2015-09-14 11:35:42 | 1ST REVIEW: FBC 2014 MECHANICAL |
| PERMIT #15090106 |
| 9/14/15 |
| |
| 1) A NEW DX SPLIT AC SYSTEM IS SHOWN ON THE PLANS- |
| PLEASE REVISE NEW WORK NOTE #1 ON SHEET M2 INDICATING |
| REBALANCING AN EXISTING RTU. |
| 2) REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION |
| AND PROVIDE AC COOLING AND HEATING CALCULATIONS: |
| CALCULATION OF HEATING AND COOLING LOADS. |
| DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE |
| PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR |
| ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE |
| COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT |
| WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE |
| MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE |
| SIZING CALCULATION SHALL BE SUBMITTED WITH THE |
| APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND |
| COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD |
| REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY |
| SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE |
| WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK. |
| ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN |
| APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE |
| DESIGN PARAMETERS SPECIFIED IN CHAPTER 3. |
| 3) PROVIDE AN EQUIPMENT SCHEDULE FOR THE HWB-1 HOT |
| WATER BOILER. |
| 4) PLEASE SHOW THE LOCATION OF THE RFM-1 MANIFOLD AS |
| SHOWN IN THE RADIANT SCHEDULE. |
| 5) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL |
| PLANS FOR THE NEW AHU- REFER TO SECTION 307 FBC-14 |
| MECHANICAL. |
| 6) PROVIDE PIPE PROTECTION DETAILS FOR THE HOT WATER |
| PIPING. INDICATE THE TYPE AND THICKNESS OF CONDUIT AND |
| SLEEVING TO BE USED FOR THE UNDERGROUND/UNDERSLAB |
| INSTALLATION- REFER TO SECTIONS 305.1.1 FBC-14 |
| PLUMBING. |
| 7) PROVIDE THE BURIAL DEPTH AND DEPTH OF BACKFILL FOR |
| THE HOT WATER PIPING- REFER TO SECTION 306.3 FBC-14 |
| PLUMBING. |
| 8) SUBMIT PRODUCT DATA (CUT) SHEETS FOR THE PEX PIPING, |
| AND FOAM INSULATION. |
| 9) SUBMIT TWO COPIES OF FLORIDA PRODUCT APPROVALS OR |
| MIAMI-DADE NOA'S FOR THE LOUVERS- SEE FLORIDA |
| DEPARTMENT DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3. |
| 10) REFER TO SECTION C403.2.4.4 FBC-14 ENERGY |
| CONSERVATION AND SHOW COMPLIANCE: SHUTOFF DAMPER |
| CONTROLS. |
| BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS SHALL BE |
| EQUIPPED WITH MOTORIZED DAMPERS THAT WILL AUTOMATICALLY |
| SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE. |
| EXCEPTIONS: |
| 1. GRAVITY DAMPERS SHALL BE PERMITTED IN BUILDINGS LESS |
| THAN THREE STORIES IN HEIGHT. |
| 2. GRAVITY DAMPERS SHALL BE PERMITTED FOR BUILDINGS OF |
| ANY HEIGHT LOCATED IN CLIMATE ZONES 1, 2 AND 3. |
| 3. GRAVITY DAMPERS SHALL BE PERMITTED FOR OUTSIDE AIR |
| INTAKE OR EXHAUST AIRFLOWS OF 300 CFM (0.14 M3/S) OR |
| LESS. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |