUSH WITH THE ROOF, PLEASE SHOW THE OVERFLOW SCUPPERS
 2 TO 4 INCHES ABOVE THE FINISH ROOF COVERING. 2014
 FBC-B 1504.3.2.1.
  
 6C) THE OVERFLOW SCUPPERS SHEET A5 DETAIL #8 ARE TO BE
 SIZED SEE FBC-B 1503.4.1. THE INSTALLATION AND SIZING
 OF SECONDARY EMERGENCY OVERFLOW DRAINS, LEADERS AND
 CONDUCTORS SHALL COMPLY WITH SECTIONS 1106 & 1107. AS
 APPLICABLE, OF CHPTER 11 OF THE FLORIDA BUILDING CODE,
 PLUMBING.
  
 7) NEITHER SHEET S-0 WHICH PROVIDES THE WIND DESIGN
 CRITERIA OR S2 ROOF FRAMING PLAN PROVIDE THE ACTUAL
 MEAN ROOF HEIGHT PRESSURES ARE DETERMINED FROM THE MEAN
 ROOF HEIGHT. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 8) SHEET S-2 ROOF PRESSURES SHOW THE MINIMUM SQUARE
 FEET OF 20 SQ.FT. THE MINIMUM SQUARE FEET FOR ROOF
 ATTACHMENT (FASTENER) IS AT 10 SQUARE FEET NOT 20
 SQUARE FEET PLEASE UPDATE PRESSURE CHART OTHERWISE
 PRESSURES ARE OK. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 9) SHEET S-5 THE SCALE NOT PROVIDED FOR THIS SHEET
 ASSUMED 3/16 TH INCH? 107,2,1,3 ADDITIONAL INFORMATION
 ISREQUIRED.
  
 10) PRESSURES FOR WALL ZONE 4 FOR WINDOWS AND DOORS
 APPEARS TO BE LOW EVEN FOR A MEAN ROOF HEIGHT OF 15
 FEET. FBC-B 1603.1.4.
  
 11) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C): STOREFRONTS,, WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 INSULATION (ROOF CURBS)
  
 12) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 13) THIS PERMIT IS FOR A SHELL BUILDING ONLY, EXEMPT
 FROM THE ENERGY CODE, NO RTU TO BE INSTALLED UNDER THIS
 PERMIT, ROOF TOP CURBS TO BE CAPPED. SHEET A5 DETAILS 6
 & 7 SHOW ROOF TOP INSULATION OF R-19 VALUE, IS THIS A
 R-19 VALUE AT THE ROOF DRAINS AS A MINIMUM? NOTE THIS
 COMMENT WILL BE A PROVISO: AT CONTRACTORS OWN RISK
 SINCE THERE IS NO ENERGY CALCULATION PROVIDING WHAT
 VALUE WILL BE PUT ON THE ROOF OP INSULATION USING THE
 WHOLE BUILDING METHOD 2014 FBC-ENERGY C101.4.8 EXEMPT
 BUILDINGS & C101.5.2 LOW ENERGY BUILDINGS.
  
 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved