Plan Review Notes
Plan Review Notes For Permit 15090106
Permit Number 15090106
Review Stop P
Sequence Number 1
Notes
Date Text
2015-09-11 09:45:071) SHT. A-001 - CODE INFORMATION - THE PLANS REFERENCE
 THE 2010 FBC. THE CODES IN EFFECT ARE THE 2014
 EDITIONS. REVISE THE NOTES.
 2) CLARIFY AS TO HOW THIS PROJECT CAN BE CLASSIFIED AS
 A "U" OCCUPANCY WHEN IT IS A PUBLIC EXHIBIT LOCATED IN
 A ZOO. WPB AMEND. TO FBC SEC. 107.2.1, 2014 FBC CHAPTER
 3.
 3) SUBMIT A COMPLETE PIPING RISER DIAGRAM FOR THE WATER
 FILTRATION SYSTEM. SUBMIT MANUF. SPECS FOR THE MAIN
 DRAIN GRATES, THE PUMP, HEAT PUMP, AND THE OZONE
 SYSTEM. SHOW ALL PIPE SIZES. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) A BACKFLOW PREVVENTION DEVICE IS REQD. ON THE WATER
 SUPPLY PER THE CWPB UTILITIES DEPT. CROSS CONNECTION
 CONTROL MANUAL.
 5) SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATIONS FOR
 THE INSTANTANEOUS WATER HEATER.
 6) A MINIMUM OF 2 DRINKING FOUNTAINS ARE REQD. PER THE
 2014 FPC TABLE 403.1 FOOTNOTE # (E) & 2014
 FBC-ACCESSIBILITY SEC. 211.2.
 7) EXPLAIN THE PURPOSE OF THE FLOOR SINK AND THE FLOOR
 DRAIN IN THE POOL. THEY CANNOT BE USED TO DRAIN THE
 POOL. DISCHARGE TO THE SANITARY SYSTEM SHALL BE THROUGH
 AN AIR GAP.2014 FBC SEC. 454.1.6.5.15.
 8) PROVIDE DETAILS FOR MAKEUP WATER. WPB AMEND. TO FBC
 SEC. 107.2.1.
  
  