Plan Review Notes
Plan Review Notes For Permit 15090229
Permit Number 15090229
Review Stop B
Sequence Number 1
Notes
Date Text
2015-09-16 17:03:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. HORIZONTAL INSTALLATIONS TYPICALLY HAVE BLOCK AS A
 SUBSTRATE (FILLED CELLS RATHER THAN FORMED AND POURED
 CONCRETE). PLEASE REVISE OR PROVIDE INFORMATION AS TO
 HOW IT HAS BEEN DETERMINED THAT THE SUBSTRATE IS
 CONCRETE (WOULD REQUIRE FORMED AND POURED COLUMNS ON
 BOTH SIDES OF EACH OPENING), FBC 5TH ED. RESIDENTIAL
 301.
  