2016-04-20 18:43:04 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ENERGY FORM CONTAINS NUMEROUS ERRORS. THE DESIGN | | LOCATION IS PALM BEACH COUNTY AND NOT MIAMI OR KEY | | BISCAYNE, THE INSULATION FOR THE FLOOR OVER THE GARAGE | | IS R-22 AND NOT R-11, THE SECOND FLOOR WALLS OF THE | | CONDITIONED SPACE HAVE R-22 INSULATION AND THE CEILING | | HAS R-38 PER THE PLANS. REVIEW AND COORDINATE THE | | ENERGY FORM WITH THE PLANS. THE FORMS ARE REQUIRED TO | | BE SIGNED AND DATED BY THE PREPARER AND THE | | OWNER/AGENT. FBC ENERGY R101.5.1.1.2 | | | | 2) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT | | SIZING CALCULATIONS AS REQUIRED BY FBCR-M1401.3. | | | | |
|