2016-04-20 18:43:04PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORM CONTAINS NUMEROUS ERRORS. THE DESIGN
 LOCATION IS PALM BEACH COUNTY AND NOT MIAMI OR KEY
 BISCAYNE, THE INSULATION FOR THE FLOOR OVER THE GARAGE
 IS R-22 AND NOT R-11, THE SECOND FLOOR WALLS OF THE
 CONDITIONED SPACE HAVE R-22 INSULATION AND THE CEILING
 HAS R-38 PER THE PLANS. REVIEW AND COORDINATE THE
 ENERGY FORM WITH THE PLANS. THE FORMS ARE REQUIRED TO
 BE SIGNED AND DATED BY THE PREPARER AND THE
 OWNER/AGENT. FBC ENERGY R101.5.1.1.2
  
 2) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS AS REQUIRED BY FBCR-M1401.3.
  
  