Plan Review Notes For Permit 15090106 |
Permit Number |
15090106 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-04-07 09:03:43 | 1301 SUMMIT BOULEVARD - ALLIGATOR EXHIBIT | | PERMIT #15090106 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PLAN INDICATES THIS PROJECT IS A LEVEL 3 ALTERATION | | AFFECTING OVER 50% OF THE EXISTING BUILDING AREA; | | THEREFORE, PER NFPA 101 SECTION 43.5.2.3 WHERE THE | | TOTAL AREA OF ALL THE REHABILITATION WORK AREAS | | INCLUDED IN A MODIFICATION EXCEEDS 50 PERCENT OF THE | | AREA OF THE BUILDING, THE WORK SHALL BE CONSIDERED AS A | | RECONSTRUCTION AND SHALL COMPLY WITH THE REQUIREMENTS | | OF SECTION 43.6 FOR THE APPLICABLE OCCUPANCY. | | 101-43.6.4.2 ON ANY STORY WITH REHABILITATION WORK | | AREAS INVOLVING OVER 50 PERCENT OF THE AREA OF THE | | STORY, A SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT | | THE STORY IN ACCORDANCE WITH THE REQUIREMENTS OF OTHER | | SECTIONS OF THIS CODE APPLICABLE TO NEW CONSTRUCTION | | FOR THE OCCUPANCY. | | | | PER NFPA 150 STRUCTURES HOUSING TYPE A ANIMALS | | (REPTILES) SHALL BE PROTECTED THROUGHOUT WITH AN | | AUTOMATIC SPRINKLER SYSTEM. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | | | | | | | |
|