Plan Review Notes
Plan Review Notes For Permit 15090106
Permit Number 15090106
Review Stop M
Sequence Number 1
Notes
Date Text
2015-09-14 11:35:421ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090106
 9/14/15
  
 1) A NEW DX SPLIT AC SYSTEM IS SHOWN ON THE PLANS-
 PLEASE REVISE NEW WORK NOTE #1 ON SHEET M2 INDICATING
 REBALANCING AN EXISTING RTU.
 2) REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION
 AND PROVIDE AC COOLING AND HEATING CALCULATIONS:
 CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 3) PROVIDE AN EQUIPMENT SCHEDULE FOR THE HWB-1 HOT
 WATER BOILER.
 4) PLEASE SHOW THE LOCATION OF THE RFM-1 MANIFOLD AS
 SHOWN IN THE RADIANT SCHEDULE.
 5) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL
 PLANS FOR THE NEW AHU- REFER TO SECTION 307 FBC-14
 MECHANICAL.
 6) PROVIDE PIPE PROTECTION DETAILS FOR THE HOT WATER
 PIPING. INDICATE THE TYPE AND THICKNESS OF CONDUIT AND
 SLEEVING TO BE USED FOR THE UNDERGROUND/UNDERSLAB
 INSTALLATION- REFER TO SECTIONS 305.1.1 FBC-14
 PLUMBING.
 7) PROVIDE THE BURIAL DEPTH AND DEPTH OF BACKFILL FOR
 THE HOT WATER PIPING- REFER TO SECTION 306.3 FBC-14
 PLUMBING.
 8) SUBMIT PRODUCT DATA (CUT) SHEETS FOR THE PEX PIPING,
 AND FOAM INSULATION.
 9) SUBMIT TWO COPIES OF FLORIDA PRODUCT APPROVALS OR
 MIAMI-DADE NOA'S FOR THE LOUVERS- SEE FLORIDA
 DEPARTMENT DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3.
 10) REFER TO SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION AND SHOW COMPLIANCE: SHUTOFF DAMPER
 CONTROLS.
 BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS SHALL BE
 EQUIPPED WITH MOTORIZED DAMPERS THAT WILL AUTOMATICALLY
 SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE.
 EXCEPTIONS:
 1. GRAVITY DAMPERS SHALL BE PERMITTED IN BUILDINGS LESS
 THAN THREE STORIES IN HEIGHT.
 2. GRAVITY DAMPERS SHALL BE PERMITTED FOR BUILDINGS OF
 ANY HEIGHT LOCATED IN CLIMATE ZONES 1, 2 AND 3.
 3. GRAVITY DAMPERS SHALL BE PERMITTED FOR OUTSIDE AIR
 INTAKE OR EXHAUST AIRFLOWS OF 300 CFM (0.14 M3/S) OR
 LESS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  