Plan Review Notes For Permit 15090101 |
Permit Number |
15090101 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-09-11 12:57:17 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15090101 | | 9/11/15 | | | | 1) PROVIDE PIPE PROTECTION DETAILS FOR THE CHILLED | | WATER PIPING. INDICATE THE TYPE AND THICKNESS OF | | CONDUIT AND SLEEVING TO BE USED FOR THE | | UNDERGROUND/UNDERSLAB INSTALLATION- REFER TO SECTIONS | | 305.1.1 FBC-14 PLUMBING. | | 2) PROVIDE THE BURIAL DEPTH AND DEPTH OF BACKFILL FOR | | THE CHILLED WATER PIPING- REFER TO SECTION 306.3 FBC-14 | | PLUMBING. | | 3) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE | | CHILLER PAD, AND WIND LOAD TIE DOWN ENGINEERING FOR | | MOUNTING THE CHILLER TO THE SLAB- SEE SECTION 301.15 | | MECHANICAL. | | 4) SUBMIT PRODUCT DATA (CUT) SHEETS FOR THE CHILLER AND | | THE UPONOR TYPE A PEX PIPING, AND FOAM INSULATION. | | 5) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | ZOOKEEPER AREAS IN THE PANTHER AND OTTER BUILDINGS- | | REFER TO TABLE 403.3 FBC-14 MECHANICAL. INDICATE HOW | | THE DESIGN USING LOUVERED VENT OPENINGS IS PROVIDING | | VENTILATION AIR FOR THOSE AREAS, AND INDICATE HOW THE | | VENT OPENINGS WERE SIZED. | | 6) SUBMIT TWO COPIES OF FLORIDA PRODUCT APPROVALS OR | | MIAMI-DADE NOA'S FOR THE LOUVERS- SEE FLORIDA | | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|