Plan Review Notes
Plan Review Notes For Permit 15090130
Permit Number 15090130
Review Stop M
Sequence Number 1
Notes
Date Text
2015-12-31 09:57:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY EFFICIENCY FORM THAT WAS SUBMITTED IS FOR
 THE 2010 FBC. THE CURRENT ONE IS FORM 405-14. FBC
 ENERGY R101.5.1.1.2
  
 2) THE ENERGY FORM CONTAINS NUMEROUS ERRORS. THE DESIGN
 LOCATION IS PALM BEACH COUNTY, THE INSULATION OF THE
 FLOOR OVER THE GARAGE IS NOT R-0, THE SECOND FLOOR
 WALLS OF THE CONDITIONED SPACE ARE WOOD FRAME. THE
 FORMS ARE REQUIRED TO BE SIGNED AND DATED BY THE
 PREPARER AND THE OWNER/AGENT. FBC ENERGY R101.5.1.1.2
  
 3) SPECIFY THE DUCT SIZES, GRILL SIZES AND CFMS AT EACH
 OUTLET. FBC 107.2.1
  
 4) SHOW THE LOCATION OF THE CONDENSING UNIT ON THE
 MECHANICAL PLANS. FBC 107.2.1
  
 5) PROVIDE AN ANCHORING DETAIL FOR THE CONDENSING UNIT
 TO SHOW THAT IT WILL WITHSTAND A 170 MPH WIND SPEED.
 FBCR-M1401.4 & FBC-R301.2.1
  
 6) DISCONNECTS ARE REQUIRED FOR BOTH THE AIR HANDLER
 AND THE CONDENSING UNIT. FBCR-E4101.5
  
 7) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE AIR HANDLER
 (PLA-A18BA4) TO SHOW THAT IT CAN BE USED WITH SUPPLY
 DUCTS. FBCR-M1401.1
  