2016-04-11 14:11:59 | 2ND REVIEW: FBC 2014 |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |
| PLUMBING COMMENTS: |
| |
| 1. WASHING MACHINE AND OUTDOOR SHOWER SHALL BE VENTED |
| INDIVIDUALLY SHALL COMPLY WITH FBC RES. SEC. P3106.1 |
| INDIVIDUAL VENT PERMITTED. |
| EACH TRAP AND TRAPPED FIXTURE SHALL BE PERMITTED TO BE |
| PROVIDED WITH AN INDIVIDUAL VENT. THE INDIVIDUAL VENT |
| SHALL CONNECT TO THE FIXTURE DRAIN OF THE TRAP OR |
| TRAPPED FIXTURE BEING VENTED. |
| |
| 2. SECOND FLOOR THE KITCHEN SHALL CONNECT DOWNSTREAM OF |
| THE BATHROOM GROUP. SHALL COMPLY WITH FBC RES. SEC. |
| P3108.1 HORIZONTAL WET VENT PERMITTED. |
| ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| LOCATED ON THE SAME FLOOR LEVEL SHALL BE PERMITTED TO |
| BE VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL |
| BE CONSIDERED THE VENT FOR THE FIXTURES AND SHALL |
| EXTEND FROM THE CONNECTION OF THE DRY VENT ALONG THE |
| DIRECTION OF THE FLOW IN THE DRAIN PIPE TO THE MOST |
| DOWNSTREAM FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN |
| SHALL CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH |
| BEING WET VENTED OR SHALL HAVE A DRY VENT. EACH |
| WET-VENTED FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO |
| THE HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE |
| BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED |
| HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. |
| |
| 3. THE OUT DOOR SHOWER SHALL BE COVERED TO PREVENT |
| STORM WATER FROM DRAINING INTO SANITARY SYSTEM. PER |
| CODE OF ORDINANCES CITY OF WEST PALM BEACH, FLORIDA |
| SEC.9-126.(5) |
| |