Date |
Text |
2015-09-26 16:12:54 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15090101 |
| ADD: 1301 SUMMIT BLVD./ PANTHER RENOVATIONS |
| CONT: TBD |
| TEL: ( ????????? |
| E-MAIL: ????????? |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SUN. SEPT. 27/ 2015 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION UNDER THE HEADING OF VALUE, |
| NOT FILED IN. 108.3* BUILDING PERMIT VALUATION. IF, IN |
| THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED |
| VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) THE COVERSHEET INDICATES THE PLANS WERE DESIGNED |
| UNDER THE 2010 FBC. PLEASE NOTE PLANS SUBMITTED ON OR |
| AFTER JUNE 30TH/ 2015 ARE TO BE DESIGNED UNDER THE 2014 |
| FBC, 5TH EDITION OF THE FLORIDA BUILDING CODE. |
| |
| 3) THE PERMIT APPLICATION INDICATES THIS PERMIT IS FOR |
| ONLY THE PANTHER RENOVATIONS. BOTH THE ARCHITECTURAL |
| AND STRUCTURAL SHEETS SHOW NEW BUILDING FOUNDATIONS AND |
| STRUCTURAL SHEETS FOR THIS BUILDING (S-1) AND OTHER |
| BUILDINGS SEE SHEET (S-4- OTTER HOUSING?) . PLEASE NOTE |
| ON THE PERMIT APPLICATION IF THESE OTHER STRUCTURES ARE |
| TO BE INCLUDED UNDER THE SCOPE OF WORK TO BE COMPLETED |
| UNDER THIS PERMIT. IF THESE OTHER SHEETS ARE NOT |
| INCLUDED UNDER THE SCOPE OF WORK, PLEAE EITHER VOID THE |
| SHEETS, "X" OUT THE DETAILS NOT COVERED UNDER THIS |
| PERMIT OR REMOVE THE SHEETS IN THERE INTIRETY.107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 4) PLEASE PROVIDE A SURVEY WITH THE PROPOSED LOCATION |
| OF STRUCTURES, THE PROPERTY IS LOCATED IN AN A-7 FLOOD |
| ZONE. FLOOD ZONE CERTIFICATES |
| FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES |
| SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. FINISH |
| FLOOR ELEVATION OF 12 FT. - |
| 6 INCHES OR HIGHER. |
| |
| DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| HEIGHT. |
| (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| ELEVATION CERTIFICATE IS REQUIRED |
| (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| ATTENDANTS |
| A/C PADS OR OTHER SLABS FOR GENERATORS |
| FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| JULY 31/2015 |
| FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| |
| 5) SHEET S0.1 UNDER THE HEADING OF FOUNDATIONS |
| INDICATES THERE IS TO HAVE A SOILS REPORT INVESTIGATION |
| THIS SITE HAS QUESTIONABLE SOILS IN BEARING CAPACITY. |
| THIS REVIEW CYCLE NO SUCH REPORT HAS BEEN SUBMITTED. |
| 2014 FBC-B 1803.5.2 QUESTIONABLE SOILS. THIS REPORT IS |
| ALSO TO PROVIDE WHAT THE MINIMUM SAFE BEARING CAPACITY |
| OF THE SOILS WILL BE. |
| |
| 6) SHEET S0.1 LIST THE 2014 FBC-B AND ASCE 7-10, |
| EXPOSURE C FOR THE WIND DESIGN. IN THE LOWER RIGHT |
| SECTION OF THIS SAME SHEET THE WIND DESIGN IS INDICATED |
| AS ASCE 7-98 125 MPH, EXPOSURE B AND ALL ASSOCIATED |
| PRESSURES ARE BLANK!!!!!!!!!!! |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 6.1.) ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND |
| GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND |
| SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 6.2.) RISK CATEGORY. |
| |
| 6.3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| |
| 6.4.) APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 6.5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| 7A) PROVIDE PRODUCT APPROVALS FOR THE FOLLOWING ITEMS. |
| 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| |
| 7B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| |
| 8) SHEET A-001 THE COVER SHEET LIST THE OCCUPANCY TYPE |
| AS S-1 STORAGE, IT WOULD APPEAR SINCE THE PUBLIC STOPS |
| AND VIEWS THE VARIOUS DISPLAYS THE OCCUPANCY WOULD BE |
| IN LINE OF A MUSEUM OR AN A3 OCCUPANCY. THE PUBLIC |
| WOULD NOT BEGOING AROUND IN A WAREHOUSE VIEWING |
| DISPLAYS. |
| |
| 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |