Plan Review Notes For Permit 15090130 |
Permit Number |
15090130 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-12-31 09:57:18 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ENERGY EFFICIENCY FORM THAT WAS SUBMITTED IS FOR | | THE 2010 FBC. THE CURRENT ONE IS FORM 405-14. FBC | | ENERGY R101.5.1.1.2 | | | | 2) THE ENERGY FORM CONTAINS NUMEROUS ERRORS. THE DESIGN | | LOCATION IS PALM BEACH COUNTY, THE INSULATION OF THE | | FLOOR OVER THE GARAGE IS NOT R-0, THE SECOND FLOOR | | WALLS OF THE CONDITIONED SPACE ARE WOOD FRAME. THE | | FORMS ARE REQUIRED TO BE SIGNED AND DATED BY THE | | PREPARER AND THE OWNER/AGENT. FBC ENERGY R101.5.1.1.2 | | | | 3) SPECIFY THE DUCT SIZES, GRILL SIZES AND CFMS AT EACH | | OUTLET. FBC 107.2.1 | | | | 4) SHOW THE LOCATION OF THE CONDENSING UNIT ON THE | | MECHANICAL PLANS. FBC 107.2.1 | | | | 5) PROVIDE AN ANCHORING DETAIL FOR THE CONDENSING UNIT | | TO SHOW THAT IT WILL WITHSTAND A 170 MPH WIND SPEED. | | FBCR-M1401.4 & FBC-R301.2.1 | | | | 6) DISCONNECTS ARE REQUIRED FOR BOTH THE AIR HANDLER | | AND THE CONDENSING UNIT. FBCR-E4101.5 | | | | 7) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS | | AND INSTALLATION INSTRUCTIONS FOR THE AIR HANDLER | | (PLA-A18BA4) TO SHOW THAT IT CAN BE USED WITH SUPPLY | | DUCTS. FBCR-M1401.1 | | |
|