Plan Review Notes
Plan Review Notes For Permit 15090106
Permit Number 15090106
Review Stop P
Sequence Number 2
Notes
Date Text
2016-02-11 06:34:271) SUBMIT THE OCCUPANT LOAD FOR THIS SPACE SINCE THE
 OCCUPANCY HAS BEEN IDENTIFIED. COMPLY WITH 2014 FBC
 TABLE .1004.1.2.
 2) A MINIMUM OF TWO TOILET ROOMS ARE REQUIRED ( ONE
 MALE, ONE FEMALE) PER TABLE 403.1 OF 2014 FPC.( THIS
 COULD NOT BE DETERMINED PREVIOUSLY DUE TO THE INCORRECT
 OCCUPANCY THAT WAS NOTED ON THE PLANS). IF THERE ARE
 ADDITIONAL SANITARY FACILITIES WITHIN 500 FEET OF THIS
 STRUCTURE, THEY MIGHT BE ABLE TO BE USED TO MEET THIS
 REQUIREMENT. TWO COPIES OF A SITE PLAN SHOWING THE
 LOCATION AND DISTANCE OF THE ADDITIONAL FACILITIES
 SHALL BE SUBMITTED IN ORDER TO MAKE A DECISION ON THIS
 REQUIREMENT.
 3) HOT/TEMPERED WATER IS REQUIRED TO THE LAVATORY. SHOW
 THIS ON THE WATER PIPING RISER.2014 FPC SEC. 607.1.
 4) SHT. A-400 - DETAILS #1 & # 3 THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE PER 2014
 FBC-ACCESS. SEC. 609.4.
 5) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2014
 FBC-ACCESS. SEC.307.2. AN OPTIONAL SKIRT MAY BE
 REQUIRED TO KEEP THE LEADING EDGE BELOW 27 INCHES.
 6) SUBMIT THE SQUARE FEET OF THE POOL WATER SURFACE
 AREA. SKIMMERS MAY BE UTILIZED WHEN THE POOL WATER
 SURFACE IS 1000 SQUARE FEET OR LESS PER 2014 FBC SEC.
 454.1.6.5.3.2.
  