Plan Review Notes
Plan Review Notes For Permit 15090106
Permit Number 15090106
Review Stop P
Sequence Number 3
Notes
Date Text
2016-04-14 13:35:371) A MINIMUM OF TWO TOILET ROOMS ARE REQUIRED ( ONE
 MALE, ONE FEMALE) PER TABLE 403.1 OF 2014 FPC.( THIS
 COULD NOT BE DETERMINED PREVIOUSLY DUE TO THE INCORRECT
 OCCUPANCY THAT WAS NOTED ON THE PLANS). IF THERE ARE
 ADDITIONAL SANITARY FACILITIES WITHIN 500 FEET OF THIS
 STRUCTURE, THEY MIGHT BE ABLE TO BE USED TO MEET THIS
 REQUIREMENT. TWO COPIES OF A SITE PLAN SHOWING THE
 LOCATION AND DISTANCE OF THE ADDITIONAL FACILITIES
 SHALL BE SUBMITTED IN ORDER TO MAKE A DECISION ON THIS
 REQUIREMENT. THERE WAS NO DOCUMENT IN THE RESUBMITTAL
 PACKAGE SHOWING ADDITIONAL SANITARY FACILITIES.
 2) SUBMIT THE SQUARE FEET OF THE POOL WATER SURFACE
 AREA. SKIMMERS MAY BE UTILIZED WHEN THE POOL WATER
 SURFACE IS 1000 SQUARE FEET OR LESS PER 2014 FBC SEC.
 454.1.6.5.3.2. THIS WAS ANSWERED IN THE NARRATIVE BUT I
 DID NOT SEE WHERE THIS NOTE WAS PLACED ON THE PLANS.
  
  