2015-11-19 10:25:26 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| 1. THE CODE INFORMATION BLOCK ON THE FRONT SHEET |
| REFERENCES NON APPLICABLE OR NONEXISTENT CODES. THE |
| APPLICABLE CODES FOR THIS PROJECT ARE THE 5TH EDITION |
| OF THE 2014 FBC AND THE 2011 EDITION OF THE NEC. |
| 2. NEC 110.16 REQUIRES THAT THE PANELBOARDS BE MARKED |
| WITH THE ARC-FLASH HAZARD WARNING LABELS. |
| 3. NEC 406.9(B) STATES THAT ALL 15 - 20 AMP RECEPTACLES |
| INSTALLED IN WET LOCATIONS SHALL IN ADDITION TO THE |
| IN-USE TYPE COVER BE LISTED FOR THE PURPOSE AS |
| WEATHER-RESISTANT. TYPE. |
| 4. NEC 408.4(B) ALL PANELS SHALL BE MARKED TO INDICATE |
| THE LOCATION OF THE SOURCE OF POWER. |
| 5. NEC 422.52 REQUIRES THAT ELECTRIC WATER COOLERS BE |
| CONNECTED TO A GFCI PROTECTED OUTLET. |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |