Plan Review Notes
Plan Review Notes For Permit 15090106
Permit Number 15090106
Review Stop B
Sequence Number 1
Notes
Date Text
2015-09-27 07:49:01BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090106
 ADD: 1301 SUMMIT BLVD./ RENOVATIONS TO WHITE ALLIGATOR
 EXHIBIT.
 CONT: CAG CONSTRUCTION
 TEL: ( 321)622-6900
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. SEPT. 27/ 2015
 ACTION: DENIED
  
 1) THE COVERSHEET INDICATES THE PLANS WERE DESIGNED
 UNDER THE 2010 FBC. PLEASE NOTE PLANS SUBMITTED ON OR
 AFTER JUNE 30TH/ 2015 ARE TO BE DESIGNED UNDER THE 2014
 FBC, 5TH EDITION OF THE FLORIDA BUILDING CODE.
  
 2) SHEET A-001 THE COVER SHEET LIST THE OCCUPANCY TYPE
 AS U- OCCUPANCY (LIVESTOCK SHELTER) , IT WOULD APPEAR
 SINCE THE PUBLIC STOPS AND VIEWS THE VARIOUS DISPLAYS
 THE OCCUPANCY WOULD BE IN LINE OF A MUSEUM OR AN A3
 OCCUPANCY. THE PUBLIC WOULD NOT BE GOING AROUND IN A
 LIVE STOCK SHELTER VIEWING A DISPLAY.
  
 3) PLEASE PROVIDE A SURVEY WITH THE PROPOSED LOCATION
 OF STRUCTURES, THE PROPERTY IS LOCATED IN AN A-7 FLOOD
 ZONE. FLOOD ZONE CERTIFICATES
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. FINISH
 FLOOR ELEVATION OF 12 FT. -
 6 INCHES OR HIGHER.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31/2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 THE PERMIT APPLICATION INDICATES THE PROPOSED VALUE OF
 THIS PROJECT IS $200,000.00 DOLLARS IN VALUE. PLEASE
 PROVIDE COST IN THE PAST FOR THIS STRUCTURE AND THE
 ESTIMATED VALUE OF THE STRUCTURE AS PRESENTLY
 CONFIGURED. THE W. P. B. MUNI CODE DEFINITIONS:
 SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF
 REPAIRS, RECONSTRUCTION, ALTERATION, OR IMPROVEMENTS TO
 A STRUCTURE, TAKING PLACE DURING THE LIFE OF A
 STRUCTURE, IN WHICH THE CUMULATIVE COST EQUALS OR
 EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE
 STRUCTURE. THE MARKET VALUE OF THE STRUCTURE SHOULD BE
 THE APPRAISED VALUE OF THE STRUCTURE PRIOR TO THE START
 OF THE INITIAL REPAIR OR IMPROVEMENT, OR IN THE CASE OF
 DAMAGE, THE VALUE OF THE STRUCTURE PRIOR TO THE DAMAGE
 OCCURRING. FOR THE PURPOSES OF THIS DEFINITION,
 "SUBSTANTIAL IMPROVEMENT" IS CONSIDERED TO OCCUR WHEN
 THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR
 OTHER STRUCTURAL PART OF THE BUILDING COMMENCES,
 WHETHER OR NOT THAT ALTERATION AFFECTS THE EXTERNAL
 DIMENSIONS OF THE STRUCTURE. THE TERM "SUBSTANTIAL
 IMPROVEMENT" DOES NOT, HOWEVER, INCLUDE ANY IMPROVEMENT
 OF A STRUCTURE TO COMPLY WITH EXISTING HEALTH,
 SANITARY, OR SAFETY CODES WHICH ARE SOLELY NECESSARY TO
 ENSURE SAFE LIVING CONDITIONS.
  
 SEC. 94-546. - PROVISIONS FOR FLOOD HAZARD REDUCTION.
 (2) NONRESIDENTIAL CONSTRUCTION. ALL NEW CONSTRUCTION
 OR SUBSTANTIAL IMPROVEMENT OF ANY COMMERCIAL,
 INDUSTRIAL OR OTHER NONRESIDENTIAL STRUCTURE SHALL
 EITHER HAVE THE LOWEST FLOOR, INCLUDING BASEMENT,
 ELEVATED TO THE LEVEL OF SIX INCHES ABOVE THE BASE
 FLOOD ELEVATION OR, TOGETHER WITH ATTENDANT UTILITY AND
 SANITARY FACILITIES, BE FLOODPROOFED SO THAT BELOW SIX
 INCHES ABOVE THE FLOOD BASE LEVEL THE STRUCTURE IS
 WATERTIGHT, WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE
 PASSAGE OF WATER AND WITH STRUCTURAL COMPONENTS HAVING
 THE CAPABILITY OF RESISTING HYDROSTATIC AND
 HYDRODYNAMIC LOADS AND EFFECTS OF BUOYANCY. A
 REGISTERED PROFESSIONAL ENGINEER OR ARCHITECT SHALL
 CERTIFY THAT THE STANDARDS OF THIS SUBSECTION ARE
 SATISFIED. SUCH CERTIFICATION SHALL BE PROVIDED TO THE
 CITY ENGINEER.
  
 NOTE IF THE EXISITNG STRUCTURE IS BELOW THE BASE FLOOD
 ELEVATION OF 12 FT. 6 INCHES AND SUBSTANIAL
 IMPROVEMENTS ARE OVER THE 50% OF THE ASSESSED VALUE OF
 THE STRUCTURE ANOTHE OPTION IS TO INSTALL FLOOD VENTS
 TO ALLOW THE WATERS TO FLOW THROUGH AND RECEDE WHEN THE
 FLOOD STAGE IS OVER. PLEASE NOTE ANY NEW WORK
 RESTROOMS, ELECTRICAL EQUIPMENT & A/C CONDENSORS WILL
 NEED TO BE SET ABOVE THE 12FT. 6 INCH ELEVATION AND
 FLOOD ELEVATIONS ARE REQUIED.
  
 4) SHEET S0.1 UNDER THE HEADING OF FOUNDATIONS
 INDICATES THERE IS TO HAVE A SOILS REPORT INVESTIGATION
 THIS SITE HAS QUESTIONABLE SOILS IN BEARING CAPACITY.
 THIS REVIEW CYCLE NO SUCH REPORT HAS BEEN SUBMITTED.
 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS
 ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY
 OF THE SOILS WILL BE.
  
 5) SHEET S0.1 LIST THE 2014 FBC-B AND ASCE 7-10,
 EXPOSURE C FOR THE WIND DESIGN. IN THE LOWER RIGHT
 SECTION OF THIS SAME SHEET THE WIND DESIGN IS INDICATED
 AS ASCE 7-98 125 MPH, EXPOSURE B AND ALL ASSOCIATED
 PRESSURES ARE BLANK!!!!!!!!!!!
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1.) ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 5.2.) RISK CATEGORY.
  
 5.3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 5.4.) APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 6) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (F) SKYLIGHT REPAIR OR REPLACEMENT?
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  