2015-11-05 09:34:00 | THE PLANS WERE INADVERTENTLY/ERRONEOUSLY STAMPED AS |
| APPROVED, BUT THE BELOW MENTIONED ITEMS SHALL BE |
| CORRECTED AND PLANS RE-SUBMITTED FOR AN APPROVAL. |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION |
| OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION |
| OF THE 2014 FBC, (FLORIDA BUILDING CODE) AS APPLICABLE |
| AND BELOW ARE THE DEFICIENCIES NOTED. |
| THOUGH THE PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN |
| ADDRESSED, THE NEW PLANS HAVE A COUPLE OF ITEMS NEEDING |
| CORRECTION: |
| |
| 1. PER NEC 110.16 ALL ELECTRICAL EQUIPMENT AND PANELS |
| SHALL BE LABELED WITH THE ARC-FLASH HAZARD WARNING |
| LABEL. |
| 2. THE QUOTED 2010 EDITION OF THE ELECTRICAL CODE DOES |
| NOT EXIST; THEREFORE COMPLIANCE WITH SAME IS NOT |
| POSSIBLE. THE CURRENT ELECTRICAL CODE IN EFFECT IS THE |
| 2011 EDITION OF THE NEC. |
| 3. PER NEC 406.9(B) IN ADDITION TO THE WEATHER-PROOF |
| COVERS ALL 15 ? 20 AMP 120 -240 VOLT NON-LOCKING |
| RECEPTACLES INSTALLED IN WET LOCATIONS SHALL BE LISTED |
| ?WR? WEATHER RESISTANT. |
| 4. ALL LIGHTING HAS TO COMPLY WITH THE REQUIREMENTS OF |
| SECTION C405 OF THE FBC-ENERGY CONSERVATION CODE. |
| 5. NEC 408.4(B) ALL PANEL SHALL BE MARKED INDICATING |
| THE LOCATION OF THEIR SOURCE OF POWER (DISCONNECT). |
| |
| THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN |
| MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED |
| FOR ANOTHER REVIEW. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |