2015-12-30 13:48:51 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC. |
| THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE |
| 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT |
| DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC |
| FIFTH EDITION. |
| |
| 2) THE PLANS REFERENCE THE 2008 NEC AND THE 2011 NEC IS |
| THE EDITION THAT APPLIES TO THIS PROJECT. |
| |
| 3) THE OCCUPANCY TYPE FOR ONE AND TWO FAMILY DWELLINGS |
| IS R-3 PER FBC SECTION 310. |
| |
| 4) SUBMIT TWO COPIES OF A SURVEY. FBC 107.2.1 |
| |
| 5) SHOW COMPLIANCE WITH FBC-R807.1 FOR ATTIC ACCESS. |
| |
| 6) DOUBLE UNDERLAYMENT IS REQUIRED FOR ASPHALT SHINGLE |
| ROOFS WITH SLOPES LESS THAN 4/12 PER FBC-R905.2.3 |
| |
| 7) THE ROOF ZONE PRESSURE DIAGRAM ON S-3 AND STRUCTURAL |
| NOTES ON S-2 HAVE -65 PSF FOR ROOF ZONES 2 AND 3. THE |
| CORNER (ZONE 3) UPLIFT PRESSURES SHOULD BE MORE. ONE |
| END OF THE ROOF IS A NOT A HIP. |
| |
| 8) THE STRUCTURAL NOTES ON S-2 HAVE THE COMPONENT AND |
| CLADDING PRESSURES FOR WALL ZONE 5 AS -50 PSF. THIS IS |
| A LITTLE LOW, IT SHOULD BE -54.1 PSF. FBC-R |
| |
| 9) FBC-R617.2.1 REQUIRES BUCKS TO EXTEND BEYOND THE |
| INTERIOR FACE OF THE WINDOW OR DOOR FRAME. THE DRYWALL |
| CAN NOT SUPPORT THE FRAME AS SHOWN IN THE DETAILS ON |
| S-3. |
| |
| 10) NOT ALL PRODUCT APPROVALS FOR SECTIONAL GARAGE |
| DOORS SPECIFY THE BUCKS TO WALL ATTACHMENT. SPECIFY THE |
| REQUIRED BUCK ATTACHMENT TO BE USED WHEN ONE IS NOT |
| PROVIDED IN THE PRODUCT APPROVAL. FBC 107.2.1 |
| |
| 11) SHOW COMPLIANCE WITH FBC-R311.7.8 FOR THE HANDRAILS |
| AT THE STAIRS. |
| |
| 12) SHOW COMPLIANCE WITH FBC-R312.1 FOR THE GUARDS AT |
| THE STAIRS. |
| |
| 13) PROVIDE COMPLETE STRUCTURAL DETAILS FOR THE STAIRS. |
| SPECIFY ALL CONNECTIONS, ANCHORS AND CONNECTORS. FBC |
| 107.2.1 |
| |
| 14) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF |
| THE DIFFERENT ROOFING MATERIALS, RIDGE VENT, |
| WINDOW/GLASS TYPES, STRUCTURAL MULLIONS AND EXTERIOR |
| DOOR TYPES. |
| |
| |
| |
| |
| |
| |
| |
| |